NOAH ACTUATION SA003 Series Скачать руководство пользователя страница 8

8

Emico Noah

NOAH ACTUATION CO.,LTD.

10. Manual Operation

11. Limit Switch Setting

11-1

Cam Switch Calibration

10-1 Remove the manual sealing bolt using

the wrench attached on the bottom of the actuator.

10-2 Turn the wrench to the clock wise for opening and

count clock wiser for closing inserting the wrench. 

10-3 Screw up the manual sealing bolt to protect the actuator 

from leakage and put the wrench in its regular place 

after use not to lose.  

11-1-1

Loosen the close cam set screw and rotate the

cam in a clockwise direction to actuate the close

limit switch.  Also, the close auxiliary switch cam

can be adjusted at this way too. 

11-1-2

Firmly tighten the cam set screws.

11-1-3

To set the open cam switches, repeat the previous instructions except rotate the actuator to the open, 

counter clockwise position and rotate the open cams in the counter clockwise direction to actuate

the open switches.

ACLS

AOLS

OLS

CLS

Dry Open Limit Switch

Dry Close Limit Switch

Open Limit Switch

※ L-wrench Size: 2.5mm

Close Limit Switch

AOLS

OLS

ACLS

CLS

Содержание SA003 Series

Страница 1: ......

Страница 2: ...rify the nameplate information to insure the correct model number torque voltage and enclosure type Be sure to completely review the actuator manual prior to operation Final limit switch adjustment must be done after mounting the actuator to the valve Incorrect adjustment may cause actuator failure Over torque switches are factory set Tampering with the over torque switch settings may damage the a...

Страница 3: ...or 18 5 Storage Temperature Temperature 20 70 IP67 Weatherproof 3 Actuator Specification The actuator must be stored in a clean dry and temperature controlled area The actuator shall be stored with the cover installed and with the conduit openings sealed Storage must be off the floor Care must be taken to guard the actuator from condensation during extreme temperature variation The heater should b...

Страница 4: ... Type With LED illumination 6mm hexagon L wrench handle included 2 x 3W 2 PF1 2 Option 2 M20x1 5 2 NPT1 2 Shell Gadus S2 V220 2 Aluminium alloy Anodizing Polyester TGIC free MODEL MAIN POWER OUTPUT TORQUE OPERATING TIME 90 NUMBER OF HANDLE TURNS WEIGHT Kg m N m 50Hz 60Hz kg SA003 3 30 in lb 261 17sec 15sec 15sec 7 5 1 7 lb 3 8 AC 120V AC 110V AC 230V AC 220V AC 24V DC 24V 47 40 36 33 23 35 MODEL M...

Страница 5: ...5 Emico Noah SA SERIES MANUAL 6 Exterior Parts Identification Top Cover Top Cover Bolts Cable entries Earth Body Base L Wrench Manual Sealing Bolt Window ...

Страница 6: ... CO LTD 7 Interior Parts Identification Full Open Close LED Lamp Terminal Earth Motor Control Board Heater 2EA Indicator Micro Switch Auxilliary Open Limit Switch Auxilliary Close Limit Switch Close Limit Switch Open Limit Switch ...

Страница 7: ...alve drive inserts are available or complete mounting kits can be supplied as request Mounting Base B C D ISO 5211 F03 Φ36 M5TAP DP8 ISO 5211 F04 Φ42 M5TAP DP10 ISO 5211 F05 Φ50 M6TAP DP10 9 Actuator Installation Model A mm Ground A SA003 80 When installing the actuator proper clearance around the actuator is required to ensure Drive Insert Option 11 DP20 ...

Страница 8: ... place after use not to lose 11 1 1 Loosen the close cam set screw and rotate the cam in a clockwise direction to actuate the close limit switch Also the close auxiliary switch cam can be adjusted at this way too 11 1 2 Firmly tighten the cam set screws 11 1 3 To set the open cam switches repeat the previous instructions except rotate the actuator to the open counter clockwise position and rotate ...

Страница 9: ...here maybe some differences as to the thread and pitch standards Check with your supplier to confirm which standard is supplied in your area Standard conduit and conduit seal fittings may be used when installing and wiring the actuator To prevent moisture and humidity from entering the actuator it is highly recommended that a seal fitting be installed in the actuator conduit entry After all the co...

Страница 10: ...ide of the actuator body 14 5 Be sure to wire and energize the heater as shown in the wiring diagram 14 6 Each actuator must be powered by their own individual relays to prevent voltage feedback and actuator damage 14 7 After the wiring is completed in the actuator use wire ties to group the wires together and clean up their appearance Be certain that the wires are secure and away from any moving ...

Страница 11: ...ed by misuse or abuse 17 Warranty One year limited warranty from the factory release date Failure or damage caused by unauthorized modifications or repairs done to the actuator Failure caused by the unauthorized modification change or the wiring Failure caused by water entering the actuator due to improper sealing of the cable entries Failure caused by improperly set limit switches Failure caused ...

Страница 12: ...n Limit Switch 250VAC 3A ACLS Aux Close Limit Switch 250VAC 3A AOLS Aux Open Limit Switch 250VAC 3A NOAH ACTUATION CO LTD 12 http www emico co kr SA003 BASE 11 20 9 130 50 114 132 5 80 Cable Entries Option 1 2 M20x1 5 2 2 NPT1 2 2 PF1 2 11 DP20 Drive Insert Option ...