13
change speeds during start-up, shut down, when thermostat
inputs change, and when the duct static pressure changes
(vents closed or opened, filter clogging, etc.). The air handler
is configured by setting the selector switches and removing
jumper connectors.
Basic Heating Airflow for Variable & Fixed Speed
Fixed & variable speed motor control boards (
&
) contain a set of dip switches for
setting the blower speed. For B6EM models, pins 1-4 set the
speed for heating. For B6VM models, the A/B switch must
be set for the appropriate cabinet size (either setting can be
used for C-size cabinets). The airflow is set automatically
based on the amount of installed heat. To determine the
appropriate switch settings for your installation, see
Basic Cooling / Heat Pump Airflow for Variable & Fixed
Speed
The basic cooling/heat-pump airflow is controlled by setting
switches 5 - 8 on the motor control board (mounted on the
blower). All airflows for other modes of operation (except
electric heat) are determined by this basic setting. FAN ONLY
would deliver 50% of the selected cooling airflow.
lists the CFM airflow values recommended for
each nominal system capacity. To determine dip switch
settings, refer to
for FSHE applications
and
for VSHE applications.
• When operating in the heat pump mode, a higher basic
airflow setting will increase the energy efficiency and
capacity but will also decrease the supply air temperature.
• For maximum capacity and energy efficiency, select an
airflow at or near the top of the range for that nominal
capacity. See
.
• For maximum dehumidification, select an airflow near the
middle or bottom of the range for that nominal capacity.
Additional information on humidity control can be found
in the Dehumidication Options section on
• For thermostats with a dehumidifier output, use a field
supplied wire to connect the thermostat’s dehumidifier
output to the terminal marked
DHuM. The thermostat
should be set so that the
DHuM output should be high
(energized) when dehumidification is needed. See also
Dehumidification Options section.
IMPoRtANt! If coil icing is observed, the basic cooling/
heat-pump airflow selected may be too low. Verify the setting
selected is within the range shown in
system is properly charged. Please refer to the instructions
supplied with the outdoor unit. If icing continues to occur,
raise the selected airflow one or two steps.
NotE: Variable speed air handlers with SEER ratings higher
than 15 are matched with a 2-stage cooling outdoor unit.
They are programmed to operate at 75% of the selected
airflow while the system is in the lo-cool mode and 100% of
the selected airflow while in hi-cool mode.
Units with an FSHE control scheme (B6EM and 5 ton B6BM
units) have a control board that includes a 7 segment display
to help the installer identify what mode the air handler
is running in as well as troubleshooting if the unit is not
contains a list of
the codes that may appear on the 7 segment display. The
display code will only show what mode the air handler is
currently in. There is not a history of fault codes that have
occurred in previous operation.
tRouBLESHootING
If the air handler fails to operate, check the following:
• Is the electric turned on?
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the air handler disconnect closed?
• Has the circuit breaker tripped or the control board fuse
burned open?
• Are any manual reset switches open?
• Is the filter dirty or plugged?
• Is the LED on both control boards constantly ON? If not,
RED LED (AN2)
DIAGNoStIc
OFF
Control Fault (No Power)
Flash
Blower Fault
ON
Normal Operation
table 3.
Air handler control Board Fault conditions
table 2.
FSHE Motor control Board Display codes
DISPLAY
coDE
cuRRENt MoDE
-
Standby is a Rotating Segment
C
Cooling Mode (Y input active)
H
Heating Mode (W input active)
f
Circulate Fan Mode (G input active)
d
Dehum Cooling Mode (DEHUM input active along with Y)
I
(one) A Motor Fault has Occurred (BMF active for more than
30 seconds)
t
(lower case t) Over Temperatures (The value of the TS input
has exceeded 80C all outputs are stopped.)
L
Lockout (Ten (10) or more Motor Faults or Over Temperature
events have occurred. All outputs are set to off for one hour.
DIAGNoStIc FAuLt coNDItIoNS
FoR VARIABLE SPEED FuRNAcES
GREEN
LED
RED
LED
Control Fault (No Power)
Off
Off
Normal Operation
On
On
Motor Fault
On
Flash
Communications Fault
Flash
Flash
table 4.
VSHE Motor control Board Display codes
Содержание B6BM Series
Страница 31: ...31...