10.

 Water Piping

This appliance is suitable for potable water and space heating applications. Do not use this appliance if any part has

been underwater.  Immediately call a qualified service technician to inspect the appliance and replace any part of the

control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold

water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb-

ing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with

either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or

The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve must

be capable of an hourly Btu rated temperature steam discharge of 380,000 Btuh. Multiple valves may be used. The

pressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and the water

heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal

when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge line

must be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separate

storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must also

comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI

Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with the

probe directly in the flow of water. This may cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.

A water heater used to supply potable water may not be connected to any heating system or components previously

used with a nonpotable water heating appliance.

When water is required in one part of the system at a higher temperature than in the rest of the system, means such

as a mixing valve shall be installed to temper the water to reduce the scald hazard.

• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.

• Take appropriate heat insulation measures (e.g., wrapping with heat insulation materials, using electric heaters)

according to the climate of the region to prevent the pipe from freezing.

• Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.

• Do not use piping with a diameter smaller than the coupling.

• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measures.

• Avoid using joints as much as possible to keep the piping simple.

• Avoid piping in which an air holdup can occur.

• Use approved piping materials.

• If installing the unit on a roof:

If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied to

the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressure

is maintained at this level.

Check the pressure before putting the unit into operation.

Failing to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and

may cause the unit to shut down frequently.

Supply water piping

• Do not use PVC piping.

• Mount a check valve and a shut off valve (near

the inlet).

• In order for the client to use the water heater

comfortably, 98.1 to 491 kPa (14 to 70 PSI) of

pressure is needed from the water supply.

Be sure to check the water pressure. If the water

pressure is low, the water heater cannot perform

to its full capability, and may become a source of

trouble for the client.

Drain piping

• Expansion water may drop from the pressure

prevention device and wet the floor. If neces-

sary, provide drain piping or use a drain hose to

remove the water.

Hot water piping

• Do not use lead or PVC piping.

• The longer the piping, the greater the heat loss.

Try to make the piping as short as possible.

• Use mixing valve with a low water resistance.

Use shower heads with low pressure loss.

• If necessary, use a pump or other means to en-

sure that the supply water pressure to the inlet

of the heater does not fall below 29 PSI when

the maximum amount of water is being de-

manded. Also install a pressure meter on the in-

let. If this is not done, local boiling will occur in-

side the water heater causing abnormal sounds

and decreasing the durability of the heat ex-

changer.

Ask a qualified plumber to perform the installation

of the plumbing. Observe all applicable codes.

Содержание N-132M

Страница 1: ...supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Owner s Gu...

Страница 2: ...e 29 Hot Water Feed Route 31 Electronic Control Unit 35 Electronic Control Unit Remote Controller and Attached Set 36 Installation Manual 37 1 Included Accessories 38 2 Optional Accessories 38 3 Quick...

Страница 3: ...erious injury and even death when ignored Denotes content that may result in fire serious injury and even death when ignored Denotes content that may result in bodily injury and physical damage when i...

Страница 4: ...e bath tub Do not turn off the water heater or change the water temperature while someone is using Be sure the gas power supplied matches the gas on the rating plate Warning Important Safety Informati...

Страница 5: ...from vent pipe Do not place combustibles such as laundry newspapers oils etc near the heater or the exhaust vent terminal Exhaust vent terminal indoor installation Indicates suggested clearances for m...

Страница 6: ...hot water supply shower and bath Do not touch the exhaust vent pipe during or immediately after operation of the water heater Do not use hair spray or spray detergent in the vicinity of the heater If...

Страница 7: ...red by the warranty Take necessary measures to prevent freezing of water and leakage of gas when leaving the unit unused for long periods of time p 18 If it is snowing check the air inlet exhaust gas...

Страница 8: ...el The above illustration shows an example of installation The exact installation configuration may be slightly different Main Unit Flue Collar Front Cover Air Inlet Water Supply Valve Gas Supply Valv...

Страница 9: ...other settings Power On Off Button For turning the heater on and off Flow Meter Alarm Set Button For setting the flow meter alarm p 14 and 15 Setting Buttons Before use remove the protective sheet fr...

Страница 10: ...t button p 15 Error Code When this indicator is lit the hot water temperature can be set p 13 Priority Indicator The illustration below shows the remote controller display What is actually displayed d...

Страница 11: ...r make the following preparations Follow steps 1 through 4 1 Open the water supply valve Open a hot water fixture to confirm that water is available and then close the fixture again 3 Open the gas sup...

Страница 12: ...rature To prevent scalding Check the water temperature by hand before bathing or showering When setting the unit to 125 F or higher the temperature display will flash for 10 seconds as a high temperat...

Страница 13: ...re settings below are examples The temperature setting necessary depends on the usage the length of piping and the time of year Initial factory setting is 110 F If fixtures incorporate mixing valves s...

Страница 14: ...Button 1 Plug the bath drain Preparation Starting with the power off Always check temperature setting before use Hot Cold On The temperature will be displayed on the remote control thermostat Previou...

Страница 15: ...ns 10 60 In 5 gallon intervals 70 100 In 10 gallon intervals or 990 gallons Note The alarm will not sound if it is set for 990 gal Note The alarm will not sound if it is set for 990 gal On Flow meter...

Страница 16: ...an be muted if it is desired 1 How to Use Muting the Remote Controller Initial factory setting is with sound Sound Muted No sound after 5 sec 1 With the remote controller off hold the Power On Off But...

Страница 17: ...next page Preventing Damage from Freezing 1 Freezing is prevented within the device automatically by the freeze prevention heater If water will not flow because it is frozen 1 Close the gas and water...

Страница 18: ...e unit 6 When the water is completely drained replace all drain plugs and close the hot water fixtures If the water heater will not be used for a long period of time Drain the water Drain the water as...

Страница 19: ...r is water resistant but not water proof Keep it is dry as possible Caution Regular Maintenance 1 Periodic Inspection Check For laundry newspaper timber oil spray cans and other combustible materials...

Страница 20: ...er with a brush under running water 6 Replace the filter and close the drain plugs Take care not to lose the packing 7 Close all hot water fixtures 8 Open the water supply valve and check that water d...

Страница 21: ...ower button turned on Are the gas and water supply valves fully open Is the water temperature setting appropriate p 12 and p 13 If the water supply temperature is high it is possible for the temperatu...

Страница 22: ...able but it should stabilize after a short time There are some types of hot water taps that discharges large volumes of hot water initially but stabilize after time To keep the temperature stable the...

Страница 23: ...le The fan may run to prevent freezing The fan can be heard when it is very cold outside Other The heater stops burning during operation Are the gas and water supply valves fully open Is the water sup...

Страница 24: ...t Abnormal combustion low gas supply pressure Error Code Cause Action If the alarm doesn t sound Open a door or window to let air in Close the hot water fixtures Press the power button to turn the uni...

Страница 25: ...rrected contact our sales agent If you want to reinstall the appliance at a different location confirm that the gas and power supply indicated on the rating plate are available at the new location If...

Страница 26: ...s Steel Copper Sheeting Copper Tubing Flame Rod Thermal Fuse Pressure Relief Valve Back Pressure Switch Lightning Protection Device ZNR Electric Leakage Prevention Device GFCI Overheat Prevention Devi...

Страница 27: ...27 External outfitting 052 025 026 025 026 003 006 002 001 005 004 012 007 012 007 056 056 018 019 022 023 024 027 029 050 034 035 050 050 040 050 050 050 053 054 050 036 050 037 055 055...

Страница 28: ...5 Front packing H CMN CMNL013 2 026 Front packing V CMN CMNL014 2 027 Current leakage safety device DTJ DTJJ015 1 029 Connection diagram label EJH EJHK002 1 034 Junction box set EHU EHUA008 1 035 Junc...

Страница 29: ...100 128 152 119 050 121 050 136 132 053 129 135 050 127 126 050 130 156 114 117 056 151 151 118 110 156 111 149 155 155 151 134 116 154 125 050 120 105 103 104 108 101 050 102 050 106 107 122 112 113...

Страница 30: ...21 1 120 Fixing plate for burner case left DMA DMAA022 1 121 Mounting plate for igniter DMA DMAA016 1 122 Manifold seal packing L DMA DMAL018 2 123 Manifold seal packing S DMA DMAL019 2 125 Main dampe...

Страница 31: ...ection procedure Left side view Case rear Right side view Front view 404 403 401 401 416 415 B A 416 415 050 423 154 154 417 050 419 418 050 424 050 422 420 421 401 416 151 405 405 415 414 152 406 402...

Страница 32: ...488 487 485 471 444 492 446 514 476 445 495 440 505 427 492 471 462 441 151 A B 454 458 056 465 443 447 444 448 513 512 446 492 471 493 491 433 492 492 493 491 445 471 444 435 513 446 512 434 481 480...

Страница 33: ...8 Bypass coupling EHA EHAD014 1 433 Water inlet pipe EHA EHAD001 1 434 Water flow sensor set 1 DUV DUVD017 1 435 Magnetic sensor BWC BWCD093 1 440 Freeze preventive heater3 BGD BGDH002 4 441 Heater fa...

Страница 34: ...fastner 12 7 6340202 2 492 Quick fastner 16A 6340300 6 493 O ring P12 5C 3359808 2 495 Mixing coupling EHA EHAD011 1 497 Mixing body EHA EHAD010 1 498 O ring P22C 7573308 1 505 Cross straight recessed...

Страница 35: ...ronic control unit Special part Special part no Special part instruction manual 888 702 703 709 053 700 706 752 751 753 754 755 801 802 Remote controller kitchen remote controller RC 7646M 2 USA Attac...

Страница 36: ...709 Relay case waterproof cover DMA DMAA026 1 751 RC 7646M 2 body USA QME QMEJ005 1 752 Drssed frame body QME QMEA003 1 753 Wall packing QHU QHUA115 1 754 Oar plug 6X25 755 Cross recessed round wood s...

Страница 37: ...heater safely read this installation manual carefully and follow the installation instructions Caution WARNING If the information in this manual is not followed exactly a fire or explosion may result...

Страница 38: ...1 Remote Controller See p 54 Remote Controller Cord 10 ft 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation VC 132 Outdoor Ven...

Страница 39: ...in pipe length between the two units When connecting 2 devices use only a single remote controller Note Connect the remote controller to only one of the devices System Diagram Insulate the hot water...

Страница 40: ...ity If the water supply is hard acidic or otherwise impure treat the water with approved methods in order to ensure full warranty coverage Use Extreme Caution if Using With A Solar Pre Heater Using th...

Страница 41: ...ering in the equipment Avoid installation in places where dust or debris will accumulate Dust may block the air supply opening causing the perfor mance of the device fan to drop and incomplete combust...

Страница 42: ...t to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary Securing of space for repair inspection 24 or more 8 or more 8 or more M...

Страница 43: ...bove paved sidewalk or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installati...

Страница 44: ...or gravity air inlet into any building 3 above any forced air inlet within 10 Vent Clearances When Heater is In stalled Outdoors With a Vent Cap Clearance Requirements from Vent Terminations to Buildi...

Страница 45: ...nd hang the unit by the upper wall mounting bracket 3 Determine the positions for the remaining four screws two for the top bracket and two for the bottom and remove the unit The weight of the device...

Страница 46: ...llow the vent pipe manufacturer s installation instructions Make the vertical section of the exhaust vent as short as possible Maintain the same vent pipe diameter all the way to the end Pipe diameter...

Страница 47: ...and protect against mechanical failure When the vent penetrates a floor or ceiling and is not running in a fire rated shaft a firestop and support is required Terminate the vent system at least 3 abo...

Страница 48: ...door air If the unit is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 100 cubic fe...

Страница 49: ...cal codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter Noritz N 132M 380 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 10 10 10 10 5 5 5 5 Gas Fire...

Страница 50: ...n Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 88...

Страница 51: ...e rest of the system means such as a mixing valve shall be installed to temper the water to reduce the scald hazard Flush water through the pipe to clean out metal powder sand and dirt before connecti...

Страница 52: ...s a mixing valve shall be provided to temper the water for the other uses to help prevent scalding For Space Heating Purposes Check Valve Aquastat Use Aquastat if Unit Isn t Controlling Pump Aquastat...

Страница 53: ...r servicing Field wiring to be performed at time of appliance installation Caution Do not let the power cord contact the gas piping Tie the redundant power cord outside the water heater Putting the re...

Страница 54: ...ing the Flow Meter Alarm Set button for 0 5 seconds will switch the indicated item number from OFF to ON or ON to OFF If the Priority lamp is flashing when an item number is displayed this indicates a...

Страница 55: ...purchased Part RC CORD26 or use 18AWG wire Install according to the National Electrical Code and all applicable local codes Connecting Remote Controller Cord to Unit Keep the remote controller cord a...

Страница 56: ...tly from a wall circuit to the pump 5 Replace the front cover Pump Control Wire Tag Supplies Power for Circulating Pump Use a Relay for Larger Pumps Connecting the pump control wire Pump Wiring This f...

Страница 57: ...lly for a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technici...

Страница 58: ...technician Shutdown Instructions 1 Stop any water demand 2 Turn off electric power 3 Turn the gas control manual valve clockwise to the off position Should overheating occur or the gas supply fail to...

Страница 59: ...BR O GY W Y BR O GY BK BK O GY BK BL Y W R BL BR BR BL R W Y BL BK GY O O GY BK BK Y BR BL W CN10 G WW W BK W CN1 CN89 BL BL O W R BK Y BL CN102 CN78 W W W BK CN63 R R W O BK V G Y W BK BL W O BK V G...

Страница 60: ...onnect Cord through the wiring throughway and into the unit 4 Plug the connector on the Quick Connect Cord to the receptacle inside the unit 5 Attach the ground wire of the Quick Connect Cord to the t...

Страница 61: ...Gas Pipe Hot Water Return Line Size the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Conn...

Страница 62: ...the pump set dipswitch 2 to OFF See SC 201 6M Installation Manual page 13 Do not connect more than one pump to the tank thermostat Hot Water Supply Remote Controller Option 2 Unit Control Option 1 Tan...

Страница 63: ...2345678 B5 B5 System Controller No 5 No 4 No 3 No 2 Remote Control terminal block Remote control terminal block System select connectors Disconnect this Connector Disconnect this Connector Disconnect...

Страница 64: ...ORPORATION Note Do not connect power to the water heater before the remote controller has been properly installed Do not disassemble the remote controller Wall Packing Connecting Wire Remote Controlle...

Страница 65: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 66: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Страница 67: ...67...

Страница 68: ...68...

Страница 69: ...69...

Отзывы: