background image

13

change speeds during start-up, shut down, when thermostat 

inputs change, and when the duct static pressure changes 

(vents closed or opened, filter clogging, etc.). The air handler 
is configured by setting the selector switches and removing 

jumper connectors.

Basic Heating Airflow for Variable & Fixed Speed

Fixed & variable speed motor control boards (

Figure 17 

(page  27)

 & 

Figure 18

) contain a set of dip switches for 

setting the blower speed. For B6EM models, pins 1-4 set the 

speed for heating. For B6VM models, the A/B switch must 

be set for the appropriate cabinet size (either setting can be 

used for C-size cabinets). The airflow is set automatically 

based on the amount of installed heat. To determine the 

appropriate switch settings for your installation, see 

Table 

7, (page 18)

, or 

Table 10, (page 20)

.

Basic Cooling / Heat Pump Airflow for Variable & Fixed 
Speed

The basic cooling/heat-pump airflow is controlled by setting 

switches 5 - 8 on the motor control board (mounted on the 

blower). All airflows for other modes of operation (except 

electric heat) are determined by this basic setting. FAN ONLY 

would deliver 50% of the selected cooling airflow. 

Table 9, 

(page  19)

 lists the CFM airflow values recommended for 

each nominal system capacity. To determine dip switch 

settings, refer to 

Table 7, (page 18)

 for FSHE applications 

and 

Table 10, (page 20)

 for VSHE applications.

•  When operating in the heat pump mode, a higher basic 

airflow setting will increase the energy efficiency and 

capacity but will also decrease the supply air temperature.

•  For maximum capacity and energy efficiency, select an 

airflow at or near the top of the range for that nominal 

capacity. See 

Table 9, (page 19)

.

•  For maximum dehumidification, select an airflow near the 

middle or bottom of the range for that nominal capacity. 

Additional information on humidity control can be found 

in the Dehumidication Options section on 

page 11

.

•  For  thermostats  with  a  dehumidifier  output,  use  a  field 

supplied wire to connect the thermostat’s dehumidifier 

output to the terminal marked 

DHuM. The thermostat 

should be set so that the 

DHuM output should be high 

(energized) when dehumidification is needed. See also 

Dehumidification Options section.

IMPoRtANt! If coil icing is observed, the basic cooling/

heat-pump airflow selected may be too low. Verify the setting 

selected is within the range shown in 

Table 9

 and that the the 

system is properly charged. Please refer to the instructions 

supplied with the outdoor unit. If icing continues to occur, 

raise the selected airflow one or two steps.
NotE: Variable speed air handlers with SEER ratings higher 

than 15 are matched with a 2-stage cooling outdoor unit. 

They are programmed to operate at 75% of the selected 

airflow while the system is in the lo-cool mode and 100% of 

the selected airflow while in hi-cool mode.
Units with an FSHE control scheme (B6EM and 5 ton B6BM 

units) have a control board that includes a 7 segment display 

to help the installer identify what mode the air handler 

is running in as well as troubleshooting if the unit is not 

functioning properly. 

Table 2, (page 13)

 contains a list of 

the codes that may appear on the 7 segment display. The 

display code will only show what mode the air handler is 

currently in. There is not a history of fault codes that have 

occurred in previous operation.

tRouBLESHootING

If the air handler fails to operate, check the following:

•  Is the electric turned on?

•  Is the thermostat operating properly?

•  Are the blower compartment door(s) in place?

•  Is the air handler disconnect closed?

•  Has the circuit breaker tripped or the control board fuse 

burned open?

•  Are any manual reset switches open?

•  Is the filter dirty or plugged?

•  Is the LED on both control boards constantly ON? If not, 

RED LED (AN2)

DIAGNoStIc

OFF

Control Fault (No Power)

Flash

Blower Fault

ON

Normal Operation

table 3. 

Air handler control Board Fault conditions

table 2. 

FSHE Motor control Board Display codes

DISPLAY

coDE

cuRRENt MoDE

-

Standby is a Rotating Segment

C

Cooling Mode (Y input active)

H

Heating Mode (W input active)

f

Circulate Fan Mode (G input active)

d

Dehum Cooling Mode (DEHUM input active along with Y)

I

(one) A Motor Fault has Occurred (BMF active for more than 

30 seconds)

t

(lower case t) Over Temperatures (The value of the TS input 

has exceeded 80C all outputs are stopped.)

L

Lockout (Ten (10) or more Motor Faults or Over Temperature 

events have occurred. All outputs are set to off for one hour.

DIAGNoStIc FAuLt coNDItIoNS

FoR VARIABLE SPEED FuRNAcES

GREEN

LED

RED

LED

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Communications Fault

Flash

Flash

table 4. 

VSHE Motor control Board Display codes

Содержание B6BM Series

Страница 1: ...ole as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious...

Страница 2: ...tion 12 Turning the Blower Off 12 System Cooling 12 System Heating 12 Selecting Minimum Electric Heat Airflow 12 Blower Configurations 12 Determining Nominal System Capacity 12 3 Speed Units 12 High E...

Страница 3: ...installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could resu...

Страница 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Страница 5: ...install all the needed gaskets and grommets around penetrations into the air handler such as for electrical wiring Air handler INSTALLATION B6 series air handler s are shipped ready for vertical upflo...

Страница 6: ...oil and drain pan assembly out of the unit 3 Remove the sheet metal hairpin covers if supplied from the back of the coil and discard 4 Place the horizontal drain pan on the opposite side of the coil O...

Страница 7: ...equipment damage personal injury or death The installer should make every effort to ensure the field installed refrigerant containing components of the system have been installed in accordance with t...

Страница 8: ...htenanadditional1 4turnusingtwowrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten to 10 12 ft lbs or 14 16 Nm Connecting the Linesets The...

Страница 9: ...d tubing or pvc pipe and adequately trapped Both drain tubes must have a minimum diameter of 3 4 and be trapped separately IMPORTANT Failure to install a trap may result in condensation overflowing th...

Страница 10: ...of the original wires supplied with the unit the replacement wire must be copper wire consisting of the same gauge and temperature rating Provide power supply for the unit in accordance with the unit...

Страница 11: ...ions The motor control board has a DHUM or D connection that allows the system to increase the amount of humidity that is removed from the circulating air See Figure 17 Figure 18 page 27 This is accom...

Страница 12: ...control boards do not support non electric heat because the heating air flow cannot be set independently Blower Configurations Determining Nominal System Capacity To select the appropriate airflows f...

Страница 13: ...ed the basic cooling heat pump airflow selected may be too low Verify the setting selected is within the range shown in Table 9 and that the the system is properly charged Please refer to the instruct...

Страница 14: ...etailers WARNING Never operate the air handler without a filter in place Dust and lint in the return air can build up on internal components resulting in loss of efficiency equipment damage and possib...

Страница 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Страница 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Upper Door Assembly Lower Door...

Страница 17: ...764 701 631 555 Corrected ESP1 0 00 0 04 0 16 0 27 0 39 0 51 0 62 0 74 Medium 1265 1232 1188 1133 1067 991 903 805 Corrected ESP1 0 00 0 00 0 03 0 15 0 28 0 41 0 54 0 68 High 1427 1385 1333 1270 1196...

Страница 18: ...805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 1290 1245 1205 1170 1125 1085 1045 1 1 0...

Страница 19: ...ttings for these airflows A Cabinet B Cabinet C Cabinet CFM Nominal Capacity CFM Nominal Capacity CFM Nomical Capacity 525 1 5 TON 525 1 5 TON 1100 3 TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TO...

Страница 20: ...1100 1 0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 n a 1 0 1 1 1 850 1 30 n a 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 14...

Страница 21: ...7 67 6 50 25 70 020H XX 52 6 50 0 102 6 60 60 110 46 0 43 3 89 3 50 45 90 009Q XX 29 7 30 26 1 30 015Q XX 45 9 50 40 2 45 B 42 48 None 3 1 3 1 15 15 3 1 3 1 15 15 005H XX 28 1 28 1 30 30 24 8 24 8 25...

Страница 22: ...ase MCA MOP MCA MOP Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit Circuit A Circuit B Circuit C Single Circuit...

Страница 23: ...seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay Stage 6 Heat on after 25 seconds delay Off Heat stages off instantly...

Страница 24: ...econd delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 10 seconds delay Stage 4 Heat on after 15 seconds delay Stage 5 Heat on after 20 seconds delay 30 KW Stage 1Heat on instantly Co...

Страница 25: ...Typical 2 Stage Heat Pump with 2 Stage Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air Conditioner Air Handler Heat Pump Air Handler Heat Pump O R C Y Air Handler Heat Pump NOTE Jum...

Страница 26: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 15 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 16 Two Stage Contro...

Страница 27: ...N TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B Figure 18 Variable Speed Motor Control Board Figure 17 Fixed Speed Motor Control Board 3A Fuse EA...

Страница 28: ...e transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cui...

Страница 29: ...sse du moteur du ventilateur peut diff rer de l illustration Consultez les Instructions d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir u...

Страница 30: ...ons d installation 2 D branchez toutes les sources d alimentation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension...

Страница 31: ...31...

Страница 32: ...INSTALLERS Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to o...

Отзывы: