![Nortek P7RE Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/nortek/p7re-series/p7re-series_installation-instructions-manual_1705921007.webp)
7
Figure 5. Supply damper
electrical connectionS
Warning:
electrical Shock, Fire or
eXPloSion haZard
Failure to follow safety warnings exactly could
result in serious injury or property damage.
improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to the indoor blower.
• When servicing controls, label all wires prior
to disconnecting. reconnect wires correctly.
• Verify proper operation after servicing.
• All electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-electrical checklist
√
Verify that the voltage, frequency, and phase of the
supply source match the specifications on the unit rating
plate.
√
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper high and low
voltage wiring.
√
Verify factory wiring is in accordance with the unit wiring
diagram
. Inspect for loose connections.
Line Voltage
• A wiring diagram is located on the inside cover of the
electrical box of the unit. The installer should become
familiar with the wiring diagram before making any
electrical connections to the unit.
•
an electrical disconnect must be located within sight
of and readily accessible to the unit.
This switch shall
be capable of electrically de-energizing the unit.
• Line voltage to the unit should be supplied from a
dedicated branch circuit containing the correct fuse
or circuit breaker for the unit. Incoming field wiring
and minimum size of electrical conductors and circuit
protection must be in compliance with information listed
on the unit data label. Any other wiring methods must
be acceptable to authority having jurisdiction.
• Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment. Extend leads through
power wiring hole (
). Connect L1 & L2 directly
to the contactor.
Low Voltage
Line Voltage
Figure 7. Power entry
Figure 6. drain trap
elbow
P-trap
condensate drainage
A 3/4” condensate fitting extends out of the side of the
unit (
). The drain trap, shipped in the electrical
compartment, must be installed to prevent water from
collecting inside the unit.
1. Thread the elbow provided with the unit into the drain
connection until hand tight.
2. Connect the condensate tubing onto the fitting, forming
a trap near the drain connection.
3. Route the condensate tube from the trap to a suitable
drain.
note:
For proper drainage, make sure the trap
is level to the ground and tubing outlet is below trap
level.
Содержание P7RE Series
Страница 19: ...19...