background image

736HPA-NV High Pressure Dispense Valve

For Nordson EFD sales and service in over  
40 countries, contact Nordson EFD or go to  
www.nordsonefd.com.

Global 

East Providence, RI USA 
800-556-3484; +1-401-431-7000 
[email protected]

Europe

 

Dunstable, Bedfordshire, UK 
0800 585733; +44 (0) 1582 666334 
[email protected]

Asia

 

China: +86 (21) 3866 9006; [email protected] 
India: +91 80 4021 3600; [email protected] 
Japan: +81 03 5762 2760; [email protected] 
Korea: +82-31-736-8321; [email protected] 
SEAsia: +65 6796 9522; [email protected]

Viton and Hytrel are registered trademarks of E.I. DuPont. 
The Wave Design is a trademark of Nordson Corporation. 
©2016 Nordson Corporation    7026829    v012416

Troubleshooting Guide

No fluid flow

•  If valve operating pressure is too low, the valve will 

not open. Increase air pressure to 4.8 bar (70 psi) 
for timed shots and 2.7 bar (40 psi) minimum for 
stripes.

•  The fluid pressure may not be high enough. 

Increase pressure.

•  The dispensing tip may be clogged. Replace tip.
•  Fluid may have solidified in the fluid body. Clean 

the fluid body.

Fluid drools after the valve closes, eventually 
stopping

•  This is caused by air trapped in the outlet section 

of the fluid body or the fluid has entrapped air. 
The air will expand after the valve closes, causing 
extrusion until the air reaches atmospheric 
pressure. Purge the valve by dispensing at a 
steady flow until air is removed.

•  If the fluid has entrapped air, it must be degassed 

before dispensing.

Fluid drips at a steady rate after the valve 
closes

•  A steady drip indicates failure of the seal due to 

particle build-up or wear. Replace the seal.

•  Fluid leakage can also occur when a fluid inlet 

fitting is threaded too far into the valve, thus 
obstructing the piston shaft. Ensure that the fluid 
inlet fitting is properly installed.

Valve responds slowly when opening and 
closing

•  Valve response is related to control air line length 

and size. EFD valves are supplied with 5 feet of 
4 mm (5/32") ID tubing attached. Any additional 
length or size change will affect response time. 
Check to be sure the length and size have not 
been changed.

Fluid flows out above upper seal

•  Fluid flowing out above the upper seal indicates a 

worn upper seal. Replace seal.

Inconsistent deposits

•  Inconsistent deposits can result if the air pressure 

controlling the valve and / or fluid pressure is 
fluctuating, or if the valve operating pressure is 
less than 4.8 bar (70 psi). Check air pressures and 
the valve operating pressure.

•  The time the valve is open must be consistent. 

Check to be sure the valve controller is providing 
a consistent output.

Отзывы: