Operation mode Description
LCD display
Warning mode
The UPS is
warning because of
overload.
Fault mode
The UPS goes to
fault mode because
output is short.
*Please check ID
event descriptions
table for complete
list of fault errors.
5.4 LCD settings configuration
There are 5 UPS settings that can be configured by the user.
1. Press and hold the “
ENTER
” button for 5 seconds to activate the
setting mode.
The first configuration parameter will be displayed on the LCD screen.
Note: The manual settings programming mode can ONLY be
invoked while UPS is in Bypass mode or Standby mode. To make
UPS on Standby mode or Bypass mode, connect utility power to
UPS and do not turn on UPS.
2. Press the “
ENTER
” button to select the setting you want to
configure.
3.
Press the “
ESC
” buttons to scroll through the different parameters
and select the parameter you want.
4.
Press the “
ESC
” button for 5 seconds to cancel and exit setting
mode. Press the “
ENTER
” button for 5 seconds to save all the
settings you just do and exit setting mode.
Setting
item
Configure
Submenu
Available
Settings
Default
Setting
LCD Display
001
Output
Voltage
= [208V]
[220V]
[230V]
[240V]
230V
002
Output
Frequency
= [50Hz]
[60Hz]
50Hz