background image

5

Quick Connect 2
This procedure can be used if there is enough room and 
lineset length to connect the lineset directly to the coil and 
eliminate the need for the quick connects.
1. Verify that there is sufficient length of lineset to reach 

the coil. Allow for appropriate and adequate bend radius.

2. Verify that there is sufficient room for the tubing when 

appropriate radii are added to the lineset.

3. Cut the existing quick connect ends from the lineset.
4. If TXV kit and new liquid line are being installed, skip 

to step 7.

5. If original liquid line is being used, relieve all pressure 

from the coil by depressing the valve on the liquid line. 
Remove the valve core.

6. Using  all  appropriate  cautions,  unbraze  and  remove 

the valve holder on the liquid line.

7. Connect the suction and liquid lineset tubes.

 CaUtion:

it is recommended that a wet rag be wrapped 
around the suction line in front of the close 
off plate before applying heat. Failure to keep 

components cool during brazing may result 

in structural damage, premature equipment 

failure, or possible personal injury. 

important: to prevent internal oxidation and scaling 
from occuring, braze all connections with dry nitrogen 
flowing through the joints.

8. Braze the individual connections with dry nitrogen flowing 

through the joints.

9. Wrap  the  refrigerant  lines  with  pressure  sensitive 

neoprene or other suitable material especially where 
the lines enter the opening in the sheet metal.

10. Proceed to 

Completing the Installation

 section.

Downturn
1. Determine the appropriate connection kit by referring 

to Table 3 (page 6).

2. Cut off 2.5 inches off the coil suction and liquid line 

tubes. 

Do not swage the cut ends.

3. Connect kit parts to coil.

 CaUtion:

it is recommended that a wet rag be wrapped 
around the suction line in front of the close 
off plate before applying heat. Failure to keep 

components cool during brazing may result 

in structural damage, premature equipment 
failure, or possible personal injury. 

important: to prevent internal oxidation and scaling 
from occuring, braze all connections with dry nitrogen 
flowing through the joints.

4. Braze the individual connections with dry nitrogen flowing 

through the joints.

5. Connect the suction and liquid lineset tubes.
6. Braze the individual connections with dry nitrogen flowing 

through the joints.

7. Proceed to 

Completing the Installation

 section.

Completing the installation
1. Check the system for leaks, including the lineset and the 

brazed joints. 

notE: Apply a soap and water solution on 

each joint or union with a small paintbrush. If bubbling 
is observed, the connection is not adequately sealed.

2. Evacuate the system of moisture and non-condensables 

to prevent low efficiency operation or damage to the 
unit. The suggested range of evacuation is 250 - 500 
microns.

3. Charge the system with refrigerant. 

please refer to 

the outdoor unit installation manual for additional 
charging instructions.

4. Install the coil access door (if removed).
5. Properly dispose of all removed parts.
6. Apply power to the unit.

coupling nut (Figure 6) to be easily hand threaded for 
the initial 2-3 rotations. These initial rotations will bring 
the diaphragms into contact and a sharp increase in 
torque will be felt.

important: IF THE NUT WILL NOT START BY HAND, 
ADJUST THE POSITION OF THE LINE SET TO ENSURE 
PROPER  COUPLING  ALIGNMENT  AND  ELIMINATE/
MINIMIZE ALL SIDE-LOAD FORCE ON THE COUPLING 
DURING ASSEMBLY.

6. Using appropriately sized wrenches (see Table 4, page 

6) for both components, tighten the female coupling nut 
while preventing rotation of the female body with respect 
to the male coupling.

important: The nut should be tightened until a definite 
increase in resistance is felt. At this point, the nut will 
have covered most of the threads on the male body. It is 
important to ensure the male and female coupling bodies 
DO NOT rotate during any portion of the wrench installation.

7. Using  a  permanent  marker  or  scribe,  mark  a  line 

lengthwise from the female coupling nut to the female 
coupling body.

8. Tighten  an  additional  wrench  flat  (60°).  Refer  to  the 

marking on the coupling nut to confirm the one wrench flat 
has occurred. 

notE: This final wrench flat is necessary 

to ensure the formation of the metal to metal leak-proof 
seal, between the male and female couplings.

9. Proceed to 

Completing the Installation

 section.

Содержание WARRCOIL01

Страница 1: ...fectsorother reproductive harm WARNING Read the Installation Instructions supplied with the furnace air handler Always observe all safety requirements outlined in this manual and on the furnace air ha...

Страница 2: ...a restrictor 0 103 inches in diameter Factory supplied orifice sizes are listed in Table 2 page 3 If the orifice must be replaced follow steps 1 5 CAUTION To prevent damage to the unit or internal co...

Страница 3: ...mponents Mark a line on both bodies and then tighten an additional 1 4 turn using two wrenches The movement of the two lines will show how much the nut is tightened If a torque wrench is used tighten...

Страница 4: ...line in front of the close off plate before applying heat Failure to keep components cool during brazing may result in structural damage premature equipment failure or possible personal injury IMPORTA...

Страница 5: ...g brazeallconnectionswithdrynitrogen flowing through the joints 4 Brazetheindividualconnectionswithdrynitrogenflowing through the joints 5 Connect the suction and liquid lineset tubes 6 Brazetheindivi...

Страница 6: ...0672A 921289 B5BM X37K B 919699D 919630D WARRCOIL03 921694 920670A 921289 B5BM X42K B 904308D 919514D WARRCOIL03 921694 920671A 921289 B5BM X48K B 919686D 919515D WARRCOIL03 921694 920672A 921289 GB5B...

Страница 7: ...ARRCOIL02 921693 N A 921339 921288 C3DA 047U B 917270D WARRCOIL02 921693 N A 921339 921288 C3DA 055U B 917271D WARRCOIL02 921693 N A 921339 921288 C5DA T25U B 919221D WARRCOIL02 921693 920662A 921339...

Страница 8: ...70A 921337 921289 C3BA 048U C 917419D WARRCOIL07 921698 N A N A UC COIL KIT 060 B3 AH 917408D WARRCOIL07 921698 N A N A C3BA 060U C 917212D WARRCOIL04 921695 N A 921290 C5BA 048U C 919140D WARRCOIL04...

Отзывы: