nLight 876599 Скачать руководство пользователя страница 3

3 of 3

nPP16 ER EFP 

UL-924 EMER. RELAY PACK

FAMILY

 

INSTRUCTIONS

Acuity Brands | One Lithonia Way Conyers, GA 30012  Phone: 800.535.2465   www.acuitycontrols.com   © 2018 Acuity Brands Lighting, Inc.   All rights reserved.   Rev. 

01/26/2019

 

IS-NPP16ER-EFP-00

4

A-LEVEL PROGRAMMING INSTRUCTIONS

Please read all 3 steps before programming
1. Enter a specific programming function by pressing button the number

of times as the desired function number from the A-Level Detailed  

Function Tables (e.g., press 23 times for function 23, Occupied Bright 

Level).

2. LED will flash back the selected function’s current setting (e.g.,

11 times for 100%). To change setting, proceed to step 3 before flash 

back sequence repeats 3 times. To exit the current function or to

change to a different function, wait for sequence to repeat 3 times 

then return to step 1.

3. Press button the number of times indicated in the particular function’s 

detailed table for the NEW desired setting. As confirmation of setting 

change, LED flashes back the NEW setting  3 times before exiting.

 

27 

 

=  Relay Always On

Forces relay to stay closed even in off state 

            1 

 

 

No*

  Yes      

28 

 

=  Dimming Always On

Maintains unoccupied dim level when in off state. Does not affect relay. 

           

      1 

 

 

No*

  Yes      

29 

 

=  Occupancy Expiration of Manual Off

 

When enabled, operation of device will revert from a push-button 

triggered override off state to Normal mode once the Occupancy Time Delay 

(adjustable via SensorView or push-button) expires. Not used with Manual 

On operating modes.

            1 

 

 

Disable*

  Enable  

Operational settings can be changed via the push-button sequence outlined below and right. Addtional settings can also be configured via SensorView software.  

A-LEVEL DETAILED FUNCTION TABLES

17

  

=  Secondary 

 

Zone Dimming Offset

Percentage voltage difference of unit’s dimming output from primary 

dimming output (Function 26, Follow Photocell Mode, must be 

enabled)

1   

-

 

100%

8    

-30%               

15    

40%

      

2

   - 90%

9    

-20%              

 16    

50%

3

   - 80%

10

   -10%              

  

17 

   60% 

      

4   

- 70%

11

     0%*               

18

    70%

      

5

   -60%

12    

10%                

19

     80%

      

6

   -50%

13

    20%                

20 

    90%

      

7

   -40%

 14  

  30%                

21

    100%

23 

 

=  Occupied Bright Level

 

The percentage of the controllable dimming range that the dimming 

output rises to when occupancy is detected. Setting is not applicable 

if Follow Photocell Mode is enabled. Note: Adjusting the dim level 

using a WallPod changes this setting when Follow Photocell Mode 

is disabled.

1%

  40%      

  

9   

80%

2

 10% 

 

 

50%      

10  

90%

3

 20% 

7

   60%      

11 

    100%*  

4

 30% 

8

   70%

24 

 

=  Unoccupied Dim Level

 

The percentage of the controllable dimming range that a dimming 

output drops the lights to after the Idle Time Until Dim timer expires

1%*

  40%      

  

9   

80%

2

 10% 

 

 

50%      

10  

90%

3

 20% 

7

   60%      

11 

    100%                

4

 30% 

8

   70%

26 

 

=  Follow Photocell Mode

 

Directs how a device’s dimming output reacts relative to a  photocell 

(ADC)

  

 

 

Disable*       

  Enabled (- only)        

3   

E/-

B-LEVEL PROGRAMMING INSTRUCTIONS

Please read all 4 steps before programming
1. Enter B-Level programming mode by holding down button until LED 

flashes  rapidly,  release,  hold  down  until  rapid  flash  again,  release,  then

immediately enter programming function as described in step 2.

2. Enter a programming function by pressing button the number of 

times as the desired function number from the table labeled B-Level 

Functions (e.g., 12 times for function 12, Occupancy Tracking Channel).

3. LED will flash back the selected function’s current setting (e.g., 1 flash 

for channel 1). To change setting, proceed to step 4 before flash 

back sequence repeats 3 times. To exit the current function or to 

change to a different function, wait for sequence to repeat 3 times 

then return to step 1.

4. Press button the number of times indicated in the particular function’s 

detailed table for the NEW desired setting (e.g., press 2 times for channel

2).  As confirmation of setting change, LED flashes back the NEW setting 3 

times before exiting.

B-LEVEL DETAILED FUNCTION TABLES

12 

 

=  Occupancy Tracking Channel

The local channel on which a device’s relay and/or dimming output 

receives occupancy information

 

  1 - 16

 (e.g., 

1

 = Channel 1*, 

2

 = Channel 2; etc.)

14 

 

=  Photocell Tracking Channel

The local channel on which a device’s relay and/or dimming output 

receives photocell information

 

  1 - 16

 (e.g., 

1

 = Channel 1*, 

2

 = Channel 2; etc.)

16 

 

=  Switch Tracking Channel

The local channel on which a device’s relay and/or dimming output 

receives switch information.  

 

  1 - 16

 (e.g., 

1

 = Channel 1*, 

2

 = Channel 2; etc.)

Note: Normal default is channel 1, units with SW2 and SA2 options are 

defaulted to channel 2

17 

 

=  Override (Relay / Dimming)

Indicates whether a device’s relay is forced on/off and/or dimming 

output is forced to max/min

1  

 Not  forced*      

2

   Override On     

3

   Override Off

18 

 

=  Special Operating Mode

Unique defined behaviors of relays and/or dimming outputs, see right 

for function definitions

     1 

 

 

Normal*

 

 

Predictive Off

     2

   Manual On 

6

      Manual  to  Override  On              

     3

   Auto to Override On             

7

   

Manual to Normal      

     4 

  Manual to Full Auto On

        

19 

 

=  Invert Relay Logic

Reverses functionality of relays

   

 

 

Normal Logic*            

2

   Inverse Logic   

21 

 

=  WallPod Dimming Adjustments

 

Defines whether user dimming adjustments are maintained after 

lights are cycled, whether they revert to default levels, or whether they 

temporarily disable a connected dimming photocell (until lights cycle)

 

 

Permanent*       

  Temporary      

3   

Photocell Temp  

Override 

22 

 

=  Maintain Dim Level when Vacant

 

Prevents lights from turning fully off once in unoccupied state

            1 

 

 

No*

  Yes     

23 

 

=  Special Switch Tracking Mode

 

Defines unique behavior related to how relays respond to particular 

switch information

            1 

 

 

Disable*

  Ignore Ons 

            2

   Ignore Offs 

 

 

Ignore Ons & Offs  

31 

 

=  High End Trim**

 

Maximum voltage level of the device’s dimming output. Commonly used for 

task tuning where absolute light level is not to be increased via a Wallpod 

or scene. When output is at high end trim, the reported control percentage 

will be 100%. Corresponding lumen output % is dependent on ballast/

driver capabilities.

 

 

0.7 V            

  3V               

  

7   

6V 

10

   9V 

      

2

   1V 

 

 

4V 

  

8   

7V 

11

   10V

3

   2V 

6

   5V    

  

9

  8V

32 

 

=  Low End Trim**

 

Minimum voltage level of the device’s active dimming range. Level can not 

be reduced via a WallPod or scene.  When output is at low end trim, the 

reported control percentage will be 1%. Corresponding lumen output % is 

dependent on ballast/driver capabilities.

 

 

0.7 V            

  3V               

  

7   

6V 

10

   9V 

      

2

   1V 

 

 

4V 

  

8   

7V 

11

   10V

3

   2V 

6

   5V    

  

9

  8V

** Setting precision of 0.1V is available via SensorView. Device status LED 

blinks out current value rounded to nearest selection above.

FUNCTION 18 DEFINITIONS

NORMAL

Operating Mode where occupancy sensors are capable of turning lights 

both on/off

AUTO TO OVERRIDE ON

Special Mode where lights are turned on initially by occupant detection but 

then left in the Override On state

MANUAL ON TO FULL AUTO

Special Mode that initially requires the occupant to manually turn on the 

lights, after which the sensor assumes full on/off control

MANUAL ON

Special Mode that always requires the occupant to manually turn the 

lights on, while having them turn off automatically by a sensor (default on 

models with SA and SA2 options)

PREDICTIVE OFF

When lights are switched off, this Special Mode determines whether 

occupants remained or left the room, so as to leave the lights in either the 

Override Off or Auto On state

MANUAL TO TIMED OVERRIDE ON

Special Mode where lights are initially turned on manually but remain in 

the Override On state for a pre-determined period (Timed Override Delay)

MANUAL TO NORMAL

Special Mode where lights are initially turned on manually but remain in 

the Normal State (enabling auto-dimming) for a pre-determined period 

(Timed Override Delay)

* indicates default setting for base 

nPP16 (D) ER EFP models.

NOTE

For further troubleshooting guidance, please contact the Controls Technical Support Team 

1(800)-535-2465

Содержание 876599

Страница 1: ...us voltage Class Rating 0 10V Dimming can be wired Class 1 or 2 Standards Ratings Energy Management Equipment UL916 E167435 Emergency Lighting and Power Equipment UL924 E342232 Mechanical Dimensions 3 38 H x 2 53 W x 1 83 D 86mm x 64mm x 47mm does not include chase nipple Mounting 1 2 Knockout 7 8 hole Color Red Connection Type RJ 45 nLight Network Ports 2 Non Dimming Model Line Voltage Leads Dimm...

Страница 2: ...277V Emer Hot RED Emer Hot Switched In BLU Emer Load Switched Out BLK Norm Hot WHT Norm Neutral nPP16 ER EFP Normal sense only OPTIONAL TEST SWITCH RED Emergency WHT RED YEL RED YEL YEL RED YEL CAT 5e LEGEND WHT RED Emer Neutral YEL 120V Emer Hot RED YEL 277V Emer Hot RED Emer Hot Switched In BLU Emer Load Switched Out BLK Norm Hot WHT Norm Neutral VIO 0 10V Dim GRY 0 10V Com GRN Earth Ground nPP1...

Страница 3: ...d setting e g press 2 times for channel 2 As confirmation of setting change LED flashes back the NEW setting 3 times before exiting B LEVEL DETAILED FUNCTION TABLES 12 Occupancy Tracking Channel Thelocalchannelonwhichadevice srelayand ordimmingoutput receivesoccupancyinformation 1 16 e g 1 Channel 1 2 Channel 2 etc 14 Photocell Tracking Channel Thelocalchannelonwhichadevice srelayand ordimmingoutp...

Страница 4: ...erte lesionespersonalesodañoalapropiedadquepuedasurgirdeincendios descargaseléctricas caídadepartes cortes abrasionesyotrospeligrosleatodaslasadvertenciaseinstrucciones incluidas en la caja o su interior además de las etiquetas de montaje Antes de instalar reparar o realizar el mantenimiento de rutina en este equipo siga estas precauciones generales La instalación y la reparación deben estar a car...

Страница 5: ...e Prueba Opcional CAT 5e LEYENDA BLANCO ROJO Emergencia Neutro AMARILLO 120V Emergencia ROJO caliente AMARILLO 277V Emergencia Caliente ROJO Emergencia Caliente Conectado AZUL Emergencia Carga Desconectado NEGRO Normal BLANCO caliente Normal Neutro VIOLETA 0 10V Atenuación GRIS 0 10V Com VERDE Tierra nPP16 ER EFP Emergencia 0 10balastro VDCo controlador LED VIOLETA GRIS VERDE NEGRO BLANCO BLANCO R...

Страница 6: ...pación Elcanallocalenelqueelrelédeldispositivoolasalidadeatenuación recibeinformacióndelaocupación 1 16 por ejemplo 1 Canal 1 2 Canal 2 etc 14 Canal de seguimiento de fotocélulas Elcanallocalenelqueelrelédeldispositivoolasalidadeatenuación recibeinformacióndelafotocélula 1 16 por ejemplo 1 Canal 1 2 Canal 2 etc 16 Canal de seguimiento del interruptor Elcanallocalenelqueelrelédeldispositivoolasalid...

Страница 7: ...s et instructions compris dans et sur la boîte de la fixation ainsi que toutes ses étiquettes Avant l installation ou l entretien particulier ou de routine de cet équipement tenir compte de ces précautions générales L installation et les réparations ne doivent être effectués que par un électricien diplômé et qualifié L entretiendoitêtreeffectuépardespersonnesqualifiéesquiconnaissentbienlafabricati...

Страница 8: ...nce JAU ROU JAU BLC NOI BLC ROU BLE Commutateur de Test Optionnel CAT 5e LÉGENDE BLC ROU urgence Neutre JAU 120 V urgence ROU JAU chaud 277 V urgence Chaud ROU urgence Chaud connecté BLE urgence Charger déconnecté NOI Norm BLC chaud Norm Neutre VIO 0 10 V Grad GRI 0 10 V Com VER mise à la terre nPP16 ER EFP Urgence Ballastou circuitDEL 0 10VCC VIO GRI VER NOI BLC BLC ROU JAU ROU JAU ROU BLE Normal...

Страница 9: ...nrelaisd appareilouunesortiedegradation reçoitl informationd occupation 1 à 16 ex 1 canal 1 2 canal 2 etc 14 canalderepéragederécepteurphotoélectrique Canallocalsurlequelunrelaisd appareilouunesortiedegradation reçoitl informationderécepteurphotoélectrique 1 à 16 ex 1 canal 1 2 canal 2 etc 16 canal de repérage d interrupteur Canallocalsurlequelunrelaisd appareilouunesortiedegradation reçoitl infor...

Отзывы: