Disconnect Switch — An electrically compatible disconnect
switch must be within line of sight of the outdoor unit.  This
switch shall be capable of electrically de-energizing the
outdoor unit.

Optional Equipment — Optional equipment requiring
connection to the power or control circuits shall be wired in
strict accordance with current provisions of the “National
Electrical Code” (ANSI C1.), with applicable local codes
having jurisdiction, and the Installation Instructions provided
with the equipment.  Optional Equipment (i.e., liquid line
solenoid valves, hard start kits, low suction pressure cutout
switch kit, high pressure cutout switch kit, refrigerant
compressor crankcase heater, etc.) should be installed in
strict accordance with the manufacturer’s Installation
Instructions.

8. START-UP AND CHECKOUT

WARNING:

Ensure electrical power to the unit is off prior to
performing the following steps.   Failure to do so
may cause personal injury or death.

!

CAUTION:

If equipped with a refrigerant compressor
crankcase heater, allow 24 hours prior to
performing a function checkout to allow for
heating of the refrigerant compressor crankcase.
Failure to comply may result in damage and
could cause premature failure of the system.

!

Air Filters — Ensure air filters are clean and in place prior
to operating the equipment.

Thermostat — Set the room thermostat function switch to
OFF, fan switch to AUTO, and move the temperature set-
point to it’s highest setting.

Prior to applying electrical power to the outdoor unit, ensure
that the unit has been properly and securely grounded.

Prior to applying electricity to the outdoor unit, ensure power
supply connections have been made at the facility power
interface and at the outdoor unit.

Outdoor Unit — Ensure the outdoor coil and top of the unit
are free from obstructions and debris, and all equipment
access/control panels are in place.

Functional Checkout:

Split System Air Conditioning equipment
contains liquid and gaseous refrigerant under
pressure.  Adjustment of refrigerant charge
should only be attempted by qualified, trained
personnel thoroughly familiar with the
equipment.  Under no circumstances should
the homeowner attempt to install and/or service
this equipment.  Failure to comply with this
warning could result in equipment damage,
personal injury, or death.

WARNING:

!

Indoor Blower — Set the thermostat function switch to
“Cooling” and the fan switch to ON or MAN.  Verify that the
Indoor Blower is operating and that airflow is not restricted.
Set the fan switch back to Auto.

Cooling — Gradually lower the thermostat temperature set-
point below the actual room temperature and observe that
the outdoor unit and indoor blower energize.  Feel the air
being circulated by the indoor blower and verify that it is
cooler than ambient temperature.  Listen for any unusual
noises.  If present, locate and determine the source of the
noise and correct as necessary.

Optional Short Cycle Protection — With the system
operating in “Cooling” mode, note the temperature setting of
the thermostat, and gradually raise the set-point temperature
until the outdoor unit and indoor blower de-energize.
Immediately lower the set-point temperature of the thermostat
to it’s original setting and verify that the indoor blower is
energized and that the outdoor unit remains de-energized.
Verify that, after approximately 5 minutes, the outdoor unit
energizes and that the temperature of the air supplied to the
facility is cooler than ambient temperature.

Heating — If provided with heating equipment, lower the
thermostat temperature to the lowest obtainable setting and
set the thermostat function switch to “Heating."  The indoor
blower and outdoor unit should stop running.  Increase the
set-point temperature of the thermostat to the maximum
setting. Verify that the heating equipment has been energized
(i.e., fossil fuel burner operating, etc.) and that the indoor
blower energizes after a short period of time.  Feel the air
being circulated by the indoor blower and verify that it is
warmer than ambient temperature.  Listen for any unusual
noises.  If present, locate and determine the source of the
noise and correct as necessary.

Adjustment of Refrigerant Charge:

Содержание 10 SEER Standard Efficiency Split System

Страница 1: ...conditioning appliances Some local codes require licensed installation service personnel for this type of equipment Read all instructions carefully before starting the installation These units have be...

Страница 2: ...itch to AUTO See Figure 1 The system will not operate regardless of the thermostat temperature setting To Operate the Indoor Blower Continuously Set the thermostat fan switch to ON See Figure 1 The in...

Страница 3: ...ions poorly ventilated areas and areas subject to accumulation of debris should be avoided The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in a...

Страница 4: ...COUPLING HALVES TOGETHER BY HAND TO INSURE PROPER CONNECTION Hold body of the line coupling hex with wrench while slowly tightening the union nut until a definite resistance bottoming out is felt b M...

Страница 5: ...sure Adjustment of refrigerant charge should only be attempted by qualified trained personnel thoroughly familiar with the equipment Under no circumstances should thehomeownerattempttoinstalland orser...

Страница 6: ...Disch Liquid Disch Liquid Disch Liquid Disch Press Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp 67 169 137 69 170 149 182 142 71 172 160 184 152 196 147 73...

Страница 7: ...Temp Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp 67 187 145 69 189 157 201 151 71 190 168 203 161 216 156 73 191 180 206 171 219 164 231 160 75 191 201 208 181 221 173 234 168 2...

Страница 8: ...uid Disch Liquid Disch Liquid Disch Liquid Disch Liquid Disch Liquid Disch Liquid Disch Press Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp Press Temp 67 180 153 69 182...

Отзывы: