Reznor, Guardian GB GR and GS, Installation Manual, EN 2020-06, D30121 Iss B Page No 21
I
Installer wiring LPHW heated models, single phase
N
L
E
CONTROL BOARD
(located in air curtain)
CHASSIS
EARTH
6 6a
N
L
E
4 4a 5 5a
1 2 3 N
FAN
1 2
3 4
ON
Comms RS485
EXT
DOOR
PIPE COLD
AIR RETURN
STAT
TIMER
FILTER
FAN 0-10v
FAIL O/P
VALVE 0-10v
AIR OUTLET
Ext Timer
(BMS)
Door Switch
Ext Temp
Sensor
J1
J2
Programmer
Keypad
SELECT
RJ45 Cable
230v 50Hz
MAINS SUPPLY
Factory Connections
Installer Wiring
900699 Guardian Series LPHW - Installer Connections
3 3a
1 1a 2 2a
7 7a
Modulating
Valve
Ext Pressure
Switch
Air Return
Sensor
Pipe Cold
Sensor
Violet
Blue
White
Yellow
Red
Black
Grey
Green / Yellow
Brown
Blue
Figure 22 Wiring diagram LPHW heated
Terminal
Description
Cable
N
Neutral
1.5mm²
L1
Live
E
Earth
Table 8 Cable specification LPHW heated
Protection
External circuit breaker with the appropriate
rating should be installed for the protection of the
installation.
Terminal
Description
Cable
Timer/BMS
(J1)
Optional external switch
1.5mm²
maximum
Door (J2)
Optional door contact
Ext
Optional external sensor
Air return
Optional sensor
Pipe cold
Optional sensor
Fail o/p
Fault output (0-5v)
Fan
Optional 0-10v fan output
Valve
Optional 0-10v valve output
Filter block
Optional filter blocked switch
PCB fuses
Rating (A)
F1
T1H (slow blow)
Table 8.1 Cable specification LPHW heated