![Nortec Links 2 NHTC Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/nortec/links-2-nhtc/links-2-nhtc_installation-and-operation-manual_1705760009.webp)
Installation
|
5
Table 4: Variable Definitions
Variable Name
R=Read
W=Write
Description
LonWorks SNVT
nvoHourOpt_x
R
Analog Value
Indicates the number of hours the
humidifier cylinder has been in
operation.
SNVT_count_inc
nvoCapLimit
R
Analog Value
Reads to capacity limitation
applied to the unit output.
(50-100%)
SNVT_switch
nvoRHDem1_
x
R
Analog Value
Reads Ch.1 input signal in %RH or
demand to humidifier.
(0-100%)
SNVT_switch
nvoSet1_
x
R
Analog Value
Reads Ch.1 setpoint setting.
(10-90%)
SNVT_switch
nvoRHDem2_
x
R
Analog Value
Reads Ch.2 input signal in %RH or
demand to humidifier.
(0-100%)
Unit must be configured for dual
channel operation.
SNVT_switch
nvoSet2_
x
R
Analog Value
Reads Ch.2 setpoint setting.
(10-90%)
Unit must be configured for dual
channel operation.
SNVT_switch
nvoSysDemand_
x
R
Analog Value
Reads humidifier system demand.
(0-100%)
SNVT_switch
nviCapLimit
R
Analog Value
Sets the humidifier’s unit capacity.
(50-100%)
nviRHDem1_
x
W
Analog Value
Writes Ch.1 demand or %RH level.
Allows BMS control of humidifier
output. (0-100%)
Unit must be configured for
networked demand
SNVT_switch
nviRHDem2_
x
W
Analog Value
Writes Ch.2 demand or %RH level.
Allows BMS control of humidifier
output. (0-100%)
Unit must be configured for
networked demand
SNVT_switch
nviSet1_
x
W
Analog Value
Writes Ch.1 setpoint (0-90%)
SNVT_switch
nviSet2_
x
W
Analog Value
Writes Ch.2 setpoint (0-90%)
SNVT_switch
nvoFault_
x
R
Binary Value
Indicates unit fault status.
0=no fault, 1=fault.
SNVT_switch
nvoHWSensor_
x
R
Binary Value
Indicates if a high-water level
condition exists in the humidifier
cylinder.
0=normal, 1=high water condition
Содержание Links 2 NHTC
Страница 4: ......
Страница 23: ...Troubleshooting 19 Figure 4 OnLine Diagnostic LED Locations Figure 5 BACnet Module LED ...
Страница 24: ...20 Troubleshooting Figure 6 LonWorks Module LED Locations Figure 7 Ethernet Port LED ...
Страница 28: ...24 Replacement Parts Figure 8 BACnet or N2 Module Figure 9 LonWorks Module ...
Страница 29: ...Replacement Parts 25 Figure 10 OnLine Module Figure 11 Ethernet Router ...
Страница 30: ...26 Replacement Parts Figure 12 Ethernet Switch ...
Страница 31: ...Technical 27 ...
Страница 32: ...28 Technical ...
Страница 33: ...Technical 29 ...
Страница 34: ......