background image

5

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect 

the line-voltage leads to the terminals on the contactor 

inside the control compartment.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in 

Table 1

. Use proper code agency 

listed conduit and a conduit connector for connecting 

the supply wires to the unit. Use of rain tight conduit is 

recommended.

•  208/230 Volt units are shipped from the factory wired 

for 230 volt operation. For 208V operation, remove the 

lead from the transformer terminal marked 240V and 

connect it to the terminal marked 208V.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance of 

the NEC (ANSI/NFPA 70), applicable local codes, and 

the instructions provided with the equipment.

grounding

 Warning:

the unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 

with local codes or, in the absence of local codes, with 

the National Electrical Code (ANSI/NFPA 70) or the CSA 

C22.1 Electrical Code. Use the grounding lug provided 
in the control box for grounding the unit.

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 

the indoor equipment.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 

comply with the current provisions of the NEC (ANSI/

NFPA 70) and with applicable local codes having 

jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 

wire gauge and wire lengths for typical thermostat 

connections are listed in 

Table 2

.

•  The thermostat should be mounted about 5 feet above 

the floor on an inside wall. DO NOT install the thermostat 

on an outside wall or any other location where its 

operation may be adversely affected by radiant heat from 

fireplaces, sunlight, or lighting fixtures, and convective 

heat from warm air registers or electrical appliances. 

Refer to the thermostat manufacturer’s instruction sheet 

for detailed mounting and installation information.

Table 1

copper Wire SiZe — aWg

(1% Voltage drop)

Supply Wire length-Feet

Supply circuit

ampacity

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

table 1. copper Wire Size

Start up & adJuStmentS

pre-Start check list

 Verify the indoor unit is level and allows proper 

condensate drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

 Verify air filters are cleaned and properly installed.

 Verify duct work is sealed to prevent air leakage.

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

  Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

 Verify the thermostat is wired correctly.

Start-up procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the system.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan 

mode to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 
balanced air distribution. If insufficient air is detected, 
examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the 

blower stops running.

Table 2

table 2. thermostat Wire gauge

thermoStat

Wire gauge

maximum recommended

 thermoStat Wire length (Ft)

24

25

22

45

20

70

18

110

Содержание S6BF-024 Series

Страница 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Страница 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Страница 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Страница 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Страница 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Страница 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Страница 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Страница 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Страница 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Страница 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Отзывы: