Installation Clearances
Before installing, check for the following:
Install in accordance with relevant building and mechanical codes, as well as any local, state
or national regulations.
Item
Distance from combustibles
• Maintain the following clearances
from both combustible and
non-combustible materials.
• There must be a clearance of 610mm
(24") or more in front of the Flue terminal.
• This restriction will not be applied to an
area where an effective shield makes a
clearance of 610mm (24") or more in
front of the exhaust outlet.
Check
Illustration
Caution
• If possible, leave 203mm (8") or more on
either
side of the unit to facilitate in-
spection.
• If possible, leave 610mm (24") or more in
front of the unit to facilitate maintenance
and service if necessary.
Securing of space for
repair/inspection
610mm
(24") or
more
203mm
(8") or
more
203mm
(8") or
more
Outdoor Clearances to Opening
into Any Building
Distance from
the top surface
Distance from
the side
305mm
(12") or
more
50mm (2")
or more
Consult vent
manufacturer
for clearances
305mm
(12") or
more
305mm (12")
or more
There must be no
building opening
within this area.
305mm (12")
or more
Flue terminal
305mm
(12") or
more