B.  REMOTE MOUNTED BLOWER PACKS – WALL MOUNTING

 

(1) 

Steam and condensate line connections are on the bottom of the blower pack.  The 
condensate connection is 3/8” and the steam lines are 7/8” or 1 ½” depending.  
Ensure that the knock out on the steam inlet has been removed prior to use. 

(2) 

To wall mount the Remote Blower Pack use 2 #12 x 3” long wood screws, supplied 
by others.  These screws must be fastened securely on a 2 x 4 wood stud or 
equivalent support.  If any spacer material is used between the bracket and the 
structural material such as drywall, increase the fastener accordingly.  In addition, 
install a single field supplied fastener in the center hole in the back of the unit to 
prevent the unit from being bumped off the support screws. 

C.  REMOTE MOUNTED BLOWER PACKS – STEAM LINE

 

NOTE 

PRIOR TO CONNECTING THE STEAM HOSE ENSURE KNOCK OUT HAS BEEN 
REMOVED. 

(1) 

Field-supplied hard copper tubing or stainless steel tubing with ½”  thick (min.) 
insulation is recommended for steam supply.  Use NORTEC supplied steam hose 
to make connection from the humidifiers to the metal lines.  See Figure 3 Steam 
Line Installation. 

(2) 

Do not install electric zone valves on steam lines. Improper adjustment will over-
pressurize the humidifier. 

(3) 

NORTEC steam supply hose or field-supplied tubing should be sloped downwards 
from the blower pack to the humidifier. Slope should be at least 2” in 12” (10 
degree slope) to promote condensate run back. See Figure 4 Steam Hose 
Installation.  If upward slope is used from the blower pack to the humidifier, the 
slope should be at least 2” per 12” to promote condensate removal at the blower 
pack.  If this slope is not possible, condensate must be removed before the blower 
pack. See Figure 5 Condensate Removal. 

(4) 

Minimize the length of steam line and keep it as straight as possible, minimizing 
bends. Avoid using 90º elbows. Wherever possible, use long radius turns (using 
tube bender on oversized copper or pairs of 45º elbows). This will reduce the 
condensate generated by heat loss. This will also reduce the back pressure and 
avoid the need to install an extended water trap. 

(5) 

Ensure that the steam hose does not kink or sag. The steam hose becomes more 
flexible when hot. The hose should be supported to prevent water traps.  Only use 
steam hose for connection or steam line runs of 5 feet or less. See Figure 4 Steam 
Hose Installation. 

(6) 

To ensure odor-free steam, always use NORTEC steam hose. Check steam hose 
and hose couplings periodically for cracks, breaks, kinks. Replace as required. DO 
NOT substitute hose.  NORTEC is not responsible for health effects or damage 
from substituted hose. 

(7) 

For GS, SE, and NH Series using large size remote mounted blower packs (>50 
lbs/hr) use 1 5/8” O.D. (Nominal 1 ½”) copper tubing.  For steam runs longer then 
20 ft, use insulated nominal 2” copper to ensure draining of condensate. 

Содержание Blower Packs 380V

Страница 1: ...2008 04 28 2525151 B BLOWER PACKS For All Atmospheric Humidifiers Installation Manual ...

Страница 2: ... LTD LIABILITY NOTICE NORTEC does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts components equipment that are not authorized or approved by NORTEC COPYRIGHT NOTICE Copyright 2008 WALTER MEIER LTD All rights reserved RECORD OF REVISIONS For each revision put the revised pages in your manual and discard the superseded pages Wr...

Страница 3: ...RVIEW Figure 1 NHTC NHPC Series Humidifier with Built On Blower Packs 2 Figure 2 Blower Pack 2 Figure 3 Steam Line Installation 4 Figure 4 Steam Hose Installation 4 Figure 5 Condensate Removal 4 Figure 6 Condensate Return Line Trap 4 Figure 7 Physical Data Dimensions RMBP 7 Figure 8 Blower Pack Spare Parts Exploded View 8 Figure 9 Wiring Diagram Blower Pack Internal Wiring External Connections 10 ...

Страница 4: ...10 00 Page 1 2008 04 28 10 00 OVERVIEW ...

Страница 5: ...and adjustable air supply 4 Control thermostat mounted on the steam distributor starts the fans when steam is generated 5 Refer to Overhead and Frontal Clearance table for blower pack requirements Minimum clearance for the sides of the unit is 4 feet 6 Steam distributors on blower packs have hot surfaces that could result in burns if touched If space allows it is recommended to mount the blower pa...

Страница 6: ... from the blower pack to the humidifier Slope should be at least 2 in 12 10 degree slope to promote condensate run back See Figure 4 Steam Hose Installation If upward slope is used from the blower pack to the humidifier the slope should be at least 2 per 12 to promote condensate removal at the blower pack If this slope is not possible condensate must be removed before the blower pack See Figure 5 ...

Страница 7: ...10 00 Page 4 2008 04 28 Figure 3 Steam Line Installation Figure 4 Steam Hose Installation Figure 5 Condensate Removal Figure 6 Condensate Return Line Trap ...

Страница 8: ...e connected to the nearest floor drain back to the unit NHTC NHPC NHRS only or a condensate pump when using short condensate runs 2 Always incorporate a trap in routing of condensate return lines Condensate that accumulates in trap will prevent possibility of steam escaping Depth of the trap must be equal or more than 3 76 mm See Figure 6 Condensate Return Line Trap 3 Ensure the trap is at least 3...

Страница 9: ...m two pole terminal block of remote blower pack to additional two pole terminal block inside electrical section of humidifier 6 For NH Series use approved wire to connect from ground clamp of remote mounted blower pack to ground clamp provided in the electrical section of humidifier ...

Страница 10: ...10 00 Page 7 2008 04 28 Figure 7 Physical Data Dimensions RMBP ...

Страница 11: ...10 00 Page 8 2008 04 28 Figure 8 Blower Pack Spare Parts Exploded View Rev C April 17 2008 ...

Страница 12: ... 2524204 Transformer 100VA 115V 380V 50 60Hz For 380V models only 1 2 2524082 Fuse 1 amp 600V HCTR Slow Blow 2 3 1583126 Fuse 1 5 amp 2 4 2522070 Relay 30A 115V SPDT 1 5 1073005 Thermostat Replace 1475005 O ring for thermostat at same time 1 6 1475005 O Ring for Thermostat 1 7 2522222 Blowerpack Fan Kit 1 Fan kit is pre assembled and includes all items identified by box on exploded view ...

Страница 13: ...10 00 Page 10 2008 04 28 Figure 9 Wiring Diagram Blower Pack Internal Wiring External Connections Wiring Diagram 2524117 Rev B March 26 2007 ...

Страница 14: ...10 00 Page 11 2008 04 28 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 15: ...u of all other warranties expressed or implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY 4 THE COMPANY s limited warranty on accessories not of the companies manufactu...

Страница 16: ...tor Avenue Ogdensburg NY 13669 TEL 1 866 NORTEC 1 EMAIL northamerica climate waltermeier com WEBSITE www humidity com CANADA Walter Meier Climate Canada Ltd 2740 Fenton Road Ottawa ON K1T 3T7 TEL 1 866 NORTEC 1 FAX 613 822 7964 Authorized Agent ...

Отзывы: