CIRCULATING AIR SUPPLY

General
Plenums and air ducts must be installed in
accordance with the Standard for the Installation
of Air Conditioning and Ventilating Systems
(NFPA No. 90A) or the Standard for the Installation
of Warm Air Heating and Air Conditioning

Systems (NFPA No. 90B).

It is recommended that the outlet duct be provided
with a removable access panel. This opening
should be accessible when the furnace is
installed in service and shall be of a size that
smoke or reflected light may be observed inside
the casing to indicate the presence of leaks in
the heat exchanger.  The cover for the opening
shall be attached in such a manner as to prevent
leaks.

!

 WARNING:

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to
the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the
venting system being placed into operation, while all other appliances
connected to the venting system are not in operation:

1.

Seal any unused openings in the venting system.

2.

Inspect the venting system for proper size and horizontal pitch, as
required in the 

National Fuel Gas Code, ANSI Z223. 1/NFPA 54 or

the CSA B149.1, Natural Gas and Propane Installation Codes and
these instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies which could
cause an unsafe condition.

3.

As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.

4.

Close fireplace dampers.

5.

Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they are operating at maximum speed.
Do not operate a summer exhaust fan.

6.

Follow the lighting instructions. Place the appliance being inspected
into operation. Adjust the thermostat so appliance is operating
continuously.

7.

Test for spillage from draft hood equipped appliances at the draft
hood relief opening after 5 minutes of main burner operation. Use
the flame of a match or candle.

8.

If improper venting is observed during any of the above tests, the
venting system must be corrected in accordance with the 

National

Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural
Gas and Propane Installation Codes.

9.

After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous conditions of
use.

Содержание RA 80+ series

Страница 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Страница 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Страница 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Страница 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Страница 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Страница 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Страница 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Страница 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Страница 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Страница 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Страница 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Страница 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Страница 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Страница 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Страница 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Страница 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Страница 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Страница 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Страница 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Страница 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Страница 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Страница 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Страница 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Страница 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Страница 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Страница 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Страница 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Страница 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Отзывы: