<Primary check>
(1) Is the room temperature higher than the preset temperature in cooling operation?
(2) Is the crossover cable connected properly?
Turn on power supply.
Does compressor delay
three minutes by
temperature changes or
others?
Does OPERATION
indication indicate?
Is it possible to detect AC
220-240V on terminal block
or contactor of compressor?
Are all of compressor cords
normal?
Is compressor motor winding
normal?(Check winding
resistor.)
Is capacitor for compressor
normal?
Is overload relay normal?
Does compressor start?
Does compressor stop after a
while?
Is gas quantity normal?
(Check gas pressure.)
Microcontroller is defective or
miniature relay is defective..
Is resistance value of room
sensor (Tr) and heat exchanger
sensor (TP1) normal?
Room sensor or heat
exchanger sensor is
defective.
Replace room sensor or
heat exchanger sensor.
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Compressor is defective.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Supply gas.
Replace compressor.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Check power supply.
Replace compressor.
Wait three minutes
Содержание NBFS-48IDU
Страница 3: ...1 Summary ...
Страница 7: ......
Страница 8: ...use of remote controller ...
Страница 9: ......
Страница 12: ......
Страница 13: ......
Страница 14: ......
Страница 15: ......
Страница 16: ......
Страница 17: ......
Страница 18: ......
Страница 19: ......
Страница 20: ......
Страница 21: ...3 indoor explosive view for 40k ...
Страница 22: ...outdoor explosive view for 40k ...
Страница 24: ...5 CIRCUIT DIAGRAM 43K INDOOR ...
Страница 25: ...43K OUTDOOR ...
Страница 42: ...Floorstanding Air Conditioning Unit ...