background image

10

electrical diagramS

Figure 7

Figure 7. Wiring diagram for 2, 2.5, 3, 3.5 ton models (with pSc motor)

Single Phase

1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.

710388B

(Replaces 710388A)

0109

WIRING DIAGRAM

Split System Air Conditioner (Outdoor Section)

NOTES:

1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 deg C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation
    instructions for control circuit and optional relay/transformer kits.
7. Anti-Short Cycle Timer (ASCT) may or may not be installed in the unit. If desired,
    ASCT is factory installed on select models only or may be field installed as shown using
    manufacturer’s approved kit. If not present, connect Yellow and Black wires per Note 6.

FIELD WIRING

LEGEND:

LOW VOLTAGE

HIGH VOLTAGE

¢710388B¤

CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch

208/230V

CC

ASCT

ASCT

(SEE NOTE 7)

H

C

F

CCH

(OPTIONAL)

R

C

S

S

C

R

L2

T2

COMPRESSOR

CONTACTS

L1

T1

COMPRESSOR

OUTDOOR FAN
MOTOR

24 VOLT FIELD
CONNECTIONS

HPS

HPS

T2

T1
T3

ASCT

(SEE

NOTE 7)

GROUNDING

SCREW

L1 L2 GND

T1

T2

L1

L2

OUTDOOR

FAN MOTOR

C

S

DUAL

CAPACITOR

R

3

1

2

START

CAPAC

START

RELAY

BLACK

BLUE

ORANGE

YELLOW

CONTACTOR

YELLOW

BLACK

RED

CRANKCASE

HEATER

(OPTIONAL)

YELLOW BLACK

SEE NOTE 6

RED OR

YELLOW

BLACK

RED OR

RED BLACK

BLACK OR

BLK WHT

C

S

R

YELLOW

OR

YELLOW

BLACK

RED OR 

RED BLACK

H

C

F

component FunctionS

high pressure Switch (hpS) - A high-pressure switch is factory-installed and located in the liquid line internal to 

the outdoor unit. The switch is designed to protect the system when very high pressures occur during abnormal 

conditions. Under normal conditions, the switch is closed. If the liquid pressure rises above 575 psig, then the switch 

will open and de-energize the outdoor unit. The switch will close again once the liquid pressure decreases to 460 

psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then 

closes, there may be a 5 minute short cycling delay before the outdoor unit will energize.
low-pressure Switch - (Select Models) A low-pressure switch is factory-installed and located in the suction line 

internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal 

conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and de-energize 

the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the 

switch interrupts the thermostat inputs to the unit. When the switch opens and then closes, there will be a 5 minute 

short cycling delay before the outdoor unit will energize. 

Содержание S6BF-024 Series

Страница 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Страница 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Страница 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Страница 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Страница 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Страница 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Страница 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Страница 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Страница 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Страница 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Отзывы: