Doc No. 702100  Page 5 of 12 

Gap to be kept to a 
minimum 

3m minimum 

Bottom of air     

curtain to be  

level with top of 

door opening 

4. Installation Details. 

Health and Safety 

Due account should  be taken of any obligations 
arising from the Health and Safety at Work Act 
1974 or relevant codes of practice. In addition 
the  installation  must  be  carried  out  in             
accordance  with  the  current  IEE  wiring          
regulations and any other relevant British 

 

 

 

Standards and Codes of Practice by a qualified 
installer. Isolate all electrical supplies to the 
heater & control panel   before proceeding. 
 
For your own safety we recommend the use of 
personal protective equipment when handling 
this air curtain. 

Airbloc air curtains are supplied with mounting 
brackets pre-fitted, and can be mounted either 
as single units, or in multiples, which can be 
bolted together to suit various door widths. 
 
The minimum mounting height is 3 metres (See 
diagram 2 below). 
 

4.1

 

Each single air curtain should be supported by 
cantilever brackets (not supplied) then fixed 
back to the building structure by bolting directly 
using 

suitable 

support 

brackets, 

or 

by            

suspending 

from 

above 

using 

suitable         

steelwork. (See diagram 3, page 6). 

4.2 

Multiple air curtains should be bolted together 
using 3 off M10 set pins, nuts and washers fitted 
through the holes provided in the mounting 
brackets, then suitable support channels (not 
supplied) must be  fixed on top of the factory 
fitted brackets along the full length of the 

 

 

 

 

 

 

assembled air curtains to spread the load.   
 
The assembly can now be fixed back to the 
building  structure  by  bolting  directly  using     
suitable support brackets, or suspending from 
above using steelwork. (See diagram 4 page 6). 
 
If  required,  the  support  channel  may  be          
extended slightly past the ends of the air 

 

 

 

 

 

 

curtains to aid fixing. 

 
 Note: Where multiple  air curtains are fitted          
above  up  and  over  doors  or  where            

central  support  is  inappropriate,  the  support           
channel should be replaced with channels of  a 
greater cross section to prevent the assembly 
from bending.
 

4.3  Mounting. 

It may be  necessary to adjust the position of the 
air outlet louvres to provide the correct airflow 
across the door opening. This can be done by 
first loosening the four locking pins   located two 
at each end of the louvres (arrowed, Fig. A), 
then loosening the intermediate locking Allen 
pins (arrowed, Fig. B). The louvres can now be 
moved to the desired position and the locking 
pins re-tightened. 

 

 Note: The AB 225 model has two pairs of    
intermediate locking Allen pins, whereas the 

AB 175 model only has one pair. 

Fig. A 

Locking pins 

Diagram 2. 

Locking Allen pins 

Fig. B 

Содержание AB 150A

Страница 1: ...OC AB RANGE AMBIENT AIR CURTAIN INSTALLATION AND OPERATING MANUAL WARNINGS 1 This appliance must only be installed by a competent person in accordance with the requirements of the Codes of Practice or the rules in force 2 All external wiring MUST comply with the current IEE wiring regulations 3 Warning this appliance must be earthed Part No 702100 Nortek Global HVAC UK Limited Fens Pool Avenue Bri...

Страница 2: ...talling an air curtain is to prevent the influx of cold outside air through a door opening into a heated area Typical applications include large despatch bay doors in factories and warehouses and internal doors between areas of different temperatures Wider door openings can be accommodated by bolting two or more units together Air curtains control the internal climate by emitting an air stream wit...

Страница 3: ...le to order See contact details on rear cover of this document 2 Dimensions Model A mm B mm C mm D mm E mm F mm G mm Weight kg AB 175A 1750 523 457 507 260 86 1695 90 AB 225A 2250 523 457 507 260 86 2195 115 H mm 201 201 AB 150A 1500 523 457 507 260 86 1345 201 80 Diagram 1 Dimensions R H VIEW LPHW STEAM H ...

Страница 4: ...1140 W Current per fan 5 2A FLC Start current per fan 12A Power Total electrical power consumption 2 28kW 3 42kW 4 56kW 2 Model AB150 AB175 AB225 AB150 x 1 AB300 x 2 AB350 x 2 AB400 x 1 x 1 AB450 x 2 AB525 x 3 AB575 x 2 x 1 AB625 x 1 x 2 AB675 x 3 Constitution AB225 x 1 table shows full range of models available and the modules that make up their construction No other variants are available WARNIN...

Страница 5: ...ir curtains should be bolted together using 3 off M10 set pins nuts and washers fitted through the holes provided in the mounting brackets then suitable support channels not supplied must be fixed on top of the factory fitted brackets along the full length of the assembled air curtains to spread the load The assembly can now be fixed back to the building structure by bolting directly using suitabl...

Страница 6: ...IR CURTAIN Diagram 4 Support channel multiple air curtains Typical support channels Air curtain 1 Air curtain 2 PLAN VIEW TWIN AIR CURTAINS Factory fitted brackets Support points 4 Installation Details cont Factory fitted mounting brackets WARNING THIS AIR CURTAIN SHOULD NOT BE INSTALLED WHERE THERE IS A CORROSIVE ATMOSPHERE ...

Страница 7: ...then a suitably positioned limit switch and striker plate will need to be fitted to the door The panel incorporates an auto off manual selector switch which when in auto mode operates the air curtain as the door opens and closes The manual position overrides the door interlock and the off position turns the air curtain off The panel may also be fitted with optional low voltage 24V AC relays for fi...

Страница 8: ... set to the required angle See Figs A B on page 5 for setting procedure 6 3 Air distribution fans The air distribution fans can be accessed by opening the fan access lid as described in section 7 1 Clean off any dust or deposits with a soft brush paying particular attention to the impeller Check that the impeller spins freely and that there is no play in the fan bearings The fan s can be removed i...

Страница 9: ...d the retaining screws securing the hinged lid on the underside of the air curtain next to the louvres Fig 3 7 Parts Replacement Allen key set Adjustable spanner Cross point screwdriver 10mm spanner 13mm spanner Fig 5 Fan closure plate Fan outlet Fig 3 Fig 4 Fig 6 Fan closure plate Fan outlet The lid can now be hinged down to access the fans as shown in Fig 4 7 1 1 Fan closure plate Before individ...

Страница 10: ...re Parts Item Description Part No 3 speed air distribution fan unit AB FAN Item Description Part No Air distribution fan 5 pin plug socket Plug 3127 Socket 3126 Fig 9 shows single air distribution fan in isolation for clarity 7 1 2 Fan removal Identify the feed cable for the fan requiring removal and disconnect it from its cable mount ed plug socket See Fig 7 The four bolts securing the fan can no...

Страница 11: ...ontactor and associated wiring All air distribution fans off YES If the fan s still fail to operate normally please contact the Nortek service department YES Check 1 Power supply YES NO Air distribution fans NO Single fan unit off Check 1 Motor thermal trip may run when cool test motor 2 Motor wiring 3 Motor plug socket 9 Fault Finding ...

Страница 12: ...tate the auto off manual control panel selector switch to the off position The air distribution fans will stop Switch off the electrical supply to the control panel The panel live lamp will extinguish 10 6 Servicing To ensure continued efficient and safe operation it is recommended that the air curtain is serviced regularly by a competent person once a year in normal working conditions but in exce...

Отзывы: