background image

7

See the unit rating plate for minimum circuit ampacity 
and maximum overcurrent protection limits.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect 
the line-voltage leads to the terminals on the contactor 
inside the control compartment.

•  Use only copper wire for the line voltage power supply 

to this unit. Use proper code agency listed conduit and 
a conduit connector for connecting the supply wires to 
the unit. Use of rain tight conduit is recommended.

•  Optional equipment requiring connection to the power or 

control circuits must be wired in strict accordance of all 
applicable national and local codes and the instructions 
provided with the equipment.

grounding

 Warning:

the unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. do not 
use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 
with all applicable state, national, or local codes that take 
precedence. Use the grounding lug provided in the control 
box for grounding the unit.

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 
the indoor equipment.

•  Single  stage  thermostats  are  recommended  for  use 

with this equipment depending on optional accessories 
installed with the unit. Select a thermostat that operates 
in conjunction with the installed accessories. 

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 
comply with applicable local codes having jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 
wire gauge and wire lengths for typical thermostat 
connections are listed in Table 1 (page 8)

•  The thermostat should be mounted about 5 feet (1.52m) 

above the floor on an inside wall. DO NOT install the 

thermostat on an outside wall or any other location 
where its operation may be adversely affected by radiant 
heat from fireplaces, sunlight, or lighting fixtures, and 
convective heat from warm air registers or electrical 
appliances. Refer to the thermostat manufacturer’s 
instruction sheet for detailed mounting and installation 
information.

example

:

AB = 236V
BC = 240V
AC = 237V

3. Determine the maximum deviation:

4. Determine  percent  of 

voltage imbalance by 
using the results from 
steps 2 & 3 in the following 
equation.

max voltage deviation
from average voltage

= 100 x

average voltage

% Voltage Imbalance

2

238

100 x

= 0.84%

Example:

2. Determine the average voltage in the power supply.

Unbalanced 3-phase Supply Voltage

Voltage unbalance occurs when the voltages of all phases 
of a 3-phase power supply are no longer equal. This 
unbalance reduces motor efficiency and performance. 
Some underlying causes of voltage unbalance may 
include: Lack of symmetry in transmission lines, large 
single-phase loads, and unbalanced or overloaded 
transformers. A motor should never be operated when a 
phase imbalance in supply is greater than 2%.

Perform the following steps to determine the percentage 
of voltage imbalance:

1. Measure the line voltages 

of your 3 phase power 
supply where it enters the 
building and at a location 
that will only be dedicated 
to the unit installation (at 
the units circuit protection 
or disconnect).

In this example, the measured line voltages were 
236, 240, and 237. The average would be 228 volts 
(236 + 240 + 237 = 713 / 3 = 238).

The amount of phase imbalance (0.84%) is satisfactory 
since the amount is lower than the maximum allowable 
2%. Please contact your local electric utility company if 
your voltage imbalance is more than 2%.

example:

From the values given in step 1, the BC voltage 
(240V) is the greatest difference in value from 
the average:

240 - 238 = 2
238 - 236 = 2
238 - 237 = 1

Highest Value

Содержание S5BMX-018E

Страница 1: ...ct and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to...

Страница 2: ...an be obtained with the thermostat system mode set in any position including OFF Turning the Air conditioner Off Change the thermostat s system mode to OFF and the fan mode to AUTO See Figure 1 NOTE T...

Страница 3: ...lower 9 Anti Short Cycle Timer Protection 9 System Cooling 9 System Heating 9 Air Conditioner Maintenance 10 Component Functions 10 Figures Tables 11 Figure 3 Unit Dimensions 11 Table 2 Unit Dimension...

Страница 4: ...amage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructio...

Страница 5: ...or mounting the outdoor unit Overhead obstructions Figure 2 poorly ventilated areas and areas subject to accumulation of debris should be avoided Sufficientclearanceforunobstructedairflowthroughthe ou...

Страница 6: ...G WARNING To avoid risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical...

Страница 7: ...connections are listed in Table 1 page 8 Thethermostatshouldbemountedabout5feet 1 52m above the floor on an inside wall DO NOT install the thermostat on an outside wall or any other location whereits...

Страница 8: ...of new or reclaimed R 22 refrigerant Refer to the unit Rating Label or Table 2 Page 11 of this manual for the correct amount of charge that matches your specific system and connecting line lengths Ch...

Страница 9: ...lter unit wiring A n t i S h o r t C y c l e T i m e r P r o t e c t i o n Single Phase Models Only 1 Set the thermostat system mode to COOL Note the temperaturesettingofthethermostatandgraduallyraise...

Страница 10: ...5 minute short cycling delay before the outdoor unit will energize Air conditioner MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit...

Страница 11: ...Metering Device Inches I D 0 052 0 056 0 065 0 070 0 070 0 072 0 082 0 090 0 092 R 22 Refrigerant charge Kg Ounces Outdoor unit Matched Indoor Unit 4 6M 15 Ft Line Set 4 2 41 85 2 61 92 2 87 101 3 01...

Страница 12: ...ercurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 curcuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Sho...

Страница 13: ...supply wire ampacities and overcurrent protection see unit rating plate 5 Connect to 24 VAC class 2 curcuit See furnace air handler installation instructions for control circuit and optional relay tra...

Страница 14: ...specified on the unit rating label Theserefrigerantchargingchartsarevalidfor awidevarietyof indoorreturnair conditions temperature and airflow and are most influenced by the outdoor ambient temperatu...

Страница 15: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 7 Charging Chart for 2 Ton Units 024E Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207...

Страница 16: ...60 140 63 145 66 150 2758 400 C F Figure 10 Charging Chart for 3 Ton Units 036G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207 175 1379 200...

Страница 17: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 11 Charging Chart for 3 5 Ton Units 042G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 120...

Страница 18: ...54 130 57 135 60 140 63 145 66 150 2758 400 C F Figure 14 Charging Chart for 5 Ton Units 060G Series Add refrigerant when below curve Remove refrigerant when above curve 689 100 862 125 1034 150 1207...

Страница 19: ...19...

Страница 20: ...cable Avg Volts ______________________________ VOLTS If Applicable Max deviation of voltage from avg volts ____________________________________ VOLTS Volt imbalance _________________________________ V...

Отзывы: