background image

4

•  When connecting refrigerant linesets together, it is 

recommended that dry nitrogen be flowing through the 

joints during brazing to prevent internal oxidation and 

scaling.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. If precise forming of refrigerant lines is 

required, a copper tubing bender is recommended. Avoid 

sharp bends and contact of the refrigerant lines with metal 

surfaces.

•  Refrigerant tubing should be supported in a manner 

that the tubing will not vibrate or abrade during system 

operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure 

that the field installed refrigerant containing components 

of the system have been installed in accordance with 

these instructions and sound installation practices to 

insure reliable system operation and longevity.

•  The maximum recommended interconnecting refrigerant 

line lengths is 75 ft. and the vertical elevation difference 

between the indoor and outdoor sections should not 

exceed 20 ft.

•  A filter dryer is provided with the unit and must be 

installed in the liquid line of the system. If the installation 

replaces a system with a filter dryer already present in the 

liquid line, the filter dryer must be replaced with the one 

supplied with the unit. The filter dryer must be installed 

in strict accordance with the manufacturer’s installation 

instructions.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 

with the manufacturer’s installation instructions.

ELECTRICAL WIRING

 WARNING:

To avoid risk of electrical shock, personal 

injury, or death, disconnect all electrical power 

to the unit before performing any maintenance 

or service. The unit may have more than one 

electrical supply.

Label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause 

improper and dangerous operation.

•  All electrical connections must be in compliance with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For Canadian installations the electrical connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram See 

Figure 6 (page 9)

Figure 7 (page 10)

Figure 8 (page 11)

Figure 9 (page 12)

Figure 10 

(page  13)

, & 

Figure 11 (page 14)

. Inspect for loose 

connections.

Line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 

become familiar with the wiring diagram before making 

any electrical connections to the outdoor unit.

• 

An electrical disconnect must be located within sight 
of and readily accessible to the unit

. This switch shall 

be capable of electrically de-energizing the outdoor unit.

•  Line voltage to the unit should be supplied from a dedicated 

branch circuit containing the correct fuse or circuit breaker 

for the unit. Incoming field wiring and minimum size of 

electrical conductors and circuit protection must be in 

compliance with information listed on the outdoor unit 

data label. Any other wiring methods must be acceptable 

to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagram / 

schematic for identification and location of outdoor unit 

field wiring interfaces See 

Figure 6 (page 9)

Figure 7 

(page  10)

Figure 8 (page 11)

Figure 9 (page 12)

Figure 10 (page 13)

, & 

Figure 11 (page 14)

. Make 

all electrical connections in accordance with all applicable 

codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. See 

the unit rating plate for minimum circuit ampacity and 

maximum overcurrent protection limits.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect the 

line-voltage leads to the terminals on the contactor inside 

the control compartment.

•  Use only copper wire for the line voltage power supply to 

this unit in strict accordance of the NEC (ANSI/NFPA 70), 

applicable local codes, and the instructions provided with 

the equipment. Use proper code agency listed conduit 

and a conduit connector for connecting the supply wires 

to the unit. Use of rain tight conduit is recommended.

•  208/230 Volt units are shipped from the factory wired for 

230 volt operation. For 208V operation, remove the lead 

from the transformer terminal marked 240V and connect 

it to the terminal marked 208V.

•  Optional equipment requiring connection to the power or 

control circuits must be wired in strict accordance of the 

NEC (ANSI/NFPA 70), applicable local codes, and the 

instructions provided with the equipment.

CoreSense

TM

 Diagnostics Module

(Select Models Only)

The CoreSense

TM

 Diagnostics Module (

Figure 2

) is a 

breakthrough innovation for troubleshooting heat pump and 

air conditioning system failures. The module installs easily 

in the electrical box of the outdoor unit near the compressor 

contactor.By using the compressor as a sensor, CoreSense 

Diagnostics helps the service technician more accurately 

troubleshoot system and compressor fault conditions.
A flashing LED indicator communicates the ALERT code 

and a diagnostic key is also imprinted on the side of the 

module to quickly direct the technician to the root cause of 

Содержание SA1BF4M2SN Series

Страница 1: ...IMPORTANT SAFETY INFORMATION 2 AIR CONDITIONER INSTALLATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Ground Level 3 Roof Mount 3 Connec...

Страница 2: ...nt Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure This unit is designed for outdoor installations only and sho...

Страница 3: ...n 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit Sufficient clearance for unobstructed airflow...

Страница 4: ...for loose connections Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit The installer should become familiar with the wiring diagram before making...

Страница 5: ...instructions supplied with the thermostat and the indoor equipment Typical AC and thermostat hookups are shown in Figure 3 The outdoor unit is designed to operate from a 24 VAC Class II control circu...

Страница 6: ...ify that it is warmer than ambient temperature Listen for any unusual noises Ifunusualsoundsoccur determinethesourceofthenoise and correct as necessary AIR CONDITIONER MAINTENANCE WARNING To prevent e...

Страница 7: ...unit Use only gage line sets which have a Schrader depression device present to actuate the valve Ahigh pressureswitchisfactory installedandlocatedinthe liquidlineinternaltotheoutdoorunit Theswitchis...

Страница 8: ...the recommended superheat value in the table then ADD refrigerant For TXV systems If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table then ADD re...

Страница 9: ...uitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and opti...

Страница 10: ...R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Crankcase He...

Страница 11: ...0 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR L FAN REL...

Страница 12: ...e unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire...

Страница 13: ...HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz NOTES 1 Disconnect all power before...

Страница 14: ...rcuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducteurs en cui...

Страница 15: ...m 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant...

Страница 16: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...allon MO Nortek Global HVAC LLC 2018 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when or...

Отзывы: