WIRING (DO NOT WIRE HOT)

USER BUTTON

On the side of the controller is a lighted user button.  This button can be used for testing and re-programming purposes.

User Button (also functions as LED 

indicator) 

UL924 Test (ER model only)

Use this test to confirm that the lighting load is properly connected and 

provides the necessary output in event of loss of power.

1. Press and Release the button.

2. Relay will close and dimming output will go to full brightness for 4 

seconds.

3. After 4 seconds expires, the device returns to its previous state and the 

indicator LED shuts off.

LED Diagnostics

The LED is illuminated whenever the button is depressed, and blinks to 

confirm the start of maintenance mode. Depress the button from the side to 

view LED and confirm that the device is operational.

Maintenance Mode 

Use this mode if you are unable to Identify this device within the Clairity Pro application.

1. Press and hold button for 10 seconds, then release. LED will begin to flash rapidly 

after 10 seconds and stop flashing when the button is released.

2. Immediately press and hold button again for 10 seconds, then release. LED will 

begin to flash rapidly after 10 seconds and stop flashing when the button is released.

3. The LED will flash twice to confirm entry into Maintenance Mode.

For 60 minutes, the device becomes identifiable in the Clairity Pro app and available 

for direct connection from mobile app to device (without requiring Group Monitor to be 

present, in case of a fault or connectivity issue with the Group Monitor).

Clairity Pro can then be used to perform functions such as:

* Reprogram device settings

* Reset device network settings

* Firmware update

* General troubleshooting and diagnostic functions

UL924 Sequence of Operation

ER Units: 

When normal power sense leads 

have absense of voltage

EM Units: 

For 90 minutes following any 

complete AC power interruption 30 ms:

•  Relay is closed and 0-10V dimming is at high 

end trim level

•  Device ignores wireless lighting control 

commands

•  24VDC output is disabled

Do NOT wire while connected to live power,

damage may occur.

 

Legend

BLK – Unswitched Hot 120-277V
WHT – Neutral
BLU – Switched Output
VIO – 0-10V Dim
GRY – 0-10V Common
RED (Terminal) – +24VDC
BLK (Terminal) – DC Common
GRN – Ground

RPP 24V

RPP 24V

LOAD

}

Normal

+24 VDC

}

 

Legend

BLK – Unswitched Hot 120-277V
WHT – Neutral
BLU – Switched Output
VIO – 0-10V Dim
GRY – 0-10V Common
RED (Terminal) – +24VDC
BLK (Terminal) – DC Common
GRN – Ground

RPP DS 24V

RPP DS 24V

LOAD

}

Normal

+24 VDC

}

RPP DS 24V EM 

120 V - 
277 V

EMERGENCY

0-10 VDC Ballast 

or LED Driver

}

RPP  D/DS 24V EM

Emergency

 

Legend

BLK– 120-277VAC Emergency Hot
WHT – Emergency Neutral
BLU– Switched Output
VIO – 0-10V Dimming (+)
GRY – 0-10V Common (-)
GRN – Ground

RED (Terminal) – +24VDC
BLK (Terminal) – DC Common

+24 VDC

}

RPP DS 24V ER

120 V - 
277 V

}

Normal

EMERGENCY

0-10 VDC Ballast 

or LED Driver

}

Emergency

RPP D/DS 24V ER

 

Legend

RED – 120-277VAC Emer. Hot
WHT/RED – Emer. Neutral
BLK – Unswitched Norm. Hot
WHT – Norm. Neutral
BLU – Switched Output
VIO – 0-10V Dim (+)
GRY – 0-10V Com (-)
RED (Terminal) - +24VDC
BLK (Terminal) - DC Com
GRN – Ground
               - Optional Test Switch
                  (by others)

+24 VDC

}

Legend

RED – 120-277VAC Emergency Hot
WHT/RED – Emergency Neutral
BLK – Unswitched Norm. Hot

*

WHT – Norm. Neutral

*

BLU – Switched Output
VIO – 0-10V Dim (+)
GRY – 0-10V Com (-)
RED (Terminal) - +24VDC
BLK (Terminal) - DC Com
GRN – Ground
               - Optional Test Switch
                  (by others)

*

 Emergency on EM devices

USING 24 VDC TERMINALS (24V models only)

Strip jacket to correct length, then 
insert firmly into terminal hole.
Gently pull to confirm that terminal 
has securely captured wirelead.

Strip length: 3/8”
Solid or tinned 
leads only
16-20 AWG

Connecting Wire to 24V Terminals

1.

2.

Max screwdriver size: 2mm

Insert precision slotted 
screwdriver into terminal slot.
Gently press screwdriver into 
terminal, then gently pull wire 
to remove.

Removing Wire from 24V Terminals