7 Technical data
BU 0135 en-4118
107
7.2.1 Electrical data
Device type
SK 1x5E… -301-340-
-751-340-
Size
1
2
Nominal motor power
(4-pole standard motor)
400 V
3.0 kW
7.5 kW
480 V
4 hp
10 hp
Mains voltage
3 AC
200 V … 500 V ± 10 %, 47 … 63 Hz
Input current
rms
7.5 A
16.0 A
FLA
7.5 A
16.0 A
Output voltage
3 AC
0 ... Mains voltage
Output current
1)
rms
7.5 A
16.0 A
FLA
7.5 A
16.0 A
LRA
52.2 A
112.0 A
Motor-mounted (ventilated)
Max. continuous power / max. continuous current
S1-50°C 3.0kW / 7.5A
7.5kW / 16.0A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
50°C
60°C
60°C
50°C
60°C
60°C
Wall mounting (unventilated)
Max. continuous power / max. continuous current
S1-50°C
S1-60°C
3.0kW / 7.5A
2.2kW / 5.5A
7.5kW / 16.0A
5.5kW / 12.5A
Max. permissible ambient temp. with nominal output current
S1
S3 70 % ED 10 min
S6 70 % ED 10 min (100 % / 20 % Mn)
50°C
60°C
60°C
50°C
60°C
60°C
General fuses (AC) (recommended)
slow-blowing 7.5…16 A
2)
16…32 A
2)
Isc
3)
[A]
UL fuses (AC) – permitted
Class
65 00
0
100 0
00
Fu
se
RK5
x
30 A
30 A
CC, J, R, T, G, L
x
30 A
30 A
CB
4)
480 V)
x
30 A
30 A
1) FLA (S1-50 °C)
2) Fuse size depending on size of connected motor
3) Maximum permissible mains overload current
4) "Inverse time trip type“ according to UL 489
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...