Cleaning the Heat Exchanger

The flushing solution needs to be rinsed and cleaned out of the water heater.

Below is the way to rinse and clean the flushing solution.

1.  Remove both drain hoses (H2 and H3) from the bucket. And then place the drain hose (H3)

     into the sink or outside to drain.

2.  Close the drain valve (V3) and then open the water inlet valve (V1).

     Do not open the fresh water outlet valve (V2).

3.  Clean the water heater with fresh water for 3 minutes or more.

     (Needs to have enough time to clean the water heater.)

4.  Close the drain valve (V4) and then remove the drain hose (H3)  from the drain valve (V4).

5.  Remove the drain hose (H1) from the drain valve (V3).

8.  Open the gas supply valve and water outlet valve (V2).

9.  Check for correct operation of the water heater.

6.  Disconnect the “blue connector for flushing” near the Circuit Board.

     The code “C00” goes out on the Remote Controller.

7.  Close the  Front Cover.

Disconnect

Detects the flow

1 minute passes

䍾㻼㼞㼛㼏㼑㼐㼡㼞㼑㻌䠎㻚㻌

Flushing the Heat Exchanger (For Single Unit)

1.  Open the Front Cover.

2.  Connect the “blue connector*****” for flushing” near the Circuit Board.

3.  Then the code “CCC” is displayed on the 

㻾㼑㼙㼛㼠㼑㻌㻯㼛㼚㼠㼞㼛㼘㼘㼑㼞㻚

4.  Turn on the circulating pump to circulate the flushing solution through the water heater

    

 

for 1 hour at a rate of 1.5 gallons per minute or more.

5.  The code “C60” is displayed on the Remote Controller when the water heater detects the flow

     of the flushing solution.

     When 1 minute passes, the code “C60” will change to “C59” on the Remote Controller.

6.  When 1 hour passes, the code “C00” is flashing on the Remote Controller.

      Do not disconnect the “blue connector for flushing” .

7.  Turn off the circulating pump.

***** The connector color is blue

and labeled “FLUSH”.

Please check whether the reverse connection of the hose (H1) and (H3) if the display number will not change.
In that case, the flow rate of the flushing solution may be under 1.5 gallons per minute.

Flashing

FLUSH

Connect

CCC

CCC

C60

C59

C00

Manifold Plate

Circuit Board

Water Heater

Circuit Board

****** LED light is only for “NCC199OD(GQ-C3257WZ US)” and“NCC199DV(GQ-C3257WZ-FF US)”.

         It is flashing while flushing. When 1 hour passes, LED light is OFF.

LED light is flashing******

Water Heater

Water

Drain Valve

NOTE : If NRC111 (GQ-C3257WX ) or NCC199 (GQ-C3257WZ ), is installed, 

             the unit has a “Water Drain Valve” on the bottom of the water heater.

Place a bucket under the water heater to drain water from the "Water Drain Valve". 

Carefully unscrew the "Water Drain Valve" to rinse flushing solution out of 

the water heater for about 10 seconds, then close the "Water Drain Valve".

Manifold Plate

Содержание ecoTOUGH NRC111-OD-NG

Страница 1: ...ructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion After completing installation please eit...

Страница 2: ...ts but may be necessary for installation Cross Recessed Head Screw Quick Connect Cord QC 2 Q ty Shape Part Part Shape Q ty 1 1 Remote Controller Cord 26ft 8m 1 each Isolation Valves includes pressure...

Страница 3: ...Block Cord Connector Cord Connector 3 Quick Connect Multi System Installation The Quick Connect Multi System allows the installation of two units together utilizing only the Quick Connect Cord Typica...

Страница 4: ...Other Than Those Specified Do not use for other than increasing the temperature of the water supply as unexpected accidents may occur as a result Check Water Supply Quality If the water supply is in e...

Страница 5: ...eat and moisture from the water heater may cause discoloration of walls and resinous materials or corrosion of aluminum materials Do not locate the vent termination directed towards a window or any ot...

Страница 6: ...re in width Provide clearance of 24 600mm or more in front of the unit to facilitate inspection and repair Do install the unit such as the wall of the second floor where the unit is out of reach When...

Страница 7: ...rdance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sid...

Страница 8: ...arts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution...

Страница 9: ...e installer The installer must be professionally trained to do such work and must always follow all local and national codes and regulations Gas line sizing calculations must be performed for every in...

Страница 10: ...length from the meter or regulator so that the following supply pressures are available even at maximum demand WARNING Natural Gas Supply Pressure Min 4 WC Max 10 5 WC LP Gas Supply Pressure Min 8 WC...

Страница 11: ...se 50 15m 175 000 Btuh requires 1 Outlet E 25 7 5m Use 30 9m 199 900 Btuh requires 3 4 Section 4 45 13 5m Use 50 15m 355 000 Btuh requires 1 1 4 Natural Gas Meter Noritz Condensing Tankless Gas Water...

Страница 12: ...ce to verify all appliances are receiving a minimum of 5 WC for NG or 8 WC for LP If all appliances are not receiving the minimum inlet pressure the gas piping system may need to be changed CAUTION Pi...

Страница 13: ...nected to any heating system or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the sy...

Страница 14: ...r on the inlet If this is not done local boiling will occur inside the water heater causing abnormal sounds and decreasing the durability of the heat exchanger Freeze Prevention Freezing is prevented...

Страница 15: ...If this water heater will be installed in an application where the supply water is hard the water must be treated with either the Noritz H2Flow or ScaleShield or a water softener Refer to the below t...

Страница 16: ...n the other to the circulating pump 4 Connect the drain hose H2 to the circulating pump 5 Connect the drain hose H3 to the drain valve V4 6 Pour 1 gallon of and gallon water into the bucket Noritz rec...

Страница 17: ...the flushing solution through the water heater for 1 hour at a rate of 1 5 gallons per minute or more 5 The code C60 is displayed on the Remote Controller when the water heater detects the flow of th...

Страница 18: ...pply valves and water out let valves 9 Check for correct operation of the water heaters is displayed when the Main Water Heater s bule connector is connected is displayed when the Sub Water Heater s b...

Страница 19: ...as short as possible Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of...

Страница 20: ...CE 1 2 PVC pipe DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES Condensing Tankless Gas Water Heater Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensate will b...

Страница 21: ...ull recirculation waranty If it is not installed the water heater can not detect the Scale Build up in the Heat Exchanger 4 Noritz recommends the use of an Isolation Kit with the installation These ki...

Страница 22: ...ly required by the water heater is 120VAC at 60 Hz The power consumption may be up to 303W or higher if using optional accessories Use an appropriate circuit Do not disconnect the power supply when no...

Страница 23: ...On Off Button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display This unit can be programmed so that it will default to one of three te...

Страница 24: ...the end of the remote controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater Exter...

Страница 25: ...m a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 26: ...mp Ground wire Connector Use one of the vacant holes Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord...

Страница 27: ...a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do no...

Страница 28: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 29: ...0mm 1 4 36mm 0 4 10mm 1 7 44mm 26 2 665mm 23 1 586mm 24 2 615mm 24 0 611mm 2 4 61mm 2 1 53mm 1 6 40mm 0 4 10mm 9 4 240mm 0 5 13mm 1 1 28mm 1 6 42mm 17 7 450mm 18 3 464mm 10 5 267mm 16 9 428mm 3 9 99mm...

Страница 30: ...s on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid location...

Страница 31: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 32: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wa...

Страница 33: ...r In order to use this product safely read this installation manual carefully and follow the installation instructions Potential dangers from accidents during installation and use are described below...

Страница 34: ...t The value in indicates the quantity Remote Controller Mounting bracket Raised countersunk head wood screw Wall anchor Raised countersunk head screw For junction box installation Machine screw When a...

Страница 35: ...f the remote controller and the frame pull the entire decorative frame forward while pressing the sections indicated where the fingers are in the figure below If it does not come off insert a flat hea...

Страница 36: ...Button the Misc settings screen appears on the display 4 Select Max set Temp using the Buttons 5 Press the ENTER Button 120 F 50 C appears on the display 6 Set the upper limit of the hot water supply...

Страница 37: ...e controller 2 Disconnect then reconnect electrical power to the water heater 3 Press the MENU Button inside the cover select Initial settings using the Buttons 4 Press the ENTER button the Initial se...

Отзывы: