Clearance Requirements from Vent Terminations to Building Openings

* All clearance requirements are in accordance with ANSI Z21.10.3 and the National Fuel Gas Code, 

ANSI Z223.1 and in Canada, in accordance with NSCNGPIC.

Description

Ref

A=

Clearance above grade, veranda, porch, 

deck, or balcony

B=

Clearance to window or door that may 

be opened

C=

Clearance to permanently closed window

D=

Vertical clearance to ventilated soffit 
located above the terminal within a 
horizontal distance of 2 feet (61 cm) 
from the center line of the terminal

*

E=

Clearance to unventilated soffit

*

F=

Clearance to outside corner

*

G=

Clearance to inside corner

*

H=

Clearance to each side of center line 
extended above meter/regulator assembly

3 ft (91 cm) within a height
15 ft (4.5 m) above the
meter/regulator assembly

I=

Clearance to service regulator vent outlet

3 ft (91 cm)

J=

Clearance to nonmechanical air supply 

inlet to building or the combustion air inlet 

to any other appliance

K=

Clearance to a mechanical air supply inlet

 6 ft (1.83 m)

L= Clearance above paved sidewalk or paved 

driveway located on public property
Clearance under veranda, porch, deck, 

or balcony

7 ft (2.13 m)†

M=

1

 In accordance with the current CSA

 B149.1 Natural Gas and Propane Installation Code

2

 In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

† A

 vent shall not terminate directly above a sidewalk or paved driveway that is located between two single

   family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor

.

* Clearance in accordance with local installation codes and the requirements of the gas supplier

.

 

Clearance to opposite wall is 24 inches (60 cm).

12 in (30 cm)‡

*

12 in (30 cm)

36 in (91 cm)

*

*
*
*

*

*

*

*

3 ft (91 cm) above if within

10 ft (3 m) horizontally

*

12 in (30 cm)

4 ft (1.2 m) below or to side

of opening; 1 ft (30 cm

)

above opening

36 in (91 cm)

4 ft (1.2 m) below or to side

of opening; 1 ft (30 cm

)

above opening

US Non-Direct Vent

Installations 

2

Canadian Non-Direct Vent

Installations 

1

Vent Terminal

D

E

B

B

F

B

A

G

H

I

C

B

M

K

J

B

B

L

Air Supply Inlet

Area Where Terminal
is Not Permitted

A

Содержание NC1991-OD

Страница 1: ...uctions Failures and damage caused by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Inst...

Страница 2: ...ed below are not included with the units but may be necessary for installation Quick Connect Cord QC 2 Q ty Shape Part Part Shape Q ty 1 1 Remote Controller Cord 26ft 8m 1 each Isolation Valves includ...

Страница 3: ...ater temperature will become unstable as the pipe length increases Quick Connect cord Union Gas Valve Union Shutoff Valve Shutoff Valve Hot Water Cold Water Leave enough clearance around the plumbing...

Страница 4: ...ater supply as unexpected accidents may occur as a result Check Water Supply Quality If the water supply is in excess of 12 grains per gallon 200 mg L of hardness acidic or otherwise impure treat the...

Страница 5: ...heat Also consider the surrounding trees and animals The heat and moisture from the water heater may cause discoloration of walls and resinous materials or corrosion of aluminum materials Do not loca...

Страница 6: ...f 24 600mm or more in front of the unit to facilitate inspection and repair Do install the unit such as the wall of the second floor where the unit is out of reach When installing the unit in a common...

Страница 7: ...a mechanical air supply inlet 6 ft 1 83 m L Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 7 ft 2 13 m M 1 In accordance with...

Страница 8: ...arts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution...

Страница 9: ...Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 10 3m 10 3...

Страница 10: ...787 1496 55 112 213 440 675 1260 Maximum Capacity of Flex TracPipe in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 206 383...

Страница 11: ...be connected to any heating system or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of...

Страница 12: ...e Use shower heads with low pressure loss If necessary use a pump or other means to ensure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount...

Страница 13: ...nt Required Treatment Required Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install No...

Страница 14: ...tat if the water heater is not controlling the pump Set the Aquastat to 10 F 5 C below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits inclu...

Страница 15: ...ly required by the water heater is 120VAC at 60 Hz The power consumption may be up to 228W or higher if using optional accessories Use an appropriate circuit Do not disconnect the power supply when no...

Страница 16: ...te controller is removed 185 F 85 C 140 F 60 C 135 F 57 C 120 F 50 C To change the default temperature adjust the dip switches as described below The default temperature is 120 F 50 C 1 Disconnect ele...

Страница 17: ...ode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of...

Страница 18: ...e controller 2 Disconnect then reconnect electrical power to the water heater 3 Press the MENU Button inside the cover select Initial settings using the Buttons 4 Press the ENTER button the Initial se...

Страница 19: ...m a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 20: ...mp Ground wire Connector Use one of the vacant holes Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord...

Страница 21: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Страница 22: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 23: ...NG HOLE NC1991 OD 1 8 45mm 2 2 55mm 2 2 56mm GAS INLET COLD WATER INLET HOT WATER OUTLET AIR INLET AIR INLET WIRING THROUGHWAY WATER DRAIN VALVE WATER FILTER HOT WATER OUTLET WATER DRAIN VALVE WIRING...

Страница 24: ...nutes of connecting electrical power before turning on the Power On Off Button press the or button on the remote controller and hold until the display blinks 99 If 99 does not blink on the remote cont...

Страница 25: ...is system will make hot water more quickly available to remote fixtures The pump will circulate water through the loop until the entire loop is warm and then the system controller will turn off the pu...

Страница 26: ...tat Pump Control Wires use external relayU Unit 1 Set Yes for the question Start pump rotation in system settings See SC 301 6M Installation Manual When installing 2 pumps in parallel Set Yes for the...

Страница 27: ...PCB Power PCB B5 B5 System Controller No 5 No 4 No 3 No 2 Remote Control terminal block Remote control terminal block Remote Controller Cord PCB Power PCB PCB Power PCB Multi System Wiring Use SC 301...

Страница 28: ...order to use this product safely read this installation manual carefully and follow the installation instructions Potential dangers from accidents during installation and use are described below Clos...

Страница 29: ...List The value in indicates the quantity Remote Controller Mounting bracket Round countersunk head wood screw Wall anchor Raised countersunk head screw For junction box installation Machine screw Whe...

Страница 30: ...f the remote controller and the frame pull the entire decorative frame forward while pressing the sections indicated where the fingers are in the figure below If it does not come off insert a flat hea...

Отзывы: