Nortek S4BE-018 Series Скачать руководство пользователя страница 8

8

Figure 3

Figure 3. charging chart for 2 - 5 ton units

S4Be-024-060 Series (txV matches)

200

220

240

260

280

300

320

340

360

380

400

420

440

460

480

500

520

540

560

580

600

75 80

85

90

95 100 105 110 115 120 125 130 135

Liquid Pressure (psig)

Liquid Temperature (F)

S4BE / SA4BE Charging Chart

Add refrigerant if
below the curve.

Remove refrigerant
if above the curve.

Do not add or remove refrigerant if

pressure reading is between unit 

curves and saturation curve.

1.5, 3, 5 TON MODELS

2, 2.5, 3.5, 4 TON MODELS

R-410A SATURATION

application notes for using the charging chart

•  This  equipment’s  cooling  system  contains 

refrigerant under high pressure. always use safe 

and environmentally sound methods when handling 

refrigerant handling or servicing the unit. review 

the factory literature and safety warnings prior to 
servicing.

•  When repairing system leaks, always use a nitrogen 

(inert) gas to protect the refrigerant system and pressure 

check the repair before re-charging. Always replace 

the filter-dryers when performing any repair to the 

refrigeration system with one capable of acid removal. 

After completing the repairs, evacuate the system to 

350 - 500 microns and weigh in the refrigerant to the 

amount specified on the unit rating label.

•  The refrigerant charging chart is valid for a variety of 

indoor, return air conditions and are most influenced by 

the outdoor ambient temperature, outdoor fan operation 

and the unit operating voltage.

  Before using this chart, make sure the unit is in a stable 

operating mode. As shown in 

Figure 3, (page 8)

, the 

ideal system sub-cooling can vary over the range of 

operation. Reference the charts to determine the ideal 

amount of sub-cooling for a given liquid pressure. Units 

charged to other values will not perform at the rated unit 

efficiency (EER) or rated Coefficient of Performance 

(COP) in heating mode.

•  To inspect a systems operation using quality instruments, 

match the measured liquid temperature to the units 

table. The measured liquid pressure reading should be 

within 3% of the table value for most installations.

•  For systems that are operating with more than a 5% 

deviation, inspect the unit for the proper voltage and 

phase balance and the refrigeration system for leaks.

•  Units that are operating at less then 95% of the nominal 

voltage or with a 2% phase imbalance may see a more 

significant deviation than the amount stated above.

• 

do not

 use the charts in systems that have a fan cycling 

under low-ambient control. Refer to the low-ambient kit 

instructions for more information (If applicable).

Содержание S4BE-018 Series

Страница 1: ...ns to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General I...

Страница 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Страница 3: ...formaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best locat...

Страница 4: ...Figure 7 Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on t...

Страница 5: ...on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 13 Compressor Protection TheCoreSenseTM Diagnostics...

Страница 6: ...the source of the noise and correct as necessary 3 Verify HI and LO refrigerant pressures 4 Allowthesystemtooperateforseveralminutesandthen set the temperature selector above room temperature Verify...

Страница 7: ...airflowsor non listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be checked...

Страница 8: ...weigh in the refrigerant to the amount specified on the unit rating label The refrigerant charging chart is valid for a variety of indoor return air conditions and are most influenced by theoutdooram...

Страница 9: ...t and optional relay transformer kits 7 Anti Short Cycle Timer ASCT may or may not be installed in the unit If desired ASCT is factory installed on select models only or may be field installed as show...

Страница 10: ...onsecutive Red Flash 2 Red Flash 3 Red Flash 4 Red Flash 5 Red Flash 9 Code 1 Yellow Flash 1 Code 2 Yellow Flash 2 Code 3 Yellow Flash 3 Code 4 Yellow Flash 4 Long Run Time Compressor running extremel...

Страница 11: ...ion see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer AS...

Страница 12: ...erate Run Compressor runs 15min then trips 7min Code 9 Red Flash 19 Over Current Protection PROT terminal has 2A input for more than 40ms Trip Solid Red Demand but compressor is not running YELLOW BLA...

Страница 13: ...h 3 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min 4x consecutive or 10x total Red Flash3 Yellow Off Code4 Yellow Flash 4 Lo...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ..._______________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO RE...

Отзывы: