Menu 7 - Switch-on point / lowest set point SP 2 

 

Via the menu “Switch-on point / lowest set point” it is possible to define the switch-on point of the pressure switch (contact 2). Setup mode is 
entered by pressing both buttons simultaneously. You can set the required value by using the buttons “▲“ or “▼“. To complete the setting 
push the two buttons simultaneously. 

Menu 8 - Switch-off point / highest set point SP 2 

 

Via the menu “Switch-off point / highest set point” it is possible to define the switch-off point of the pressure switch (contact 2). Setup mode is 
entered by pressing both buttons simultaneously. You can set the required value by using the buttons “▲“ or “▼“. To complete the setting 
push the two buttons simultaneously. 

Menu 9 - Set point negation SP 1 

 

Via the menu “Set point negation“ it is possible to invert the output signal of set point 1. Setup mode is entered by pressing both buttons 
simultaneously. To select between standard (not inverted) signal (S1St) and inverted signal (S1In) it is necessary to press one of both buttons 
until the desired function is displayed. To finish the configuration and to store the selection it is required to press both buttons simultaneously. 

Menu 10 - Set point negation SP 2 

 

Via the menu “Set point negation“ it is possible to invert the output signal of set point 2. Setup mode is entered by pressing both buttons 
simultaneously. To select between standard (not inverted) signal (S2St) and inverted signal (S2In) it is necessary to press one of both buttons 
until the desired function is displayed. To finish the configuration and to store the selection it is required to press both buttons simultaneously. 

Menu 11 – Switch on delay SP 1 

 

Via the menu “Switch-on delay“ it is possible to set the delay time of set point 1. Setup mode is entered by pressing both buttons 
simultaneously. You can set the required value by using the buttons “▲“ or “▼“. The delay time can be set between 0.01 and 90 seconds.  
To complete the setting push the two buttons simultaneously. 

Menu 12 – Switch off delay SP 1 

 

Via the menu “Switch-off delay“ it is possible to set the delay time of set point 1. Setup mode is entered by pressing both buttons 
simultaneously. You can set the required value by using the buttons “▲“ or “▼“.The delay time can be set between 0.01 and 90 seconds. To 
complete the setting push the two buttons simultaneously. 

Menu 13 – Switch on delay SP 2 

 

Via the menu “Switch-on delay“ it is possible to set the delay time of set point 2. Setup mode is entered by pressing both buttons 
simultaneously. You can set the required value by using the buttons “▲“ or “▼“.The delay time can be set between 0.01 and 90 seconds. To 
complete the setting push the two buttons simultaneously. 

 

Содержание NIPRESS P6

Страница 1: ...Manufacturer H 1043 Budapest Dugonics u 11 Phone 36 1 889 0100 Fax 36 1 889 0200 sales NIVELCO Process Control Co E mail nivelco com www nivelco com NIPRESS P6 programming device...

Страница 2: ...NSTALLATION AND WIRING 3 2 1 GENERAL NOTES 3 2 2 STEPS OF INSTALLATION 3 2 3 WIRING 4 2 4 DIMENSIONS 5 3 PROGRAMMING 6 3 1 OPERATING AND DISPLAY MODULE 6 3 2 CONFIGURATION 6 3 3 STRUCTURE OF THE MENU...

Страница 3: ...rogramming device P6 with integrated cable operating manual 2 INSTALLATION AND WIRING 2 1 GENERAL NOTES Please note that this device is a sensitive programming kit Handle the device carefully so that...

Страница 4: ...e plug on the programming device Female plug on end of cable for DK 100 M 8 x 1 4 pin plastic for DK 200 M 12 x 1 5 pin plastic for DK 100 M 8 x 1 4 pin plastic for DK 200 M 12 x 1 5 pin plastic Suppl...

Страница 5: ...jbdp612a0600p_02 5 12 2 4 DIMENSIONS Programming device P6 front and side view Programming device P6 view from above...

Страница 6: ...help of two miniature push buttons located in the front button with this button you move forward in the menu system or increase the displayed value button with this button you move back in the menu s...

Страница 7: ...PS Switching mode of contact 1 Menu 3 H 1 y CP 1 Switching mode of contact 1 Menu H 4 y 2 CP2 Contact 1 n o 5 S1on Menu Contact 1 ff o 6 S1of Menu Contact 2 n o 7 S2on Menu Contact 2 off S2o Menu 8 f...

Страница 8: ...h buttons simultaneously setup mode is entered To select the desired function it is necessary to press or buttons until the desired function is displayed To finish the configuration and to store the s...

Страница 9: ...t negation it is possible to invert the output signal of set point 2 Setup mode is entered by pressing both buttons simultaneously To select between standard not inverted signal S2St and inverted sign...

Страница 10: ...ch on point 2 For the teaching operation you have to push both buttons simultaneously Then ref will appear in the display and you have to connect the reference pressure on the pressure port of the swi...

Страница 11: ...2 Showing the low limit of the measuring range When the menu Lo r is active it is possible to display the low limit of the measuring range of the pressure switch The low limit is displayed for two sec...

Страница 12: ...sible dirt deposited should be cleaned off All repairs will be carried out at the Manufacturer s premises 5 WARRANTY NIVELCO provides warranty of 3 three years in compliance with details described in...

Отзывы: