2 Assembly and installation
BU 0135 en-4118
49
ATEX zone 22 3D. This also includes connectors and switches that may also not be used in such an
environment.
Control and parametrisation units
are basically
not
approved for
operation in
ATEX zone 22 3D
.
They may therefore only be used for commissioning or maintenance purposes and if it has been
ensured that no explosive dust atmosphere exists.
Designation
Part Number
Use permissible
Power supply
SK CU4-24V-123-B(-C)
275271108 / (275271608)
Yes
SK CU4-24V-140-B(-C)
275271109 / (275271609)
Yes
Fuses
SK CU4-FUSE(-C)
275271122 / (275271622)
Yes
Wall mounting kits
SK TIE4-WMK-1-EX
275175053
Yes
SK TIE4-WMK-2-EX
275175054
Yes
Adapter kits
SK TI4-12-Adapter kit_63-71-EX
275175038
Yes
SK TI4-3-Adapter kit_80-112-EX
275175039
Yes
2.4.1.3 Commissioning information
For Zone 22 the cable glands must at least comply with protection class IP55. Unused openings must
be closed with blank screw caps that are suitable for ATEX Zone 22 3D (generally IP 55).
The motors are protected from overheating by the device. This takes place by means of evaluation of
the motor PTC (TF) at the device side. In order to ensure this function, the PTC must be connected to
the intended input (Terminal 38/39).
It must also be ensured that the nominal current of the motor has been set.
Overview of required parameter settings:
Parameter
Setting value
Factory setting
Description
P203
Rated motor current
Data according to
rating plate
[xxx]
Setting takes place at the factory side or must
be carried out as per the motor type plate.
P535
I²t motor
According to motor
and ventilation
[0]
The I²t- monitoring of the motor must be
switched on. The set values depend on the
type of ventilation and the motor used. See
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...