NFP - rev. 04 / 23.05.2018
Check the nameplate for correct specification of the power supply.
The EU-Type examination certificate (incl. appendix) and the declaration of
conformity are located at the end of the manual.
Fig. 14-1
Nameplates AC/DC (Ex versions)
15
Specifications
Power supply
100…240 V AC, +10 % / -15 %, 47…63 Hz
24 V DC, ±15 %, 5 % residual fluctuation
Power consumption
AC: max. 18 VA, typ. 7 VA
DC: max. 15 W, typ. 6 W
Wall mount enclosure
Material: Polycarbonate
Weight:
approx. 1200 g
Protection
IP65
Operating conditions
Protection class I
Overvoltage category II
Pollution degree 2
Altitude
AC unit for use in altitudes up to 3000 m above MSL.
At relay voltages >150 V the use is restricted to an altitude
of max. 2000 m (AC and DC units)
Operating temperature
-20…+60 °C / for Ex: -20…+40 °C
Storage temperature
-30…+70 °C
Max. humidity
90 %, non-condensing
Display
Back-lit full graphic LCD, 128x64 pixel
Operation
6 keys, menu driven in German, English, French and Polish
Inputs
1x digital input
1x flow velocity pipe sensor type POA connectable
Outputs
1/3x 0/4…20 mA, load 500 Ohm, 12 bit resolution,
accuracy 0,1 % (after calibration)
2x relays SPDT, maximum load 230 V AC / 2 A (cos.
ϕ
0,9)
Data memory
4 MB, 64512 data points, for programming and readings
memory; read-out via front-side USB stick
Storage cycle
1 minute to 1 hour
Ex approval (option)
II (2) G [Ex ib Gb] IIB
Содержание NFP
Страница 82: ...Instruction Manual NIVUS Full Pipe page 82 NFP rev 04 23 05 2018 Approvals and certificates...
Страница 83: ...Approvals and certificates NFP rev 04 23 05 2018 page 83...
Страница 84: ...Instruction Manual NIVUS Full Pipe page 84 NFP rev 04 23 05 2018...
Страница 85: ...Approvals and certificates NFP rev 04 23 05 2018 page 85...
Страница 86: ...Instruction Manual NIVUS Full Pipe page 86 NFP rev 04 23 05 2018...
Страница 87: ...Approvals and certificates NFP rev 04 23 05 2018 page 87...