Vertical Vent Termination

Firestop

Firestop/

Support

Roof

Flashing

Roof

Jack

Storm

Collar

Rain

Cap

Hanger

Strap

Elbow

Condensation

Drain (Install
According to

Local Codes)

Appliance

Adapter*

**1' Min. - 3' Max.

* Adapter not required when 
  using Noritz N-Vent.

**1' minimum recommended,
but not required. Avoid installing
elbow directly on flue.

• Terminate at least 6' from the combustion air

intake of any appliance, and 3' from any
other building opening, gas utility meter, service
regulator etc.

• Enclose exterior vent systems below the roof

line to limit condensation and protect  against
mechanical failure.

• When the vent penetrates a floor or ceiling and

is not running in a fire rated shaft, a firestop and
support is required.

• Terminate the vent system at least 2' above, but

not more  than 6' above the roof line, or accord-
ing to the vent pipe manufacturer's instructions.

• Terminate the vent system at least 2' above any

portion of a building located within 10' horizon-
tally.

• Provide vertical support every 12' or as required

by the vent pipe manufacturer's instructions.

• Slope the horizontal vent 1/4" for every 12" to-

wards the drain tee.

• Do not vent straight upwards.

Always have a horizontal section of venting.

• Install a condensation drain in the horizontal

section of the venting.

Horizontal Vent Termination

• Terminate at least 12" above grade or

above snow line.

• Terminate at least 7' above a public walk-

way, 6' from the combustion air intake of
any appliance, and 3' from any other
building opening, gas utility meter, ser-
vice regulator etc.

• Terminate at least 3' above any forced air

inlet within 10', 4' below, 4' horizontally
from or 1' above any door, window, or
gravity air inlet into any building per National
Fuel Gas Code ANSI Z223.1/NFPA 54.

• Slope the horizontal vent 1/4" downwards

for every 12".

• Use a condensation drain if necessary.
• In the Commonwealth of Massachusetts

a carbon monoxide detector is required
for all side wall horizontally vented gas
fuel equipment.  Please refer to Technical
Bulletin TB 010606 for full installation in-
structions.

Appliance

Adapter*

Elbow

Hanger

Straps

Wall

Thimble

Termination

**1' Min. - 3' Max.

Slope vent

Downwards

* Adapter not required when 
  using Noritz N-Vent.

**1' minimum recommended,
but not required. Avoid installing
elbow directly on flue.

Содержание N-0931M-ASME

Страница 1: ...customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death Installation mus...

Страница 2: ...er s Guide Warranty Installation Manual this document 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Outdoor Vent Cap VC4 1 1...

Страница 3: ...een the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat...

Страница 4: ...he water with approved methods in order to ensure full warranty coverage CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is sized for...

Страница 5: ...e Dust may block the air supply opening causing the performance of the device fan to drop and incomplete combustion to occur as a result Avoid installation in places where special chemical agents e g...

Страница 6: ...re the unit will be exposed to excessive winds Before installing make sure that the vent termination or the vent cap in an outdoor installation will have the proper clearances according to the Nationa...

Страница 7: ...ave 8 or more on either side of the unit to facilitate inspection If possible leave 24 or more in front of the unit to facilitate maintenance and service if necessary If possible leave 3 or more above...

Страница 8: ...lk or paved driveway located on public property Under veranda porch deck or balcony 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the...

Страница 9: ...he outdoor vent cap If it is necessary to vent above the roof line in an outdoor installation also use the base of the vent cap for rain protection Vent Clearances When Heater is In stalled Outdoors W...

Страница 10: ...be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a ve...

Страница 11: ...ting system Vent Piping Use only UL listed category III vent materials Follow the vent pipe manufacturer s installation instructions Make the vertical section of the exhaust vent as short as possible...

Страница 12: ...anufacturer s instructions Slope the horizontal vent 1 4 for every 12 to wards the drain tee Do not vent straight upwards Always have a horizontal section of venting Install a condensation drain in th...

Страница 13: ...is installed in a mechanical closet provide a 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 90 cubic feet of fresh air per m...

Страница 14: ...s line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 250 000 Btuh Clothes Dryer 35 000 Btu...

Страница 15: ...in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 8...

Страница 16: ...em or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mixin...

Страница 17: ...wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or ot...

Страница 18: ...Optional Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1...

Страница 19: ...pump 4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a hig...

Страница 20: ...e water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Ground To prevent electrical shock provide a ground with resistance l...

Страница 21: ...emote controller according to the instructions in the Installation Guide p 31 The Noritz Tankless Gas Water Heater can be programmed so that it will default to one of four tempera tures if the remote...

Страница 22: ...and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of sl...

Страница 23: ...hich 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not availab...

Страница 24: ...lack 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3...

Страница 25: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Страница 26: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 27: ...WAY 120VAC VIEW FROM TOP 14 4 11 7 7 120VAC WIRING THOROUGHWAY COLD WATER INLET 3 4 WIRING THOROUGHWAYS HOT WATER OUTLET 3 4 16 Multi System A Installation without a recirculation system Insulate or a...

Страница 28: ...Pipe Hot Water Return Line Size the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connecto...

Страница 29: ...ontrol When installing 2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 2 6 GPM Install the pl...

Страница 30: ...onnect this Connector Disconnect this Connector Disconnect for system controller Disconnect for system controller Disconnect this Connector Remote Controller Cord PCB Power PCB PCB Power PCB Disconnec...

Страница 31: ...otes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locat...

Страница 32: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 33: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Отзывы: