background image

7

Air Filter Requirements

 WARNING:

Never operate the unit without a filter in place. 

Dust and lint could accumulate on internal parts, 

resulting in loss of efficiency, equipment damage, 

and possible fire.

NOTE TO INSTALLER:

 After installing or replacing the 

filtration system for this unit, add the following statement 
on or adjacent to the filter service panel: “Replace filter(s) 
installed in your system only with the same dimensional 
size filters that are being replaced.”
•  An air filter is not supplied with this package unit as 

shipped from the factory. The installer must provide 

a high velocity filter that is appropriately sized to the 

return air duct opening or internal filter rack. The filters 

must comply with ANSI/UL 900 or CAN/ULC-S111.

•  Horizontal installations require the air filter system be 

installed in the return air ductwork. 

•  For recommended external filter sizes, refer to Table 2 

(page 12) under 

Heat Pump Maintenance

•  All return air must pass through the filters before entering 

the evaporator coil. It is important that all filters be kept 

clean and replaced frequently to ensure proper operation 

of unit. Dirty or clogged filters will reduce the efficiency 

of the unit and result in unit shutdowns. 

•  Air filter pressure drop is recommended not to exceed 

0.08 inches WC. 

•  Single phase downflow applications require either a 

Nortek internal filter kit be used, or an air filter system 

be installed in the return air ductwork. See Table 2 for 

specific unit model and filter sizes. 

•  Horizontal installations require the air filter system be 

installed in the return air ductwork.

HEAT PUMP INSTALLATION

Packaging Removal

Remove the shipping carton and User’s Manual from 

the equipment. Take care not to damage the tubing 

connections when removing the carton. For rooftop 

installations, remove and discard the two supports attached 

beneath the unit.

Rigging & Hoisting

 WARNING:

To avoid the risk of property damage, personal 

injury, or death, it is the rigger’s responsibility 

to ensure that whatever means are used to hoist 

the unit are safe and adequate:
•  The lifting equipment must be adequate for the 

load. Refer to 

Table 3 (page 13)

 for unit weights.

• The unit must be lifted from the holes in the 

base rails using cables or chains.

•  Spreader bars are required to protect the unit 

and ensure even loading.

•  Keep the unit in an upright position at all times. 

The rigging must be located outside the units 

center of gravity. Refer to 

Figure 7 (page 13)

 

for locating the center of gravity.

• All panels must be securely in place during 

rigging and hoisting.

Minimum Clearances

Q104SD units are certified as combination heating and 

cooling equipment for outdoor installation only. 

Figure 

2 (page 6)

 displays the minimum clearances to 

obstructions for both downflow and horizontal discharge.
Units may be installed on wood flooring or on Class A, B, 

or C roof covering material when used with bottom supply 

and return air ducts as long as the following requirements 

are met:
• If using horizontal supply and return air ducts, the 

horizontal roof curb kit and return air kit must be installed 

prior to unit installation. Horizontal roof curb is required.

•  If using bottom discharge with return air ducts a roof 

curb must be installed prior to unit installation. See 

Rigging and Hoisting section for setting of the unit.

Ground Level

Ground level installations must be located according to 

local building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown 

in Figure 2. Also consider clearances for access to the 

internal filter.

•  A suitable mounting pad must be provided and separate 

from the building foundation. The pad must be level to 

ensure proper condensate disposal and strong enough 

to support the unit’s weight. The slab height must be a 

minimum of 2” (5cm) above grade and with adequate 

drainage. See 

Figure 3

.

2”

Figure 3. Ground Level Installation

Содержание Q104SD Series

Страница 1: ...mon sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety wa...

Страница 2: ...ing an R 410A Unit in AC Mode 12 Charging an R 410A Unit in Heating Mode 12 Verification of charge in Heat Mode 12 HEAT PUMP MAINTENANCE 12 FIGURES TABLES 13 Figure 7 Q104SD Heat pump Dimensions 13 Ta...

Страница 3: ...oorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the f...

Страница 4: ...selector setting HEAT PUMP MAINTENANCE CAUTION Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or d...

Страница 5: ...asoline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit U...

Страница 6: ...ng load of the area to be conditioned must be calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the elect...

Страница 7: ...beneath the unit Rigging Hoisting WARNING To avoid the risk of property damage personal injury or death it is the rigger s responsibility to ensure that whatever means are used to hoist the unit are s...

Страница 8: ...ning the correct fuse or circuit breaker for the unit Incoming field wiring and minimum size of electrical conductors and circuit Units require horizontal roof curb and return air kit for horizontal i...

Страница 9: ...the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rises above 650 psig then the switch will open and de energi...

Страница 10: ...seconds regardless of whether short is removed or not Qualifying conditions of minimum ambient or coil temperature do not need to be met when the unit is forced into defrost If the short across the TE...

Страница 11: ...ify the unit is level and allows condensate to drain Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment access control panels are in place Verifythatth...

Страница 12: ...he unit rating plate Return to the system when the outdoor temperature is 60 degrees F or higher and follow the steps defined in Charging an R410A Unit in AC Mode NOTE Unit charge MUST be verified in...

Страница 13: ...2 29 5 26 0 43 0 39 3 X60K 530 29 5 26 0 43 0 39 3 FIGURES TABLES Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT O...

Страница 14: ...t Defrost Board L 24V Output Fault Monitor See thermostat manual for compatibility Brown Orange Accesory Heat Plug Indoor Thermostat Sub Base Unit Terminal Block 1 2 3 4 5 6 7 8 9 to Blower Relay Cool...

Страница 15: ...See installation instructions in the branding kit 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la...

Страница 16: ...16 Figure 10 Charging Chart for 2 Ton Units Figure 11 Charging Chart for 2 5 Ton Units Charging Charts Cooling...

Страница 17: ...17 Figure 13 Charging Chart for 3 5 Ton Units Figure 12 Charging Chart for 3 Ton Units...

Страница 18: ...18 Figure 14 Charging Chart for 4 Ton Units Figure 15 Charging Chart for 5 Ton Units...

Страница 19: ...9 1380 22 9 1315 24 0 1215 26 0 Tap T5 1850 17 1 1795 17 6 1740 18 2 1710 18 5 1640 19 3 1595 19 8 1540 20 5 1475 21 4 X48K Tap T1 950 33 2 900 35 1 865 36 6 730 43 4 670 47 0 585 54 2 510 62 2 Tap T...

Страница 20: ...VOLTS Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO REPLACEMENT PARTS Replacement parts are available through your distributor...

Отзывы: