Vertical Vent Termination

Firestop

Firestop/

Support

Roof

Flashing

Roof

Jack

Storm

Collar

Rain

Cap

Hanger

Strap

Elbow

Condensation

Drain (Install
According to

Local Codes)

Appliance

Adapter*

**1' Min. - 3' Max.

* Adapter not required when 
  using Noritz N-Vent.

**1' minimum recommended,
but not required. Avoid installing
elbow directly on flue.

• Terminate at least 6' from the combustion air

intake of any appliance, and 3' from any
other building opening, gas utility meter, service
regulator etc.

• Enclose exterior vent systems below the roof

line to limit condensation and protect  against
mechanical failure.

• When the vent penetrates a floor or ceiling and

is not running in a fire rated shaft, a firestop and
support is required.

• When the vent termination is located not less

than 8' from a vertical wall or similar obstruc-
tion, terminate above the roof at least 2', but not
more than 6', in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.

• Provide vertical support every 12' or as required

by the vent pipe manufacturer's instructions.

• Slope the horizontal vent 1/4" for every 12" to-

wards the drain tee.

• A short horizontal section is recommended to

prevent debris from falling into the water heater.

• Install a condensation drain in the horizontal

section of the venting. For installations in tight
spaces where there is not enough room to in-
stall two elbows and a horizontal drain tee, a
vertical drain tee may be substituted.

Horizontal Vent Termination

• Terminate at least 12" above grade or

above snow line.

• Terminate at least 7' above a public walk-

way, 6' from the combustion air intake of
any appliance, and 3' from any other
building opening, gas utility meter, ser-
vice regulator etc.

• Terminate at least 3' above any forced air

inlet within 10', 4' below, 4' horizontally
from or 1' above any door, window, or
gravity air inlet into any building per National
Fuel Gas Code ANSI Z223.1/NFPA 54.

• Slope the horizontal vent 1/4" downwards

for every 12" toward the termination.

• Use a condensation drain if necessary.
• In the Commonwealth of Massachusetts

a carbon monoxide detector is required
for all side wall horizontally vented gas
fuel equipment.  Please refer to Technical
Bulletin TB 010606 for full installation in-
structions.

Appliance

Adapter*

Elbow

Hanger

Straps

Wall

Thimble

Termination

**1' Min. - 3' Max.

Slope vent

Downwards

* Adapter not required when 
  using Noritz N-Vent.

**1' minimum recommended,
but not required. Avoid installing
elbow directly on flue.

Содержание proTough NR98SV

Страница 1: ...the customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death NORITZ AMERI...

Страница 2: ...troller Cord 10ft 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap VC4 1 1 Quick Connect Cord Q ty Shape Par...

Страница 3: ...tween the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent he...

Страница 4: ...rwise impure treat the water with approved methods in order to ensure full warranty coverage WARNING CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the...

Страница 5: ...e Dust may block the air supply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation in places where special chemical agents e g...

Страница 6: ...ove the roof line in an outdoor instal lation use high temperature sealant around the flue collar for rain protection Avoid installation where the unit will be exposed to excessive winds Before instal...

Страница 7: ...8 or more on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary If possible leave 3 or more above an...

Страница 8: ...lk or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the...

Страница 9: ...t into any building 3 above any forced air inlet within 10 Vent Clearances When Heater is In stalled Outdoors With a Vent Cap All clearance requirements are in accordance with ANSI Z21 10 3 and the Na...

Страница 10: ...be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a ve...

Страница 11: ...r will be required to properly connect the vent to this appliance Consult the manufacturer s instructions for the proper appli ance adapter Vent Piping Noritz N Vent is suggested for the vent system I...

Страница 12: ...section is recommended to prevent debris from falling into the water heater Install a condensation drain in the horizontal section of the venting For installations in tight spaces where there is not e...

Страница 13: ...is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per m...

Страница 14: ...the gas line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz NR98 SV 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 5...

Страница 15: ...Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 888 2078 1...

Страница 16: ...stem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mix...

Страница 17: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Страница 18: ...SV Cold to Water Heater Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush...

Страница 19: ...ump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a high...

Страница 20: ...eater may cause electrical interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until electrical wiring is finished Disconnect power before servicing Failure...

Страница 21: ...or as shown on the right 5 Replace the front cover of the water heater 4 screws 6 Reconnect electrical power to the water heater but do not turn it on 7 Press and hold the FLOW METER ALARM SET button...

Страница 22: ...and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of sl...

Страница 23: ...hich 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not availab...

Страница 24: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Страница 25: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Страница 26: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 27: ...1 4 8 2 8 4 5 5 9 7 8 3 1 1 4 7 0 GAS INLET 3 4 4 0 5 2 0 3 x 0 6 OBLONG HOLE HEIGHT OF EACH FITTINGS FROM BOTTOM OF CASE HOT WATER OUTLET COLD WATER INLET GAS INLET WIRING THROUGHWAY WATER DRAIN VAL...

Страница 28: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locat...

Страница 29: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 30: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Отзывы: