Humidifier Mandatory Pre-Start-up Checklist (p.1 of 2)
Unit Serial #:
_ _ _ _ _ _ _ _
# of humidifiers:
_____
Tag:
_____________
Unit type:
NHSC / NHDI
Voltage:
_____V/___ph
Steam output:
____lbs./hr
Customer/Job:
_______________
Address:
__________________________________________________
Inspected by:
_____________
Date of inspection:
___/___/___
______________________________________________________________________________________________
W
WATER QUALITY:
- Well water
r
-City water
r
-Softened water
r
- Conductivity: _______mhmos
- Hardness: _____gr.
–Silica____ppm
HUMIDIFIER MOUNTING:
Clearances around the unit
Acceptable
Obstruction
- Front (door opens freely?)
3ft min
r
_______________
- Top (steam lines)
1ft min
r
____________________
- Bottom (fill, drain, controls)
1ft min
r
____________________
- Right (main pwr)
3ft min
r
____________________
- Left (main pwr)
2” min
r
____________________
- Ensure the scale tank bracket is locked in place
r
STEAM LINES:
CONDENSATE LINES:
- Slope up 2” per 12”
r
- Slopped back to drain
r
- Slope down ½” per 12”
r
- Trapped 2” more than static duct pressure
r
- Traps
r
- Size _______
- Insulated
r
- Length/Size ____________
- 90 deg. elbows qty: ____
- 45 deg. Elbows qty: ____
- Can condensate be trapped anywhere in the steam line? Yes
r
no
r
WATER LINES:
-½” at max 4ft from the unit
- 3/8” connection at fill
-water pressure: 30-80psig
DRAIN LINES:
-Air gap located within 3ft of the unit
r
- Slopped to drain
r
-Size:________
WIRING:
No loose wires around the unit or on the PC board? Yes
r
no
r
CONTROLS:
Installed
Location / Wiring /Setting
- High limit:
r
_____________________
- Air proving:
r
_____________________
- Mod controller:
r
_____________________
- Other:
r
_____________________
POWER
- Voltage, amperage rating and fuse corresponds to Spec Label
r
- Disconnect switch located close to humidifier
r
Field contact:___________________________ Signature:_______________________________