Nortek FS4BF Скачать руководство пользователя страница 7

7

air conditioner maintenance

 Warning:

to prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

 caUtion:

the unit should never be operated without a 

filter in the return air system. replace disposable 

filters with the same type and size.

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed 

at the factory and does not require lubrication.

reFrigerant charging

 Warning:

S4BF Split System air conditioners are shipped 

charged with r410a refrigerant and ready 

for installation. if repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. Under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

After refrigerant line connections are completed, it is 

required that you leak check and evacuate the indoor 

section and all line connections (using proper methods) 

before finalizing the full system refrigerant charge.

•  Refrigerant  charging  charts  are  applicable  only  to 

matched assemblies and listed airflows for the indoor 

coil. Refer to 

Figure 4 (page 8)

Figure 5 (page 9)

Figure 6 (page 9)

, & 

Figure 7 (page 10)

 for correct 

system charging.

•  S4BF outdoor units with non-AHRI listed indoor coils 

are not recommended. Deviations from rated airflows or 

non-listed combinations may require modification to the 

expansion device and refrigerant charging procedures 

for proper and efficient system operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the 

outdoor unit. Use only gage line sets which have a 

“Schrader” depression device present to actuate the 

valve.

•  A high-pressure switch is factory-installed and located 

in the liquid line internal to the outdoor unit. The switch 

is designed to protect the system when very high 

pressures occur during abnormal conditions. Under 

normal conditions, the switch is closed. If the liquid 

pressure rises above 575 psig, then the switch will open 

and de-energize the outdoor unit. The switch will close 

again once the liquid pressure decreases to 460 psig. 

Please note that the switch interrupts the thermostat 

inputs to the unit. Thus, when the switch opens and 

then closes, there may be a 5 minute short cycling 

delay before the outdoor unit will energize.

•  On  select  models  a  low-pressure  switch  is  factory-

installed and located in the suction line internal to 

the outdoor unit. The switch is designed to protect 

the compressor from a loss of charge. Under normal 

conditions, the switch is closed. If the suction pressure 

falls below 5 psig, then the switch will open and de-

energize the outdoor unit. The switch will close again 

once the suction pressure increases above 20 psig. 

Please note that the switch interrupts the thermostat 

inputs to the unit. When the switch opens and then 

closes, there will be a 5 minute short cycling delay 

before the outdoor unit will energize.

charging the Unit in ac mode

(With outdoor temperatures above 65° F)

1. With the system operating at steady-state, measure 

the liquid refrigerant pressure (in psig) at the outdoor 

unit service valve.

2. Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure from 

the appropriate charging chart. See 

Figure 4 (page 8)

Figure 5 (page 9)

Figure 6 (page 9)

,  

Figure 7 

(page 10)

.

•  If  the  pressure  measured  in  Step  1  is  greater  than 

the required liquid refrigerant pressure determined in 

Step 3, then there is too much charge in the system. 

Remove refrigerant and repeat Steps 1 through 3 until 

the system is correctly charged.

•  If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in Step 

3, there is too little charge in the system. Add refrigerant 

and repeat Steps 1 through 3 until the system is correctly 
charged.

Содержание FS4BF

Страница 1: ...NCE Installation Instructions important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 General Information 3 Before You Install this Unit 3 Locating the Air Conditioner 3 Packaging Removal 3 Grou...

Страница 2: ...autions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operati...

Страница 3: ...g the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit The outdoor unit should be installed no closer than 18 inches from the outside...

Страница 4: ...the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre Ele...

Страница 5: ...c key is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 17 Compressor Protection Th...

Страница 6: ...re Verify the fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to...

Страница 7: ...tionsfromratedairflowsor non listedcombinationsmayrequiremodificationtothe expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charge can be...

Страница 8: ...ary over the range of operation Reference the charts to determine the ideal amount of sub coolingforagivenliquidpressure Unitschargedto other values will not perform at the rated unit efficiency EER o...

Страница 9: ...110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F S4BF 036KB Charging Chart Cooling Figure 6 Charging Chart for 4 Ton Models Add refrigerant when below curve Remove refrigerant when a...

Страница 10: ...when below curve Remove refrigerant when above curve 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure...

Страница 11: ...onductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circu...

Страница 12: ...R C S S C R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Cr...

Страница 13: ...le Phase 60 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR...

Страница 14: ...tection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avan...

Страница 15: ...R C S L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR CSC C Y2 Y LPS HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdo...

Страница 16: ...class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducte...

Страница 17: ...system 6 Thermostat is malfunctioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrige...

Страница 18: ...ssor bearings are seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blo...

Страница 19: ...19...

Страница 20: ...____________________________ Unit Installed Minimum clearances per Figure 1 page 3 YES NO INSTALLER NAME CITY________________________ STATE_________________ REFRIGERATION SYSTEM Was unit given 24 hr w...

Отзывы: