Brake resistor – SK BRU5-1-240-050 

 

8 / 9 

  

275299004 - 0821 

 Information

 

 

In order to use the signal from the temperature switch it must be connected to a free digital input of the 

frequency inverter and, for example, parameterised with the function "Voltage block" or "Quick stop".  
Switching power of the normally closed contact: 

• 

2 A at 24 V DC 

• 

2 A / 230 V AC 

For detailed information, please refer to the frequency inverter manual 

 "Further documentation and 

software www.nord.com". 

 

Pos: 31 /Technische Informationen/Bremswiderstände/Parameter & Fehlermeldungen @ 13\mod_1472734349965_388.docx @ 345591 @ 55 @ 1 

 

Parameter 

For optimum operation of the braking resistor, the following frequency inverter parameters need to be 

changed. 

Parameter 

Meaning 

Remarks 

P556 

Braking resistor 

Value of the braking resistor for calculation of the maximum brake power in order to protect the 

resistor. 

• 

Error I

2

t limit (E003.1) is triggered. For further details, see 

 in P737. 

P557 

Brake resistor type 

Continuous power (nominal power) of the resistor, to display the actual utilisation in P737. For a 

correctly calculated value, the correct value must be entered into P556 and P557. 

• 

0.00 = Off, monitoring disabled 

 

P700 

Actual operating status 

This parameter holds information on the actual operating status of the frequency inverter, such as 

fault, maintenance, and reason for switch-on inhibit. 

P701 

Last fault 

This parameter holds information on the frequency inverter’s last faults. 

P737 

Usage rate brakeres. 

This parameter holds information on the actual usage degree of the brake chopper or the actual 

utilisation of the braking resistor in generator mode. 

• 

Depending on parameter settings P556 and P557. 

• 

If both are correctly set, the resistance is displayed. 

 

Refer to the frequency inverter manual for details 

 "Further documentation and software 

www.nord.com". 

 

Error messages 

Error messages from the braking resistor - the current or archived message for the last fault - can be 

read out from the information parameter Current Fault P700 and the Last Fault P701 in the error memory 

of the frequency inverter. 

Error   

(E030/E050) 

Meaning 

Remarks 

3.1 

I

2

t overcurrent limit 

Brake chopper: I

2

t limit has been triggered, 1.5x value for 60 s reached (

 P556, P557) 

• 

Avoid overcurrent in braking resistor

 

5.0 

Overvoltage Ud 

Link circuit voltage too high 

• 

Check the function of the braking resistor (cable break) 

• 

Resistance of connected braking resistor too high

 

 

Refer to the frequency inverter manual for details 

 "Further documentation and  software 

www.nord.com". 

Pos: 32 /Technische Informationen/Bremswiderstände/Unterbau- Bremswiderstände [SK 5xxP]/BRU5/Anschlussbild Unterbau- Bremswiderstand [SK BRU5-1-...] @ 33\mod_1555317562556_388.docx @ 2527580 @ 5 @ 1 

 

Содержание 275 299 004

Страница 1: ...shock The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off Work must not be carried out unless the device has been disconnected from the voltage a...

Страница 2: ...equency inverter results in generator braking energy that depending on the particular application is dissipated by a braking resistor This excess energy is converted into heat The footprint braking re...

Страница 3: ...s to a single use within 120 s Pos 18 Technische Informationen Bremswiderst nde Unterbau Bremswiderst nde SK 5xxP BRU5 Basisinformation II Teil SK BRU5 1 33 mod_1555395702126_388 docx 2528350 1 o Gene...

Страница 4: ...nt on the resistor s surface deposits of flammable material must be avoided in order to avoid ignition Cleaning of the resistor must be carried out with a dry duster on a regular basis when the resist...

Страница 5: ...Unterbau mit 100 C 275911200 62 mod_1610615070087_388 docx 2714390 1 NOTICE Impermissible heating If the footprint braking resistor is mounted directly below the frequency inverter a temperature switc...

Страница 6: ...m 11 x 12 x 10 Mounting L M4 thread mm 5 Cable line Wire length mm 50 Wire end sleeve mm 10 Dimension drawing Pos 27 Technische Informationen Bremswiderst nde Unterbau Bremswiderst nde SK 5xxP BRU5 Al...

Страница 7: ...frequency inverter in a horizontal position with the 2 fastening screws which are provided For frequency inverter on mounting surface Braking resistor on mounting surface Similar to illustration 2 Ins...

Страница 8: ...al operating status of the frequency inverter such as fault maintenance and reason for switch on inhibit P701 Last fault This parameter holds information on the frequency inverter s last faults P737 U...

Страница 9: ...resistor Pos 35 Technische Informationen Bremswiderst nde Unterbau Bremswiderst nde SK 5xxP BRU5 Weiterf hrende Dokumentationen und Software SK BRU5 33 mod_1554822291112_388 docx 2526801 5 1 Further d...

Отзывы: