2.3

 

D

IMENSIONS

 

D

†

C

 

 

4

††

 

 

†

 

 

1/2

 

"

 

BSP

 FLUSH MEMBRANE

 

D

†

E

 

 

4

††

 

 

†

 

 

1”

 

BSP

 FLUSH MEMBRANE

 

DH

†

 

 

4

††

 

 

†

 

DJ

†

 

 

4

††

 

 

†

 

WITH COOLING ELEMENT

 

D

†

V

 

 

4

††

 

 

†

 

V

ARIVENT

 

DN40/50 

T

RANSMITTER WITH

 

PLK-501-2 

~33

Ø34,5

Ø26,5

33

SW 27

~6

0

15

18

1/2" BSP

 

SW 44

22

19

1" BS P

Ø50

~6

0

~33

33

Ø34 ,5

Ø26 ,5

 

Ø26,5

~3

2

 

4848

33

33

Ø34,5

Ø26,5

17

Ø64

Ø71
Ø84

 

~33

33

50

 

D

†

D

 

 

4

††

 

 

†

 

3/4" BSP 

FLUSH MEMBRANE

 

D

†

F

 

 

4

††

 

 

†

 

1 1/2" BSP 

FLUSH MEMBRANE

 

 

 

3. INSTALLATION 

Due to its small size and weight NIPRESS D-400 can be directly installed on 
tanks, pipes, machines, etc. without mounting device. 

To provide chance for replacement of the instrument during operation the use 
of closing armature is recommended. A simple ball valve will be suitable for 
lower pressures and for higher pressures (above 6 bar) a three-way blow-off 
needle-valve can be suggested.  
For measuring hydrostatic pressure for level the unit should be thread in a 
stub at the tank wall possibly near to the bottom. 
Using longer impulse tube its proper sloping for the necessary deaerating and 
emptying has to be ensured. 

Measuring low pressures in systems with substantial height difference 
between the transmitter and place of measurement the hydrostatic pressure 
of the medium in the impulse pipe should be taken into consideration. In the 
case of outside installation, the unit is supposed to be protected against rain 
or splash water. 

 

3.1 INSTALLATION REGULATION 

Depending on the medium measured, the medium may cause hazard to the 
installer, therefore you should be wearing suitable protective clothing, gloves, 
and goggles. 

For mounting and dismantling SW27 or SW44 open-end wrench should be 
used. Take care for the vulnerable flush face diaphragm. 

 

The cylindrical housing of the transmitter should not be gripped 

and tightened with pipe wrench! 

 

The plug-in electric connector can be unplugged after releasing and removing 
its fastening screw. The connection insert can be pushed out by a screw 
driver from the direction of the screw. 

Pushing electric cable through the cable gland it can be connected to the 
relevant points of the connector. Make sure that the cable gland and sealing 
plate of the connector will be tight. 

For the sake of noise suppression, the transmitter should be grounded. If the 
grounding of the appliance with the pressure transmitter is appropriate no 
further action will be needed. If not, the grounding should be performed. 

Installation steps: 

The specified tightening torques must not be exceeded! 

Tightening torques

:

 

1/4” BSP: max. 5 Nm; 1/2” BSP max. 10 Nm; 3/4” BSP: max. 15 Nm; 1” BSP: 
max. 20 Nm; 1 1/2" BSP: max. 25 Nm. 

Mounting steps for connections according to DIN 3852: 

Do not use any additional sealing material such as teflon tape! Check the o-
ring is undamaged, it has a flawless and clean surface and seated in the 
designated groove. Screw the device into the corresponding thread by hand, 
and tighten the parts with a suitable torque wrench.  

Mounting steps for dairy pipe connections (DIN11851):

 

 

Check the o-ring is undamaged, it has a flawless and clean surface and 
seated in the designated groove. 
Centre the dairy pipe connection in the counterpart. Screw the cup nut onto 
the mounting part, then tighten it using a suitable wrench. 

Mounting steps for Clamp and Varivent

£

 connections: 

Choose a suitable seal for the measured medium and pressure. Place the 
seal onto the corresponding mounting part. Centre the clamp connection or 
Varivent

£

 connection above the counterpart with seal, then fasten the device 

with a suitable fastening element (e. g. half-ring or retractable ring clamp) 
according to the supplier’s instructions. 

3.2 CONDITIONS OF SAFE OPERATION

 

Before device turn on, make sure the installation is complete, and there are 
no visible defects. The device may only be used within the limitations 
specified in the technical specifications. 
The device connector must be installed in such a way that the IP20 level of 
protection is always remain. 
Ex ia certified transmitters can only be operated in qualified, certified and 
approved galvanically isolated intrinsically safe Ex ia circuits complying with 
the technical data and the device’s explosion protection marking.  
The metal housing of the device must be connected to the EP network. 

 

D

AIRY PIPE 

DIN

 

11851 

T

RI

-C

LAMP

 

10

ØA

ØB

51

33

33

Ø34

Ø26,5

 

5

ØA

ØB

50

33

33

Ø34

Ø26,5

 

T

YPE

 

D

†

O–

4

††

†

 

D

†

P–

4

††

†

 

D

†

R–

4

††

†

 

D

†

T–

4

††

†

 

D

†

L–

4

††

†

 

D

†

M–

4

††

†

 

D

†

N–

4

††

†

 

D

IMENSIONS

 

DN 25 

DN 40 

DN 50 

3/4" 

1" 

1 1/2" 

2" 

A

 

[mm] 

23 32 45 14 23 32  45 

B

 

[mm] 

44  56 68.5 25 50.5 50.5  64 

P

N

 

[bar] 

 0.25 

 40 

 0.25 

 40 

 0.25 

 25 

 4 
 8 

 0.25 

 16 

 16 

 16 