dkc3127a0600p_01 - 19/20 

Menu 35 – Error signal definition (only 4

 – 

20 mA / 3-wire adjustable)

 

 

Set the desired error signal (this is given out in case of a defect).  

Permissible options:  
"0FF" (no error signal), "C 0" (0 mA or 0 V), "C L0" (3.5 mA or 1.75 V) and "C HI" (23 mA or 
11.5 V). The error message appears only when Menu 6 "HILo" is set to "on". 

 

Menu 36 – Offset compensation / position correction  
(only 4

 – 

20 mA / 3-wire adjustable) 

 

Enter the POSI menu; if offset 

 ambient pressure it is necessary to place the 

device under pressure pended on mounting position (the pressure reference has to 
correspond to the zero point of the pressure measuring range); press the two buttons at the 
same time; "oF I"will be appeared on the display; press the two buttons at the same time; 
"Pro2" will be displayed; press the two buttons at the same time; the display will now show 
"o"; the reference value can now be inputted with the push buttons; the reference value is, 
for example, 5% (-0.2 bar) of the measuring range: -1 bar – 15 bar; enter 5% using the 
buttons, then press the two buttons simultaneously; the display will show "oF5". Accordingly, 

the right and stable pressure should be added to the system (-0.2 bar).  
If the measured value displayed on the display is a bad value, the operating sequence must 
be repeated.  
A position correction is required if the installation position is different from the calibration 
position (as this may cause a little deviation of the signal, so the displayed value will be 
wrong). The analogue output signal (for devices with analogue output signals) will have no 
effect; if you move the offset, the entire scale will be moved. 

 

Menu 37 – Load defaults (only 4

 – 

20 mA / 3-wire adjustable) 

 

With this menu item you can undo the previous changes and delete them. To 

reset the factory defaults, press the two buttons at the same time after entering this menu 
item. Note that any changes you have made so far will be lost, so that the password will 
return to "0005". 

 

Menu 38 –Load configuration (only 4

 – 

20 mA / 3-wire adjustable) 

 

Load configurations stored on the device (Menu 39). (Choose from 1 to 5). 

 

Menu 39 – Store configuration (only 4

 – 

20 mA / 3-wire adjustable) 

 

Store the device configuration settings. To do this, select a number from 1 to 5. 

 
 
 
 

SPECIAL MENUS: 

To access the special menu, select "PAof" with the "

" or "

" button, then press both 

buttons to activate the menu item. "1" appears on the display. 

 

Special menu 1 – Full-scale compensation 

 

Full-scale compensation is necessary if the indicated value for full scale differs 

from the real full scale value in the application; compensation is only possible with a 
respective reference source if the deviation of the measured value is within defined limits; 
set "0238"; confirm with both buttons; "FS S" will appear in the display; now it is necessary to 
place the device under pressure (the pressure must correspond to the end point of the 
pressure measuring range); press both buttons, to store the signal being emitted from the 
pressure switch as full scale; the display will show the set endpoint, although the entire 
range detection signal has been moved away. 

 

Special menu 2 – Offset compensation / position correction  
(only available for standard 2- / 3-wire and 4 – 20 mA / 2-wire Ex ia) 

 

Set "0247"; the menu description is identical with menu "P0SI" (menu 36) for  

3-wire-devices). 

 

Special menu 3 – Load defaults  
(only available for standard 2- / 3-wire and 4 – 20 mA / 2-wire Ex ia)

 

 

Set "0729". The menu item description is the same as "FAct", “Menu 37” for  

3-wire devices. 

 

Special menu 4 – Set password 

 

Set "0835"; apply the setting by pressing the two push buttons together.; "SEtP" 

appears on the display; now set the password using the 

- or 

-buttons. 

Free to choose from 0 to 9999 except for the following code numbers: 0238, 0247, 0729, 
and 0835. Finally, after setting the desired code number, you must save it by pressing the 
two buttons together. 

 

Содержание NIPRESS DK-300

Страница 1: ......

Страница 2: ...dkc3127a0600p_01 2 20 DK 300 DK 400 DK 800...

Страница 3: ...AL CONDITIONS OF SAFE USE 11 4 INSTALLATION 11 4 1 INSTALLATION INSTRUCTION 11 4 2 WIRING 12 4 3 EXAMPLES OF ARRANGEMENTS 14 5 PROGRAMMING 14 5 1 OPERATING INFORMATION 14 5 2 CONFIGURATION 14 5 3 PASS...

Страница 4: ...pressure switch with welded stainless steel flush sensor This makes it suitable for numerous applications in various industrial sectors and is also ideal for viscous or pasty media This device is a 2...

Страница 5: ...BSP C 0 0 1 0 5 1 0 5 2 2 PNP switching output 9 3 4 BSP 1 D 0 0 16 1 R 4 PNP switching output 3 E 1 4 NPT G 0 0 25 1 2 4 20 mA 2 wire 1 PNP switching output Ex ia F 1 2 NPT H 0 0 4 2 3 0 0 6 5 4 0 1...

Страница 6: ...tching output 9 1 BSP E 0 0 16 1 R 4 PNP switching output 7 E 3 4 TriClamp T 0 0 25 1 2 4 20 mA 2 wire 1 PNP F 1 TriClamp L 0 0 4 2 3 switching output Ex ia 1 1 2 TriClamp M 0 0 6 5 4 2 TriClamp N 0 1...

Страница 7: ...PNP switching output 7 1 2 BSP C 0 0 4 1 3 2 PNP switching output 9 3 4 BSP 1 D 0 0 6 2 4 4 PNP switching output 2 E 1 4 NPT G 0 1 2 5 4 20 mA 2 wire 1 PNP switching output Ex ia F 1 2 NPT H 0 1 6 4...

Страница 8: ...Output 1 PNP switch output 3 or 2 PNP switch output 3 or 4 PNP switch output 4 Analog output optional Power supply Load resistance 4 20 mA output 2 wire 13 V 36 V DC Rmax USupply 13V 0 02 A 4 20 mA o...

Страница 9: ...DC Intrinsically safe data Use only with Ex ia certified power supply module Uimax 28 V DC Iimax 93 mA Pimax 660 mW Ci 0 nF Li 0 mH Max switching current 6 70 mA Permissible temperatures for environm...

Страница 10: ...KR 4 DIN11851 hygienic connections DKV 4 VARIVENT PN 25 bar DL 4 COOLING ELEMENT 300 C 572 F Size 1 1 2 Size DN 25 DN 40 DN 50 3 3 ACCESSORIES Installation and programming manual Warranty card EU decl...

Страница 11: ...ipe wrench Due to electronic noise protection the pressure switch housing is grounded If the grounding of the technology is correct the pressure switch does not require a separate grounding Otherwise...

Страница 12: ...on of a device with cable outlet following bending radiuses have to be complied with Cable without ventilation tube static installation 5 fold cable diameter dynamic application 10 fold cable diameter...

Страница 13: ...dard 2 m PVC cable without ventilation tube permissible temperature 5 C 70 C 23 F 158 F Supply 1 1 1 white Supply 3 2 3 brown 3 wire Signal only in 3 wire 2 3 2 green Contact 1 4 3 4 grey Contact 2 5...

Страница 14: ...and provides information about the menu items The two buttons below the display are used for moving in the menu and setting the parameters Button this button allows you to move forward in the menu sys...

Страница 15: ...zero point and EP end point the analogue output can be configured The following example shows how to use these menu items According to this example your device has a measurement range of 0 400 bar So...

Страница 16: ...dkc3127a0600p_01 16 20 5 6 STRUCTURE OF THE MENUSYSTEM STRUCTURE OF THE STANDARD 2 AND 3 WIRE AND THE 4 20 mA 2 WIRE EX ia SYSTEM...

Страница 17: ...dkc3127a0600p_01 17 20 4 20 mA 3 WIRE ADJUSTABLE...

Страница 18: ...e output signal Menu 6 Exceeding message Set On or Off Menu 7 Menu 9 Menu 11 Menu 13 Set switch on points switching outputs S1 S4 Set a power on value for the relevant output S1 S2 S3 S4 outputs from...

Страница 19: ...fter entering this menu item Note that any changes you have made so far will be lost so that the password will return to 0005 Menu 38 Load configuration only 4 20 mA 3 wire adjustable Load configurati...

Страница 20: ...sary possible dirt deposited should be cleaned off The repair will be carried out at the NIVELCO premises only When dismantling the device it must always be done in the depressurized and currentless c...

Отзывы: