CRC100R Quick Installation Guide
ISSUE 03
Main Configuration Settings
Item
Screen Display
Values
Menu
Default
Relay Operate Time
-
how long the strike
relay operates for.
R e l a y ?
N N
500ms (set to 0)
1 to 30 seconds
Config 3
(3
seconds)
Anti-timeback
–
how
long after use a card
is once again valid.
A T B ?
N N
Disabled (set to
0)
1 to 30 minutes
Config 0
(Disabled)
REX/Arming –
select
use of the
REX/Arming input.
R E X _
REX for use with
free exit button.
ARM for use as
an arming input.
Config REX
Card Format -
the
way that the data is
stored on the cards.
F o r m a t _
Several values
must be set here.
See explanation
below.
Format Standard
MAG (See
below)
Standard Nortech Clock & Data (Mag) Card Format Settings
If the CRC100R is to be used with standard cards that have been supplied by Nortech, the
card format settings should be:
Format:
MAG
Digits:
10
Len:
8
Offset:
02
Note:
No site code is necessary as all digits are used as the card number.
Standard Nortech 26-Bit Wiegand Card Format Settings
If certain cases, the customer requests 26-bit Wiegand card encoding, the card format
settings should be set to ‘W26’. No further parameters need to be set for this format:
To configure other card formats, refer to the User Manual.
Adding Cards When They Are Not Available or Adding Blocks of
Sequential Cards
Press
repeatedly until the ‘Cards’ menu is displayed (shows the current number of
cards in the system).
Press
once to enter ‘Cards’ menu:
F r o
m :
N N N N N N N N
Where NNNNNNNN is the card number last card presented to the
controller (or added manually).
Modify ‘From’ card number using
to change the current digit
value (over curser) and
to change the position of the curser.
Press
to enter the card ‘from’ card number.
Page
3