BU 0750 GB
Technical design subject to change
81
7.3 Basic parameters
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P100
Parameter set
immer sichtbar
0 ... 3
[ 0 ]
Selection of the parameter set you want to work with. Four parameter sets are available. Each pa-
rameter the setting of which does not extend to the other parameters is marked
P
.
The parameter set which is to be used for operation is activated via a digital input or as a result of a
bus-transmitted command. Parameter sets may be switched in the course of operation (on-line).
Setting
Digital input
function [8]
Digital input
function [17]
ControBox
display
0 =
Parameter set 1
LOW
LOW
1
2
1 =
Parameter set 2
HIGH
LOW
2
1
2 =
Parameter set 3
LOW
HIGH
1
2
3 =
Parameter set 4
HIGH
HIGH
2
1
If the inverter is enabled via the keyboard (ControlBox, PotentiometerBox or ParameterBox), the set
of operating parameters made available will be the one selected in P100.
P101
Copy parameter set
Always available
0 ... 4
[ 0 ]
To copy the set of parameters selected in P100 >Parameterset< to another parameter set, select
the option you wish to be executed below and terminate the input with the ENTER command.
0 =
No copy
1 =
Copy to param. set 1
2 =
Copy to param. set 2
3 =
Copy to param. set 3
4 =
Copy to param. set 4
P102
Acceleration time
P
Always available
0 ... 320.00 s
[ 2.00 ]
or [ 3.00 ]
Acceleration time is understood to be the time required for the frequency to rise from 0Hz to the
maximum frequency set in P105 following a linear ramp. If a current setpoint <100% is used, ramp-
ing up will take less time depending on which setpoint has been adjusted.
Under certain circumstances acceleration may take longer than provided for by the setting, e.g. as a
result of inverter overload, setpoint delay, ramp smoothing, or when the current limit has been
reached.
P103
Deceleration time
P
Always available
0 ... 320.00 s
[ 2.00 ]
or [ 3.00 ]
Deceleration time is understood to be the time required for the frequency to be reduced from the set
maximum frequency (P105) down to 0Hz along a linear ramp. Using a current setpoint <100% will
result in a corresponding reduction of deceleration time.
Under certain circumstances deceleration may take longer than provided for by the setting, e.g. as a
result of >Ramp smoothing< (P106) or because of the >Disconnection mode< (P108) that has been
selected.