Accessories
Accessories
AX
OFF&TRIP
ON
Auxiliary contact (AX)
AX12 and AX11 are connected, AX 14 and AX11 are disconnected when the circuit breaker
is under open or free release status; AX12 and AX11 are disconnected, AX 14 and AX11 are
connected when the circuit breaker is under closing status.
Breaking and making status of circuit breaker:
Function
Electrical characteristics
Wiring diagram
Installation diagram of internal accessories
1)
QF
Power
Making
indication
Breaking
indication
L1
L2
AX11
AX14
AX12
The auxiliary contact can be connected to indicator to form a control circuit. The operator can
learn the breaking and making position of the circuit breaker without opening the distribution
cabinet.
Operating
voltage (V)
AC
DC
110
220~240
380~415
110~120
220
Operating
current (A)
AC-15
5
4
2
—
—
DC-13
—
—
—
0.25
0.25
Operating
voltage (V)
AC
DC
110
220~240
380~415
110~120
220
Operating
current (A)
AC-15
5
4
2
—
—
DC-13
—
—
—
0.25
0.25
AX12
AX11
AX14
AX12
AX11
AX14
Model
Ex9M1
Ex9M2
Ex9M3
Ex9M4
Ex9M5
Ex9M6
Installation
diagram
Maximum
number of
accessories
that can be
mounted
AX
2
2
3
4
4
2 (3)
2)
AL
1
1
1
1
1
1 (0)
2)
SHT/UVT
1
1
1
1
1
1 (1)
2)
AL
OFF&ON
TRIP
Alarm contact (AL)
The alarm contact is used to send signal in case of overload, short circuit, undervoltage or free release.
Terminals AL92 and AL91 are connected when the circuit breaker is open; terminals AL94 and AL91
are disconnected when the circuit breaker is closed; terminals AL92 and AL91 are disconnected and
terminals AL94 and AL91 are connected when the circuit breaker is in release status.
In remote control system, the DI module of PLC can receive the electrical signal sent by the alarm
contact of circuit breaker so that the PLC can detect the fault in the circuit in time. The fault signal can
be transmitted to the screen at the operation station in the control room through the communication
module of the PLC so that the operator can learn the release information of the circuit breaker.
Reasons for alarm contact to send fault indication signal:
Overload
Short circuit
Undervoltage
Manual free release
Function
Breaking and making status indication of circuit breaker:
Alarm contact
DI module
Communication module
Bus
Operation station
PLC
Power
supply
*
*
*
*
AL92
AL91
AL94
AL92
AL91
AL94
Electrical characteristics
Remote control
Wiring diagram
QF
Power
Alarm
indication
Normal
indication
L3
L4
AL91
AL94
AL92
The alarm contact can be connected to indicator and buzzer to form a fault release alarm circuit.
When the circuit breaker trips, the circuit can inform the operator in time.
Note:
1)
1P circuit breaker is not available with accessories, 2P product can be install with 1 AX and 1 AL;
2)
The number in the brackets are the number of accessories for electric version; the electric
version product can be install with 1 SHT and 1 UVT.