background image

2

TABLE OF CONTENTS

IMPORTANT SAFETY INFORMATION .......................2

GENERAL INFORMATION ..........................................2

About the Heater Kit ..................................................2
Clearances to Combustibles......................................3

Standard Air Handlers ............................................3
Variable Speed Air Handlers ..................................3

Electrical Supply ........................................................3

HEATER KIT INSTALLATION ......................................3

E Element Assembly Installation ...............................4
Electric Heater Kits with Circuit Breakers ..................5

5, 8, & 10 kw Electric Heater Kits ...........................5
15, 20, 25, & 30 kw Electric Heater Kits .................5

3-Phase 9 & 15 kw electric heater kits ...................5
Line Cover ..............................................................5

Electric Heater Kits without Circuit Breakers .............5
Power Wiring .............................................................6
Staging ......................................................................6

MOTOR SPEED SELECTION ......................................6

Standard Air Handlers ...............................................6
Variable Speed Air Handlers .....................................7

WIRING DIAGRAMS ....................................................8

Figure 7 - Single Ph. - 5Kw Series  ........................8
Figure 8 - Single Ph. - 8 & 10kW Series  ...............8
Figure 9 - Single Ph. - 15kW Series  ......................9
Figure 10 - Single Ph. 20kW Series .......................9
Figure 11 - Single Ph. 24kW Series .....................10
Figure 12 - Single Ph. 25kW Series .....................11
Figure 13 - Single Ph. 29kW Series .....................12
Figure 14 - Single Ph. 30kW Series .....................13
Figure 15 - Three Phase. - 9 & 15kW Series  ......14

IMPORTANT SAFETY INFORMATION

INSTALLER: Please read all instructions before servicing 

this equipment. Pay attention to all safety warnings and 

any other special notes highlighted in the manual. Safety 

markings are used frequently throughout this manual to 

designate a degree or level of seriousness and should not 

be ignored. 

WARNING

 indicates a potentially hazardous 

situation that if not avoided, could result in personal injury 

or death. 

CAUTION

 indicates a potentially hazardous 

situation that if not avoided, may result in minor or moderate 

injury or property damage.

 WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION 
HAZARD
Failure to follow safety warnings exactly could 
result in serious injury or property damage.
Improper servicing could result in dangerous 

operation, serious injury, death or property 
damage.
•  Before  servicing,  disconnect  all  electrical 

power to air handler.

•  When servicing controls, label all wires prior 

to disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

GENERAL INFORMATION

About the heater kit

H6HK Series electric heater kit is approved for field 

installation in B5, B6, MB7, HMG, HMB, & HCG, air 

handlers. All sizes are available with factory-provided 

circuit-breakers for short circuit protection and to provide 

a disconnecting means. Also available are 5, 8, and 10 kw 

electric heater kits without circuit-breakers. Refer to the 

National Electric Code (ANSI/NFPA 70) and applicable 

local codes for over-current protection and disconnect 

requirements.

NOTES:

•  The  20,  24/25,  and  29/30  kw  electric  heater  kits 

are  NOT approved for installation in A-cabinet air 
handlers. The 25Kw & 30Kw kits are for B5 C-cabinet 
air handlers. The 24 & 29 Kw kits are for B6, MB7, 
HMG, HMB, & HCG C-cabinet air handlers. Use 
the model identifcation code (Figure 1, page 2) and 

H

HK

020

-

H

1

Product Type:

H-Heater

Product Identifier:

HK - Heater Kit

Generation:

6 - Sixth Series

 

No. of Breakers

Electric Code:

H=240 - 1 - 60
Q=208 / 240 - 3 - 60

Stage

Sequencer

005 - 5Kw
008 - 8Kw
009 - 9Kw

010 - 10Kw

015 - 15Kw
020 - 20Kw
024 / 025 - 25Kw
029 / 030 - 30Kw

Primary Capacity:

6

 

Figure 1. Heater Kit Identification Code

Содержание H6HK Series

Страница 1: ...tion service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national and local codes and standards Read these instructions thoroughly before starting the installation Follow all precautions and warnings contained within these instructions and on the unit The instructions included with this keater kit are for installations i...

Страница 2: ...s situationthatifnotavoided mayresultinminorormoderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Improper servicing could result in dangerous operation serious injury death or property damage Before servicing disconnect all electrical power to air handler When servicing con...

Страница 3: ...block and that the supply wiring is sized according to the current NEC codes and any other state or local codes See the rating label or Table 1 page 4 for minimum circuit ampacities and maximum overcurrent protection All electric heater kits 10 kw or less are supplied from the factory configured for use with a single HEATER KIT INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure...

Страница 4: ...60 015H XX 240 14 4 55 25 80 60 30 90 59 25 83 60 30 90 020H XX 240 19 2 55 50 105 60 60 125 59 50 109 60 60 125 025H XX 240 24 0 59 50 25 134 60 60 30 150 030H XX 240 28 8 59 50 50 159 60 60 60 175 005H XX 208 3 6 27 30 30 40 008H XX 208 5 6 39 40 42 50 010H XX 208 7 2 48 50 52 60 015H XX 208 10 8 48 21 70 50 25 80 52 22 73 60 25 80 020H XX 208 14 4 48 43 92 50 50 100 52 43 95 60 50 100 025H XX 2...

Страница 5: ...he circuit breaker must be positioned side with 1 4 terminals to the right as shown in the Figure 2 2 Remove the lower circuit breaker knockout from the air handler upper access door 15 20 24 25 29 30 kw Electric Heater Kits NOTE1 Theheavyredandblacksupplyleadsarebundled by circuit with wire ties at the factory The bundle coming from the top element tier is circuit A NOTE 2 The element assembly is...

Страница 6: ...he supply wires MOTOR SPEED SELECTION Standard Air Handlers The blower speed is preset at the factory for operation at the same speed for heating and cooling by using the blower motor jumpering terminal on the blower motor and connecting it to the desired speed with both the red and black wires connected to the jumpering terminal For optimum system performance and comfort it may be necessary to ch...

Страница 7: ...quired when using a 20 24 25 29 30 kw electric heater kit in a downflow application AlsoseeClearancestoCombustibles page3 4 Replace the upper door and secure it to the unit 5 Restore power to the unit Variable Speed Air Handlers The minimum electric heat airflow is selected by setting switches on the air handler circuit board Selecting the minimum electric heat airflow sets the minimum air flow th...

Страница 8: ...uctors with a minimum temperature rating of 60 C for supply connections ELEMENT BLACK BLACK ELEMENT RED 710561A Figure 7 Wiring Diagram for H6HK Single Stage Air Handler with Circuit Breaker s 5 kw Series TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only Legend Field Wiring Factory Wiring Low Voltage High Voltage RELAY GREY ORANGE BLACK RED RED LIMIT POWER BLACK 1 2...

Страница 9: ...CK BLACK BLACK ELEMENT ELEMENT RED RED RED RED RELAY BROWN ELEMENT BLACK LIMIT RED RED 1 2 3 4 5 6 7 RED BLACK Figure 9 Wiring Diagram for H6HK Single Stage Air Handler with Circuit Breaker s 15 kw Series CIRCUIT BREAKERS SUPPLY VOLTAGE GROUND 1 2 3 4 5 6 7 POWER GREY ORANGE BLUE YELLOW RELAY RELAY RELAY ELEMENT LIMIT LIMIT RED BLACK BLACK Legend Field Wiring Factory Wiring Low Voltage High Voltag...

Страница 10: ...ld Wiring Factory Wiring Low Voltage High Voltage BLACK BLACK RED RED BLACK NOTES 1 If any of the original wire supplied with this unit must be replaced it must be replaced with wiring material of the same gauge size and temperature rating 2 The installation of this heater kit may require a change in the blower speed tap connection See Installation Instructions for details 3 Use copper conductors ...

Страница 11: ...ltage High Voltage BLACK BLACK RED RED BLACK RED RED NOTES 1 If any of the original wire supplied with this unit must be replaced it must be replaced with wiring material of the same gauge size and temperature rating 2 The installation of this heater kit may require a change in the blower speed tap connection See Installation Instructions for details 3 Use copper conductors with a minimum temperat...

Страница 12: ... Voltage High Voltage BLACK BLACK RED RED BLACK NOTES 1 If any of the original wire supplied with this unit must be replaced it must be replaced with wiring material of the same gauge size and temperature rating 2 The installation of this heater kit may require a change in the blower speed tap connection See Installation Instructions for details 3 Use copper conductors with a minimum temperature r...

Страница 13: ...D RED BLACK RED RED NOTES 1 If any of the original wire supplied with this unit must be replaced it must be replaced with wiring material of the same gauge size and temperature rating 2 The installation of this heater kit may require a change in the blower speed tap connection See Installation Instructions for details 3 Use copper conductors with a minimum temperature rating of 60 C for supply con...

Страница 14: ...age used 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge TRANSFORMER 24V BLACK WHITE RED GREY HEATER KIT PLUG 2 1 BLACK RED ELEMENT 1 BLACK L1 L2 L3 L1 L2 L3 ELEMENT 2 ELEMENT 3 BLACK YELLOW RED BLACK RED BLACK YELLOW RED ELEMENT 3 ELEMENT 2 ELEMENT 1 CONTACTOR BLACK 3 4 5 6 7 RELAY RED ORANGE GREY From indoor air handler circuit board RED GREY From indoor air han...

Страница 15: ......

Страница 16: ...INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER Specifications illustrations subject to change without notice or incurring obligations 01 14 709524A Replaces 7095240 ...

Отзывы: