10
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual leaks. A halide torch (or any other detector using a naked flame)
shall not be used
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
11. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need re-calibrated.(Detection equipment shall be calibrated
in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and
is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage
of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas(25% maximum )is confirmed .
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine shall be avoided as the chlorine may
react with the refrigerant and corrode the copper pipe work.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
both before and during the brazing process.
12. Removal and evacuation
When breaking into the refrigerant circuit to make repairs- or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered to:
remove refrigerant;
purge the circuit with inert gas;
evacuate;
purge again with inert gas;
open the circuit by cutting or brazing;
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be “flushed’ with OFN to render the unit safe. This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing
to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling
down to a vacuum. This processing shall be repeated until no refrigerant is within the
system. When the final OFN charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place. This operation is absolutely vital if brazing operations
on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close
to any ignition sources and there is ventilation available.
13. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
WARNINGS (for using R290/R32 refrigerant only)
Содержание AK-20L
Страница 2: ......
Страница 4: ......
Страница 23: ......
Страница 24: ...22 23 27 H R290 R32 28 34 34 35 35 36 36 37 37 37 38 38 39 39 40...
Страница 25: ...23 l l...
Страница 26: ...24 8...
Страница 27: ...25 1 l...
Страница 28: ...26 l PCB T 3 15A 250V 350V CO2 24...
Страница 29: ...27 l 2002 96 EC 27 2003 l CO2 l A B...
Страница 30: ...28 4m2 R32 R290 R32 290 H R290 R32...
Страница 31: ...29 R290 R32 1 2 3 4 5 6 1 2 3 4 5 CO2 6 H R290 R32...
Страница 32: ...30 7 8 9 7 H R290 R32...
Страница 33: ...31 8 9 10 11 O LFL 25 12 H R290 R32...
Страница 34: ...32 13 14 H R290 R32...
Страница 35: ...33 80 15 16 H R290 R32...
Страница 36: ...34 Power 35 85 5 Up Down 0 0 24 key pads Fan High Normal High Normal FAN 1 2 3 5 4 6...
Страница 37: ...35 35 85 0 24 5 35 90 S 3 3 3 45 55 5 2 Timer Timer off imer on Timer Timer Timer off U DOWN 24 5 0 0 2...
Страница 38: ...36 2 10 5 4 1 2 3 30 50mm A 2 3 30 50cm 30 50cm 1 2 3...
Страница 39: ...37 20001 5 1 24 5 C 35 C 3 220 240 50 z 40cm 20cm 20cm 20cm 4 20cm...
Страница 40: ...38 2 1 8 2 30 8 2 13 5mm 7 1 3 2 2 Fig 5 Fig 6 7...
Страница 41: ...39 1 2 3 30 8 11 4 1 8 10 9...
Страница 42: ...40 ES AS PI P2 5 C 41 F...
Страница 43: ...email newsletter Inventor l link QR code https www nobuklima gr egiisi nobu eggyisi 3 xronia l email A...
Страница 63: ......
Страница 64: ......