Maximum Vent Lengths

• 

This appliance has been designed to be vented 

with either 3" (75mm) or 4" (100mm) PVC or 

CPVC pipe. 

   Do not exceed the following maximum vent lengths:

8.

 

Vent Pipe Installation

(Indoor Installation Only)

WARNING

Be sure to do

CARBON MONOXIDE POISONING

Follow all vent system requirements in accordance with relevant local or state regulation, 

or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI 

Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with the Natural Gas and 

Propane Installation Code CSA B149.1 – latest edition.

  No. of Elbows 

Max. Straight Vent Length*

 

24' (  7.2m)  24' (  7.2m)

 

30' (  9.0m)  30' (  9.0m)

 

35' (10.8m)  35' (10.8m)

 

41' (12.6m)  41' (12.6m)

 

47 (14.4m)  47 (14.4m)

 

53' (16.2m)  53' (16.2m)

  Pipe diameter 

3" (75mm)  4" (100mm)

•  The venting system shall be installed in accordance 

with the water heater manufacturer's instructions 

and, if applicable, the venting system manufacturer's 

instructions.

•  This is a Category IV appliance.

  Only  vent  materials  approved  for  use  with 

Category IV appliances should be used.

•  Under  normal  conditions,  this  appliance  will 

not  produce  an  exhaust  flue  temperature 

in  excess  of  149°F  (65°C)  and  schedule  40 

PVC pipe may be used as the vent material.  

If required by local code, use schedule 40 or 

80 CPVC.

  Refer to page 14 for additional requirements.
•  Make  sure  the  vent  system  is  gas  tight  and 

will not  leak.

•  Support the vent pipe with hangers at regular 

intervals as specified by these instructions or 

the instructions of the vent manufacturer.

• 

All  piping  must  be  fully  supported.  Use  pipe 

hangers at a minimum of 3 ft (0.9 m) intervals. 

Do not use the Water Heater to support the 

vent piping.

• Do not common vent or connect more than 

one appliance to this venting system.

•  The total vent length including horizontal & vertical 

vent runs should be no less than 3' (0.9m).

• 

Do not store hazardous or flammable substances 

near the vent termination and check that the 

termination is not blocked in any way.

• Steam or condensed water may come out 

from the vent termination.  Select the location 

for the termination so as to prevent injury or 

property damage.

•  If snow is expected to accumulate, take care 

the end of the pipe is not covered with snow 

or hit by falling lumps of snow.

• The vent for this appliance shall not terminate:
  i)  over public walkways; or
  ii)  near  soffit  vents  or  crawl  space  vents  or 

other  areas  where  condensate  or  vapor 

could create a nuisance or hazard or 

cause property damage; or

  iii)  where  condensate  vaper  could  cause 

damage or could be detrimental to the 

operation  of  regulators,  relief  valves,  or 

other equipment.

General Requirements

Clearances

PVC or CPVC has been approved for use on this 

appliance with zero clearance to combustibles.

   * Not including the termination

•  Maintain the same vent pipe diameter from the 

heater flue to the vent termination. The exhaust 

and  intake  pipes  must  be  the  same  vent  pipe 

diameter.

Содержание GQ-C2857WS-FF US

Страница 1: ...he in stallation instructions Failures and damage caused by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in acc...

Страница 2: ...Cord QC 2 1 1 1 each Isolation Valves includes pressure relief valve Owner s Guide Installation Manual this document Bird Screen for 4 100mm PVC VT4 PVCS Bird Screen for 3 75mm PVC VT3 PVCS 2 2 PVC Co...

Страница 3: ...Connector Cord Connector 3 Quick Connect Multi System Installation The Quick Connect Multi System allows the installation of two units together utilizing only the Quick Connect Cord Typical Plumbing...

Страница 4: ...ures do not get to scalding levels Do not use a solar pre heater with the quick connect multi system Precautions for Mobile Home Installation Verify that the gas supply type matches the gas type liste...

Страница 5: ...facturer does not recommend installing the water heater in an attic due to safety issues If you install the water heater in an attic Make sure the unit will have enough combustion air and proper venti...

Страница 6: ...ode requirements in your area or call 1 855 960 3434 and request instructions Be sure to do Prohibited Prohibited CAUTION The Commonwealth of Massachusetts The water heater can be used for hot water o...

Страница 7: ...t is recommended to leave 8 200mm or more on either side of the unit 24 600mm or more in front of the unit 3 75mm or more above and below the vent pipe Securing of space for repair inspection 24 600mm...

Страница 8: ...Clearance in accordance with local installation codes and the requirements of the gas supplier Clearance to opposite wall is 24 inches 60 cm 12 in 30 cm 12 in 30 cm 6 in 15 cm for appliances 10 000 B...

Страница 9: ...nda porch deck or balcony is fully open on a minimum of two sides beneath the floor Clearance in accordance with local installation codes and the requirements of the gas supplier Clearance to opposite...

Страница 10: ...arts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution...

Страница 11: ...water into the exhaust accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the ap...

Страница 12: ...gas tight and will not leak Support the vent pipe with hangers at regular intervals as specified by these instructions or the instructions of the vent manufacturer All piping must be fully supported...

Страница 13: ...ged when adjusting the dip switches to switch the airflow amount The unit can be adjusted to accommodate longer vent runs refer to the below table to find the maximum vent length based on the number o...

Страница 14: ...has been approved for use on this appliance with zero clearance to combustibles All piping must be fully supported Use pipe hangers at a minimum of 3 0 9m intervals Do not use the water heater to sup...

Страница 15: ...short horizontal section is recommended to prevent debris from falling into the water heater When using a horizontal section slope the horizontal vent 1 4 upwards for every 12 300mm toward the termina...

Страница 16: ...prior to the termination 4 100mm pipe requires the use of a reducing coupling just prior to the termination 1 25mm to 2 50mm Insert Bird Screen in End of Termination There must be a 1 25mm to 2 50mm c...

Страница 17: ...e Exhaust Intake 3 Min WARNING If the distance between the air inlet and exhaust vent terminations is too short the water heater will draw in the exhaust gases through the intake There is a risk of in...

Страница 18: ...2 0 6m but not more than 6 1 87m in accordance with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or Natural Gas and Propane Installation Code CSA B149 1 Provide vertical support every 3 0 9m or as...

Страница 19: ...nt clearance of 4 or more in front of the unit is required A 24 or more clearance is recommended in order to facilitate maintenance and repair If combustion air will be provided through a duct size th...

Страница 20: ...the installer The installer must be professionally trained to do such work and must always follow all local and national codes and regulations Gas line sizing calculations must be performed for every...

Страница 21: ...ding to total btuh demand of the building and length from the meter or regulator so that the following supply pressures are available even at maximum demand WARNING Natural Gas Supply Pressure Min 4 W...

Страница 22: ...se 50 15m 175 000 Btuh requires 1 Outlet E 25 7 5m Use 30 9m 180 000 Btuh requires 3 4 Section 4 45 13 5m Use 50 15m 355 000 Btuh requires 1 1 4 Natural Gas Meter Noritz Condensing Tankless Gas Water...

Страница 23: ...t each appliance to verify all appliances are receiving a minimum of 5 WC for NG or 8 WC for LP If all appliances are not receiving the minimum inlet pressure the gas piping system may need to be chan...

Страница 24: ...be connected to any heating system or components previ ously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest o...

Страница 25: ...sing abnormal sounds and decreasing the durability of the heat exchanger Total Hardness 200 mg L 12 gpg or less Aluminum 0 05 to 0 2 mg L or less Chloride 250 mg L or less Copper 1 mg L or less Iron 0...

Страница 26: ...If this water heater will be installed in an application where the supply water is hard the water must be treated with either the Noritz H2Flow or ScaleShield or a water softener Refer to the below t...

Страница 27: ...nd then the other to the circulating pump 4 Connect the drain hose H2 to the circulating pump 5 Connect the drain hose H3 to the drain valve V4 6 Pour 1 gallon of and gallon water into the bucket Nori...

Страница 28: ...ctor marked FLUSH near the Circuit Board 3 Then the code CCC is displayed on the 4 Turn on the circulating pump to circulate the flushing solution through the water heater for 1 hour at a rate of 1 5...

Страница 29: ...the gas supply valves and water outlet valves 10 Check for correct operation of the water heaters 855 960 3434 is displayed when the Main Water Heater s blue connector is connected is displayed when t...

Страница 30: ...Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water...

Страница 31: ...h pump Floor drain MAINTAIN CLEARANCE DO NOT ADD ANY VALVES Condensing Tankless Gas Water Heater Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensate will b...

Страница 32: ...ce valve with unions and a pressure relief valve Notes 1 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and service valve with unions and...

Страница 33: ...eater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie the redundant power cord out side the water heater Putting the redundant length of co...

Страница 34: ...On Off Button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display This unit can be programmed so that it will default to one of three te...

Страница 35: ...e controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater External connection termi...

Страница 36: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 37: ...Connect Cord Clamp Ground wire Connector Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Co...

Страница 38: ...r normal the burner may need to be cleaned by qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure t...

Страница 39: ...rol manual valve clockwise to the off position Should overheating occur or the gas supply fail to shut off turn off the manual control valve to the appliance Handling after trial operation If the unit...

Страница 40: ...00mm 2 8 70mm 1 4 36mm 6 7 170mm 5 5 140mm 3 9 100mm 2 8 70mm 1 4 36mm 1 6 40mm 2 4 61mm 5 5 140mm 9 4 240mm 1 1 28mm 26 2 665mm 23 1 586mm 0 4 10mm 4 0 5 13mm 6 0 24 x 0 4 6mm x 10mm OBLONG HOLE 0 4...

Страница 41: ...on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the con troller Avoid locations...

Страница 42: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Отзывы: