Operating mode Description
LCD display
Online mode
When the input voltage is
within acceptable range,
UPS will provide pure
and stable AC power to
output. The UPS will also
charge the battery in
online mode.
23 0
INPUT
Vac
23 0
OUTPUT
Vac
P1
ECO mode
Energy saving mode:
When the input voltage is
within voltage regulation
range, UPS will bypass
voltage to output for
energy saving. The UPS
will also charge the
battery at ECO mode.
23 0
INPUT
Vac
23 0
OUTPUT
Vac
P1
Frequency
Converter mode
When input frequency is
within 40 Hz to 70 Hz,
the UPS can be set at a
constant output frequency,
50 Hz or 60 Hz. The UPS
will still charge battery
under this mode. The
capacity of the UPS should
be derated to 80% when
Frequency Converter
mode is enabled.
23 0
INPUT
Vac
23 0
OUTPUT
Vac
P1
Battery mode
When the input voltage
is beyond the acceptable
range or power failure, the
UPS will backup power
from battery and alarm is
sounding every 5 seconds.
7 2 0
INPUT
Vdc
23 0
OUTPUT
Vac
P1
Bypass mode
When input voltage is
within acceptable range
but UPS is overload, UPS
will enter bypass mode
or bypass mode can be
set by front panel. Alarm
is sounding every 10
seconds.
23 0
INPUT
Vac
23 0
OUTPUT
Vac
P1
Standby mode
UPS is powered off and
there is no output supply
power, but the UPS still
can charge batteries.
23 0
INPUT
Vac
0
OUTPUT
Vac
Fault mode
When a fault has
occurred, the ERROR icon
and the fault code will be
displayed.
INPUT
Vac
0
OUTPUT
Vac
Fault event
Fault code
Icon
Bus start fail
01
-
Bus over
02
-
Bus under
03
-
Inverter soft start fail
11
-
Inverter voltage high
12
-
Inverter voltage Low
13
-
Inverter output short
14
Battery voltage too high
27
Battery voltage too low
28
Charger output short
2A
-
Over temperature
41
-
Overload
43
Charger failure
45
-
Over input current
49
-
5.6 Operating mode description
5.7 Faults Reference Code