Table 7. Blower Performance Data
036K
MOTOR SPEED
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
936
901
891
840
789
739
688
613
Med-Low
1,160
1,122
1,087
1,046
1,001
950
899
855
Medium
1,287
1,253
1,213
1,178
1,142
1,092
1,049
1,002
Med-High
1,434
1,394
1,353
1,328
1,297
1,248
1,220
1,202
High
1,550
1,515
1,495
1,457
1,429
1,416
1,388
1,355
030K
MOTOR SPEED
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
869
832
795
758
704
639
579
507
Medium
933
903
866
820
770
714
640
576
High
1,014
971
929
884
833
780
714
640
024K
MOTOR SPEED
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
846
795
756
707
668
589
533
467
High
926
890
845
791
732
672
603
536
019K
MOTOR SPEED
0.1
0.2
0.3
0.4
0.5
0.6
Low
683
663
605
529
442
307
High
783
733
665
576
484
350
018K
MOTOR SPEED
0.1
0.2
0.3
0.4
0.5
0.6
Low
665
645
592
521
422
326
High
769
719
656
565
459
347
NOTES:
1. Airflow is shown in cfm, +/- 5%.
2. External static pressure is shown in inches W.C.
3. All airflows are measured with filter and with dry coil. For wet coil, subtract .1” external static pressure.
4. See unit nameplate or installation instructions for maximum recommended external static pressure.
Table 8. Control Board Operation
CONTROL SIGNAL
& MODE
OPERATION
TOTAL KW
BOARD ACTION
W
(EHEAT)
ON
5 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
8KW / 10 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
OFF
Heat stages off instantly
Blower off after 15 second delay
W & Y
(AUX HEAT)
ON
5 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
8KW / 10 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
OFF
Heat stages off instantly
Heat blower turns off after 40 second delay
G
(FAN)
ON
Cool blower on after 3 second delay
OFF
Cool blower off instantly
Y
(H.P. & COOL)
ON
Cool Blower on after 3 second delay
OFF
Cool Blower off after 40 second delay
Airflow Data