The water supply is to be carried out according to the figure above 
and the applicable local regulations for water installation.

The indicated connection specifications must be observed.

– Admissible supply water temperature 33.8 to 77.0ºF (1 to 25ºC).

– Admissible mains pressure 30 to 80 (hammer-free system).

Notes on water quality:

For the water supply of the Nortec RS, use exclusively untreated 
drinking water, water from RO system or de-ionized water. 

– The use of additives such as corrosion inhibitors, disinfectants, 
etc. is not allowed, since these additives may endanger health 
and affect proper operation. 

– Conductivity should be between 1 and 1500 

μS/cm. Note that 

conductivity less than 1 μS/cm is 

very aggressive water (this is 

equivalent to a resistivity of 1 M

Ω

 or greater). It is recommended 

to blend such water with other less-treated water to ensure the 
supply is not overly aggressive. 

– Hardness should be between 0 and 12 grains/gallon. 

– Silica content should be between 0 and 12 ppm. 

– pH should be between 6.5 and 7.5. 

– Chloride content should be between 0 and 50 ppm. 

– The connection material must be pressure-proof and certified 
for use with the particular supply (drinking water, RO, or DI water). 

– Important! Before connecting the water line, the line must be 
well flushed out. 

The water drain is to be carried out according to the figure found in 
Section 5.6.1 of the RS Series Installation Manual, 2582419 and 
the  applicable  local  regulations  for  water  installations.  The 
indicated connection specifications must be observed. 

–  Make  sure  that  the  drain  pipe  is  correctly  fixed  and  easily 
accessible for inspections and cleaning purposes. 

–  The  draining  temperature  is  maximum  140ºF  (60ºC).  Use 
temperature-resistant materials only! 

– Lead drain line down to the funnel with a constant downslope 
(min. 1.2°). 

Note: On units with two steam tanks, each drain line must be led 
into a separate funnel with trap. 

– Attach drain line in such a way, that it cannot slip out of the 
funnel or bottom out in the funnel. 

– The open end of the drain line must not touch the funnel (min. 
air gap 0.79" (2 cm)). 

– We recommend to install the funnel with an lateral off-set of 8" 
(20 cm) to the side of the unit, to prevent damage to humidifier 
due to rising steam.

Water Installation

Содержание RS SERIES

Страница 1: ...Steam Humidifier ...

Страница 2: ......

Страница 3: ...Installation Overview ...

Страница 4: ...pipes and upslope min 10º downslope min 2º of the steam hoseismaintained operation max surface temperature of the metal housing approx 140 160 F 60 70 C Make sure therefore that the construction wall pillar etc to which the unit is to be mounted does not consistofheat sensitivematerial Install the steam humidifier in such a manner that it is freely accessible with sufficient space available for ma...

Страница 5: ...idecontentshouldbebetween0and50ppm The connection material must be pressure proof and certified forusewiththeparticularsupply drinkingwater RO orDIwater Important Before connecting the water line the line must be wellflushedout The water drain is to be carried out according to the figure found in Section 5 6 1 of the RS Series Installation Manual 2582419 and the applicable local regulations for wa...

Страница 6: ...rom elbows according to equivalent length tables Important When deciding on the length and layout of steam hoses it should be noted that steam hoses may become shorter and or longer depending on temperature and age The steam hose must be secured to the steam distributor and humidifier steam outlet by means of hose clamps Solid steam pipes should be connected to the steam distributor and steam humi...

Страница 7: ...Electrical Connection For wiring diagram of double tank humidifier refer to Installation Manual 2582419 ...

Страница 8: ... 19 2015 EMAIL nortec humidity com 835 Commerce Park Drive Ogdensburg NY 13669 Nortec Humidity Ltd does not accept any liability for any damage caused by faulty installation or the use of components that are not approved ...

Отзывы: