 Water Piping

This appliance is suitable for combination potable water and space heating applications. It cannot be used for space 

heating applications only. Do not use this appliance if any part has been underwater.  Immediately call a qualified 

service technician to inspect the appliance and replace any part of the control system and gas control which has 

been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the 

cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local 

plumbing inspector on how to control this situation.
A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying 

with  either The  Standard  for  Relief  Valves  and Automatic  Shutoff  Devices  for  Hot  Water  Supply  Systems, ANSI 

Z21.22, or The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief 

valve must be capable of an hourly Btu rated temperature steam discharge of 199,900 Btuh. Multiple valves may be 

used. The pressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and 

the water heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for 

disposal when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The 

discharge line must be installed to allow complete drainage of both the valve and the line. If this unit is installed with 

a separate storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve 

must also comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply 

Systems, ANSI Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install 

the valve with the probe directly in the flow of water. This may cause unwarranted discharge of the valve.
Piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.

A  water  heater  used  to  supply  potable  water  may  not  be  connected  to  any  heating  system  or  components 

previously used with a nonpotable water heating appliance.

When water is required in one part of the system at a higher temperature than in the rest of the system, means 

such as a mixing valve shall be installed to temper the water to reduce the scald hazard.

Installation and service must be performed by a qualified plumber.  In the 

Commonwealth of Massachusetts, this product must be installed by a licensed 

plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel 

Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

•  Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.

•  Perform the following insulation measures for prevention of freezing. 

-  Take appropriate heat insulation measures (e.g., wrapping with heat 

insulation materials, using electric heaters) according to the climate 

of the region to prevent the pipe from freezing.

-  Make sure that there are no water leaks from the cold and hot water 

supply pipes, then insulate the pipes completely. 

-  Be sure to also completely insulate the water supply valve and the 

cold and hot water connections on the water heater (refer to the fig

-

ure on the right).  

-  Do not cover the water drain plug with insulation so that water in the 

pipe can be drained. (Refer to the figure in the right.)  

• 

Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.

•  Do not use piping with a diameter smaller than the coupling.

•  When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure

.

•  Avoid using joints as much as possible to keep the piping simple.

•  Avoid piping in which an air holdup can occur.

•  If installing the unit on a roof:

•  About lower-level hot water supply

  If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied 

to the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water 

pressure is maintained at this level.

  Check the pressure before putting the unit into operation.

  Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and 

may cause the unit to shut down frequently.

Completely insulate 

the water inlet and 

outlet fittings.

Insulate the water 

supply valve completely

.

Do not cover the water 

drain plug with insulation

so that water in the pipe 

can be drained.

Pipe 

Size

Length  (including fittings)

10'

20'

30'

40'

50'

60'

70'

80'

90'

100'

125'

150'

200'

(3m)

(6m)

(9m) (12m) (15m) (18m) (21m) (24m) (27m) (30m) (38m) (45m)

(60m)

1/2"

275

189

152

129

114

103

96

89

83

78

69

63

55

3/4"

567

393

315

267

237

217

196

185

173

162

146

132

112

1"

1,071

732

590

504

448

409

378

346

322

307

275

252

213

1 1/4"

2,205

1,496

1,212

1039

913

834

771

724

677

630

567

511

440

1 1/2"

3,307 2,299 1,858 1,559 1,417 1,275 1,181

1,086

1,023

976

866

787

675

2"

6,221

4,331

3,465

2,992

2,646

2,394 2,205 2,047 1,921 1,811

1,606 1,496 1,260

Содержание GQ-C3257WZ US

Страница 1: ...or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion After completing ins...

Страница 2: ...Part Part Shape Q ty 1 1 Remote Controller Cord 26ft 8m 1 each Isolation Valves includes pressure relief valve Pipe Cover PC 3S SUS 1 1 Owner s Guide Warranty Installation Manual this document 1 Syst...

Страница 3: ...Block Cord Connector Cord Connector 3 Quick Connect Multi System Installation The Quick Connect Multi System allows the installation of two units together utilizing only the Quick Connect Cord Typica...

Страница 4: ...erature of the water supply as unexpected accidents may occur as a result Check Water Supply Quality If the water supply is in excess of 12 grains per gallon 200 mg L of hardness acidic or otherwise i...

Страница 5: ...he water heater may cause discoloration of walls and resinous materials or corrosion of aluminum materials Do not locate the vent termination directed towards a window or any other structure which has...

Страница 6: ...width Provide clearance of 24 600mm or more in front of the unit to facilitate inspection and repair Do install the unit in a location where the unit is out of reach such as the wall of the second flo...

Страница 7: ...149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that...

Страница 8: ...arts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution...

Страница 9: ...e installer The installer must be professionally trained to do such work and must always follow all local and national codes and regulations Gas line sizing calculations must be performed for every in...

Страница 10: ...ding to total btuh demand of the building and length from the meter or regulator so that the following supply pressures are available even at maximum demand WARNING Natural Gas Supply Pressure Min 4 W...

Страница 11: ...se 50 15m 175 000 Btuh requires 1 Outlet E 25 7 5m Use 30 9m 199 900 Btuh requires 3 4 Section 4 45 13 5m Use 50 15m 355 000 Btuh requires 1 1 4 Natural Gas Meter Noritz Condensing Tankless Gas Water...

Страница 12: ...t each appliance to verify all appliances are receiving a minimum of 5 WC for NG or 8 WC for LP If all appliances are not receiving the minimum inlet pressure the gas piping system may need to be chan...

Страница 13: ...nnected to any heating system or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the s...

Страница 14: ...let If this is not done local boiling will occur inside the water heater causing abnormal sounds and decreasing the durability of the heat exchanger Freeze Prevention Freezing is prevented within the...

Страница 15: ...s an example Please check with the actual water heater about the position of piping and form If this water heater will be installed in an application where the supply water is hard the water must be t...

Страница 16: ...ain valve V3 and then the other to the circulating pump 4 Connect the drain hose H2 to the circulating pump 5 Connect the drain hose H3 to the drain valve V4 6 Pour 1 gallon of and gallon water into t...

Страница 17: ...The code C60 is displayed on the Remote Controller when the water heater detects the flow of the flushing solution When 1 minute passes the code C60 will change to C59 on the Remote Controller 6 When...

Страница 18: ...t Covers 9 Open the gas supply valves and water outlet valves 10 Check for correct operation of the water heaters is displayed when the Main Water Heater s blue connector is connected is displayed whe...

Страница 19: ...g ON OFF PROG ALARM OFF 120 F Temp CCC Error unit 01 Beep Beep Press ON ON ALARM OFF STOP OFF Display Example In case of Unit 1 s blue connector is connected System down is displayed when the all unit...

Страница 20: ...cedure 3 1 3 5 7 Disconnect the blue connector marked FLUSH for flushing The Code CCC goes out on the Remote Controller 8 Close the Front Covers 9 Open the gas supply valves and water outlet valves 10...

Страница 21: ...as short as possible Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of...

Страница 22: ...CE 1 2 PVC pipe DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES Condensing Tankless Gas Water Heater Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensate will b...

Страница 23: ...p control requirement in order to maintain the full recirculation waranty 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and service va...

Страница 24: ...ly required by the water heater is 120VAC at 60 Hz The power consumption may be up to 303W or higher if using optional accessories Use an appropriate circuit Do not disconnect the power supply when no...

Страница 25: ...to allow a maximum temperature setting of 120 F 50 C To access higher temperature settings through the remote controller follow the steps below When setting the maximum temperature to 125 185 F 55 85...

Страница 26: ...ode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of...

Страница 27: ...cover select Initial settings using the Buttons 4 Press the ENTER button the Initial settings screen appears on the display 5 Select F gal C L using the Buttons 6 Press the ENTER Button and select eit...

Страница 28: ...m a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 29: ...lamp Ground wire Connector Use one of the vacant holes Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Co...

Страница 30: ...a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do no...

Страница 31: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 32: ...AIN 1 2 WIRING THOROUGHWAYS 2 2 56mm 2 2 55mm 1 7 44mm 0 8 20mm GAS INLET COLD WATER INLET HOT WATER OUTLET CONDENSATE DRAIN FROM BOTTOM OF CASE HEIGHT OF EACH FITTING 4 0 5 13mm 6 0 24 x 0 4 6 x 10mm...

Страница 33: ...tes of connecting electrical power before turning on the Power On Off Button press the or button on the remote controller and hold until the display blinks 99 If 99 does not blink on the remote contro...

Страница 34: ...is system will make hot water more quickly available to remote fixtures The pump will circulate water through the loop until the entire loop is warm and then the system controller will turn off the pu...

Страница 35: ...tat Pump Control Wires use external relayV Unit 1 Set Yes for the question Start pump rotation in system settings See SC 301 6M Installation Manual When installing 2 pumps in parallel Set Yes for the...

Страница 36: ...02 PCB Power PCB B5 B5 System Controller No 5 No 4 No 3 No 2 Remote Control terminal block Remote control terminal block Remote Controller Cord PCB Power PCB PCB Power PCB Multi System Wiring Use SC 3...

Страница 37: ...to both the cold water supply piping and the hot water supply piping to prevent freezing during cold weather and to prevent heat loss through the piping Unit 1 Unit 2 Unit 3 Unit 10 Unit 11 Unit 12 S...

Страница 38: ...ontroller This system will make hot water more quickly available to remote fixtures The pump will circulate water through the loop until the entire loop is warm and then the system controller will tur...

Страница 39: ...e Hot water storage tank copper or stainless steel pipe Return line circulation pump Size for max flow Size for max flow Storage tank supply line copper or stainless steel pipe Storage tank return lin...

Страница 40: ...nit 2 Unit 3 CAUTION The below diagram shows the connection of 3 units to the system controller When connecting 4 or more units follow the same procedure Connect the water heaters to the system contro...

Страница 41: ...r In order to use this product safely read this installation manual carefully and follow the installation instructions Potential dangers from accidents during installation and use are described below...

Страница 42: ...t The value in indicates the quantity Remote Controller Mounting bracket Raised countersunk head wood screw Wall anchor Raised countersunk head screw For junction box installation Machine screw When a...

Страница 43: ...f the remote controller and the frame pull the entire decorative frame forward while pressing the sections indicated where the fingers are in the figure below If it does not come off insert a flat hea...

Отзывы: