Reset Run Hour Counter
Resets the humidifier controller’s
run hour counter to zero hours
40560
255 will start the run hours
counter process.
0 will be accepted to clear the
run hours counter.
Current damping
Buffers the measured current
40510
From 0 to maximum
(depending on software ability)
Electrode current
The value of the electrode current
in Amps
30850
Hex value representing the
humidifies current in amps
Resolution: 0.10 amps
Example:
015F (hex) = 35.1 Amps
Steam output
The current steam output in Kg/Hr.
or LBS/hr
See UNITS (Modbus 40031)
30860
Hex value representing the
humidifies steam output in
kg/hr
Resolution: 0.10 kg or LBS
Example:
013B (hex) = 31.5 kg/hr or
LBS/hr
Run hour counter
The number of hours the
humidifier has been in operation
since the last time the run hour
counter was reset
30414
Hex value representing the
number of humidifier oper
additional hours since the last
reset.
Resolution: 5 minutes
Maximum count: 5460 Hours.
Example:
07D0 = 2000 hours
Firmware version
The firmware version of the
humidifier controller
30361
Packed BCD version 3.52
would be 0x0352
Humidifier state
Describes the current state of the
humidifier and it’s I/O’s
Contactor ON/OFF
Fill Valve ON/OFF
Drain Valve ON/OFF
30800
Bit Allocation
Note More than one bit can be
active at any time.
Contactor on = 1
Fill valve on = 2
Drain valve on = 4
Maximum production
The rated maximum steam
production for the humidifier
30802
Value written into Unit type
(40600) is also stored here
Alarms
The humidifier shall describe any
faults
Too long to fill
Excess Current
End of cylinder life
No current
30364
Bit Allocation
Note More than one bit can be
active at any time.
Too long to fill = 1
Excess current = 2
End of cylinder life = 4
No Current = 8
- 9 -
Содержание MES Electrode
Страница 2: ......
Страница 14: ... 11 MES ...
Страница 15: ... 12 ...
Страница 16: ... 13 ...
Страница 18: ... 15 ...