WARING
Danger of injury!
The simulation of OCM F outputs will access any following facility areas with-
out any safety locking measures!
Simulations are allowed to be executed exclusively by NIVUS expert person-
nel or by expert companies trained by NIVUS in cooperation with experienced
users. Be sure to always observe safety precautions!
WARING
Make sure to have a safety person available
The simulation of analog inputs and outputs is allowed to be carried out by
specialist electricians only who have sound knowledge on the control system
of the facility. This requires detailed preparation.
It is absolutely necessary to have a safety person available!
The following system must be set to manual operation mode. Actuators or
similar have to be disabled if possible or have to be functionally restricted in a
way not to cause any damage.
Simulation
It is possible to simulate a free adjustable analog output current on the 3 ana-
log outputs. Select the desired analog output with the >right< or >left< keys.
After entering the PIN code >2718< you can increase or decrease the mA val-
ue in steps of 0.01 mA using the >up< or >down< keys during simulation. Fur-
thermore it is possible to directly enter desired values to simulate by pressing
ENTER. A maximum output current of 20.475 mA can be simulated
(see Fig. 9-79).
Fig. 9-79
Simulation of analog outputs