![Noark ASD25DC Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/noark/asd25dc/asd25dc_user-manual_1697700018.webp)
User Manual 31
User Manual 30
ASD25DC air switch disconnector control circuit reference wiring diagram
Control circuit wiring
main circuit
Auxiliary contact for user
Control power
Reference wiring diagram as following
Energy
storage
indication
Undervoltage
Opening Closing
Ready to
close
indication
C04 4 groups
C06 6 groups
N4 4NO,4NC
N6 6NO,6NC
Ready to close contact indication (optional)
9#,10#,11#: ready to close contact indication;
Signal indicator should be provided by user itself.
MD spring charge motor working power
30#, 31#, 32#: MD spring charge motor working power input;
Spring chargr indicator should be provided by user itself.
UVT undervoltage relasse (optional)
33#, 34#: UVT undervoltage release working power input;
SB3 emergency disconnecting button should be provided by user
itself.
Undervoltage release is within special order range, wiring are not
provided for regular supply.
SHT shunt release
35#, 36#: SHT shunt release working power input, if DC working
voltage is used, 35# is positive pole, 36# is negative pole. SB1
opening button should be provided by user itself.
XF shunt release
37#, 38#: XF closing coil working power input, if DC working voltage
is used, 37# is positive pole, 38# is negative pole. SB2 closing button
should be provided by user itself.
AX1 - AX6 auxiliary contacts
39# - 62# (AX1 - AX6): C04 for regular suuply, C06
、
N4
、
N6 for
specially ordered.
http://na.noark-electric.com
ZASD25DC202208UL