background image

4

B3BV

Minimum Circuit

Maximum Over-Current

Ampacity

Protection

Circuit

Circuit

Single

Circuit

Circuit

Single

Model #

Voltage

KW

A

B

Circuit

A

B

Circuit

15 KW

240

14.4

55.0

25.0

80.0

60.0

30.0

90.0

20 KW

240

19.2

55.0

50.0

105.0

60.0

50.0

125.0

Table 2. Electrical Data

cations.  Remove the single circuit adaptor
kit cover and verify that the lugs are config-
ured correctly for the application.  If the
lugs are not configured for the application,
refer to the instructions included with the
kit and modify the configuration.  Install the
single circuit adaptor kit (if used) in the line
side (“on” end) of the circuit breakers.
Tighten the lugs securely (45 in-lbs rec-
ommended).

Connect the supply wiring to the circuit
breakers, single circuit adaptor kit, or ter-
minal block. Tighten the lugs securely.

When using dual supply circuits verify that
the supply sized for circuit “A” is connected
to the circuit breaker that is connected to
the top element assembly.

Replace metal circuit breaker line cover.
Refer to Figure 2 for thermostat wiring
examples.

A/C or H/P COIL INSTALLATION

Approved air conditioning and heat pump
system components are listed on the unit
nameplate.

To install the indoor coil:
1.

Remove door cover plate, door and
coil close-off plate (with insulation).
Discard door cover plate.

2.

For upflow applications slide the coil
into the track located in the bottom of
the unit.

3.

For downflow applications the down-
flow adaptor (see Table 1) must be
used.  Install the downflow adaptor
and coil as directed in the instructions
included with the kit.

4.

Reinstall the door and coil close-off
plate (with insulation).  NOTE:  In
downflow applications the door is ro-
tated 180° so that the refrigerant and
condensate lines remain on the left
side.

5.

Install the refrigerant and condensate
lines as directed in the instructions
included with the outdoor unit.

MOTOR SPEED SELECTION

The blower speed is preset at the factory
for operation at the same speed for heat-
ing and cooling. For optimum system per-
formance and comfort, it may be neces-
sary to change the factory set speed. To
change the blower speed, disconnect all
electrical power to the unit and remove the
upper door. Connect the black wire from
the motor to the desired blower speed
marked on the terminal block of the blower
motor. Terminal 4 = High Speed, Terminal
5 = Med Speed and Terminal 6 - Low
Speed.

Replace the upper door and secure it to
the unit. Restore power to the unit.

High speed operation is required when
using a 20 kw electric heater kit in a
downflow application.

Содержание B3BV Series

Страница 1: ...cause fire electrical shock or other conditions which may result in personal injury or property damage Unless otherwise noted in the instructions only factory authorized kits or accessories may be use...

Страница 2: ...VentilAire connections must be made for the system to conform to H U D rules Do not leave disconnected after servicing or adding A C to the system RETURN AIR In closet or alcove installations provide...

Страница 3: ...ing metal strap and or fas teners at the top of the unit and at the bottom of the unit POWER WIRING WARNING To avoid risk of electric shock personal injury or death disconnect electrical power to the...

Страница 4: ...e To install the indoor coil 1 Remove door cover plate door and coil close off plate with insulation Discard door cover plate 2 For upflow applications slide the coil into the track located in the bot...

Страница 5: ...E O Y Thermostat Green Red Brown G R W2 Orange Grey O Y R C B3BV Electric Furnace Heat Pump OD Section Typical Heat Pump System Connection W2 C W1 NOTE Jumper betweenW2 and E is requiredwhenno OD T S...

Страница 6: ...LUG SUPPLY VOLTAGE RED BLACK BLACK BLACK BLACK BLACK LIMIT GRAY 1 COM 2 CAP 3 CAP 4 HIGH 5 MED 6 LOW N C N O Com Figure 3 Typical System Wiring Diagram 20 kw 2 Stage Shown Air Handler with Factory Ins...

Страница 7: ...T B3BV NO NO DESCRIPTION 015K B 020K B 1 270012 Element Assembly 4 8 kw 1 270006 Element Assembly 9 6 kw 1 2 2 621908 Contactor 1 pole 1 621909 Contactor 2 pole 1 2 3 626518 Limit 1 pole 160 F 2 2 4 6...

Страница 8: ...laces7081020 Specifications and illustrations subject to change without notice and without incurring obligations PrintedinU S A 10 02 708195C 708195 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTI...

Отзывы: